TM
Automatic Humidifier Control
SEH-7100-000
®
by Skuttle Indoor Air Quality Products
Safety and Installation Instructions*
INSTALLER: READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE BEGINNING
INSTALLATION. (Throughout this document, the terms “Compustat” and “humidifier control”
are used interchangeably.)
WARNING: This product is for residential applications only, and must be installed by a qualified HVAC contractor.
Failure to comply could invalidate the product warrant
ページ2に含まれる内容の要旨
STEP 4: Select an Exterior Location to Mount the Outdoor Temperature Sensor Placement of the outdoor temperature sensor must meet these requirements: Figure 3 • It must be mounted on the North, Northeast or Northwest side of the house, where direct sunlight will not influence the sensor. • It must be placed at least 3 feet from all exhaust vents. • It must be installed above the expected snow line (see Figure 3). CAUTION: Incorrect indoor humidity levels will result if these require
ページ3に含まれる内容の要旨
NOTE: The humidifier control will operate properly with either a switched or continuous power source. Whether you are using accessory terminals or an external transformer, a minimum 10 VA is required STEP 9: Connecting to the Humidifier Strip the wires used for all the humidifier control terminal connections 1/4". If furnace accessory terminals are used, wire the solenoid valve directly to the “Out” terminals on the humidifier con- trol. Also attach a jumper wire to the Wire Connec
ページ4に含まれる内容の要旨
Installing the Humidifier Control to Operate Manually Figure 9 If it is not possible to use the outdoor temperature sensor, or if the homeowner wants to control the humidifier manually, Compustat can be reconfigured for manual operation. (See Figure 9.) 1. Locate the three-pin arrangement marked “AUTO/MAN”, protruding from the con- trol board (directly to the right of the wiring connections). 2. Pull upward to remove the black, two-pin connector from the auto position. Rein- stall it
ページ5に含まれる内容の要旨
Temperature/Resistance Chart 100°F 6,000 ohms 38°C 90°F 7,500 ohms 32°C 80°F 9,500 ohms 27°C 70°F 11,500 ohms 21°C 60°F 14,000 ohms 16°C 50°F 18,000 ohms 10°C 40°F 23,000 ohms 4°C 30°F 28,500 ohms -1°C 20°F 37,000 ohms -7°C 10°F 46,500 ohms -12°C 0°F 61,500 ohms -18°C -10°F 78,500 ohms -23°C -20°F 105,500 ohms -29°C -30°F 135,000 ohms -34°C For automatic applications… • Make sure the outdoor temperature sensor is mounted complete
ページ6に含まれる内容の要旨
101 Margaret Street, Marietta, OH 45750 Phone: (800) 848-9786 Fax: (740) 373-9565 Email: customerservice@skuttle.com Web: www.skuttle.com