ページ1に含まれる内容の要旨
I56-2769-003R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825Ohio A venue,St. Charles ,Illinois 60174
800/736-7672, FAX: 630/377-6495
SelectableOutput Strobes, Horns,and Hor n/Strobes
www.systemsensor.com
Foruse with the following models:P2R, P2RH,P2RK, P2RHK, P2W,P2WH, P4R, P4RH, P4RK,P4RHK, P4W , P4WH, SR, SRH, SRK,SRHK, SW, SWH, PC2R, PC2RH,
PC2RK, PC2RHK, PC2W, PC2WH,PC4R, PC4RH, PC4RK, PC4RHK, PC4W, PC4WH, SCR,SCRH, SCRK,SCRHK, SCW, S
ページ2に含まれる内容の要旨
CandelaSelection for P, S, PC,& SC series models HornSelection for P,PC, & H series models For strobe candela selection, adjust the slide switch located Horn setting selection is accomplished by using the rotary on the rear of the product while watching the viewing win- switch on the back of the product (see Table 5). The current dow under the reflector on the front of the unit. Use Table draw for various horn settings f
ページ3に含まれる内容の要旨
Table 7. 2-wireHor n/StrobeStandar d Candela Range (15–115 cd)Cur rentDraw (mA) 8–17.5 Volts 16–33 Volts DC Input 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-temporal High 141 152 91 100 116 176 201 221 229 Non-temporal Medium 133 145 75 85 102 163 187 207 216 Non-temporal Low 131 144 68 79 96 156 182 201 210 FWRInput Temporal High 136 155 88 97 112
ページ4に含まれる内容の要旨
Mounting installed using the proper SpectrAlert Advance water- tight junction box. The wall mount watertight junction Figure 6. box must be mounted with its internal post in the lower left corner as shownin Figure 8. 2. Connectfield wiring accor dingto terminal definitions. Figure 7. 3. If the product is not to be installed at this point, use the Backbo xskirt dust cover to prevent contamination of the wiring termi- modelnumber