Siemens BACNET 125-5037 user manual

User manual for the device Siemens BACNET 125-5037

Device: Siemens BACNET 125-5037
Category: Automobile Parts
Manufacturer: Siemens
Size: 0.73 MB
Added : 5/21/2013
Number of pages: 48
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Siemens BACNET 125-5037. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Siemens BACNET 125-5037.

For your convenience

If looking through the Siemens BACNET 125-5037 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Siemens BACNET 125-5037 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Siemens BACNET 125-5037 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Siemens BACNET 125-5037 User manual - Online PDF
Advertisement
« Page 1 of 48 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Siemens BACNET 125-5037 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Siemens BACNET 125-5037. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1






Siemens BACnet
VAV Actuator
Owner’s Manual
125-5037 Rev. AA, February 2008

Summary of the content on the page No. 2

Summary of the content on the page No. 3

Rev. AA, February 2008 NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document. All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license. WARNING This equipment generates, use

Summary of the content on the page No. 4

Summary of the content on the page No. 5

Table of Contents How To Use This Manual .............................................................................................. V  Manual Organzation ...................................................................................................... V  Manual Conventions ..................................................................................................... VI  Manual Symbols .............................................................................................

Summary of the content on the page No. 6

Table of Contents Fail-safe Operation .................................................................................................... 7  Heating and Cooling Switchover ............................................................................... 7  Modulate Damper During Heating Mode (optional) ................................................... 7  Hot Water Reheat ...................................................................................................... 8  Electric Reheat ..

Summary of the content on the page No. 7

Siemens BACnet VAV Actuator Owner’s Manual Point Database .............................................................................................................. 20  Overview .................................................................................................................... 20  Troubleshooting ............................................................................................................ 29  Basic Service Information .......................................

Summary of the content on the page No. 8

Summary of the content on the page No. 9

How To Use This Manual This manual is written for the owner and user of Siemens Building Technologies BACnet VAV Actuator. It is designed to help you become familiar with the Siemens BACnet VAV Actuator and its applications. This section covers manual organization, manual conventions, symbols used in the manual, and other information that will help you use this manual. Manual Organzation This manual contains the following chapters: • Chapter 1, Hardware, describes the hardware compone

Summary of the content on the page No. 10

How To Use This Manual Manual Conventions The following table lists conventions to help you use this manual in a quick and efficient manner. Convention Example Actions that you Type F for Field panels. should perform are Click OK to save changes and close the dialog box. specified in boldface font. Error and system The message Report Definition successfully renamed messages are appears in the status bar. displayed in Courier New font. New terms appearing The Open Processor conti

Summary of the content on the page No. 11

1 Product Overview Introduction The BACnet VAV Actuator is the Siemens Building Technologies, Inc. FLN controller used in pressure independent Variable Air Volume applications (Figure 1). It provides Direct Digital Control (DDC) for eight applications, and can operate independently as a stand-alone DDC room controller or networked with a field panel. The controller provides all input/output, system, and local communication connections. Hardware consists of the controller and the mount

Summary of the content on the page No. 12

Product Overview Air Velocity Sensor BACnet Connection Status/DO LEDs Power Connection Airflow Pickup Tubes Figure 1. Siemens BACnet VAV Actuator. Hardware Inputs Analog • Air Velocity Sensor (AVS) • Duct temperature sensor (optional) Application 2561 • Room temperature sensor (RTS) • Room temperature setpoint dial (optional) Digital • Night mode override (optional) • Wall switch (optional) Hardware Outputs Analog • None 2 Siemens Building Technologies, Inc. TEC0496R1

Summary of the content on the page No. 13

Siemens BACnet VAV Actuator Owner’s Manual Digital Application 2560, 2561, 2562, 2563 • Autozero Module (AZM) (optional) All • Damper Actuator 2565, 2566, 2567 • Fan 2563 • First valve actuator (required) 2563 • Second valve actuator (optional) or AZM (optional) 2562 • Stage 1 electric reheat; or, 2-position heating valve 2564, 2566 • Stage 1 electric reheat 2562, 2564, 2566 • Stage 2 electric reheat (optional) 2562, 2564, 2566 • Stage 3 electric reheat (opti

Summary of the content on the page No. 14

Product Overview Communication Wiring The controller connects to the field panel by means of a Floor Level Network (FLN) trunk. Communication wiring connects to the three screw terminals on the controller labeled “+” (positive), “-“(negative), and “S” (Shield) (Figure 3). FLN TRUNK 3-Wire Network Interface +- e to earth Terminator Note: = System Common (SHIELD) (SHIELD) 120 ohm (-) (-) ½ W (+) (+) 120 ohm ½ W Wirenut NOTE: When wiring a 3-wire system to a 2-wire system see the Wirin

Summary of the content on the page No. 15

Siemens BACnet VAV Actuator Owner’s Manual Duct Temperature Sensor An optional duct temperature sensor provides duct air temperature sensing inputs to the controller. For more information about temperature sensors, contact your local Siemens Building Technologies, Inc. representative. Related Equipment • Autozero Module (optional) 540-200 • Relay Module • Damper Actuator(s) • Duct Temperature Sensor (10K Ω) (optional) • Room Temperature Sensor Contact your local Siemens Building

Summary of the content on the page No. 16

2 Applications Basic Operation The BACnet VAV Actuator provides Direct Digital Control (DDC) for Variable Air Volume (VAV) terminal box applications. Temperature control varies with the application. If present, heating can be provided by hot water, up to three stages of electric reheat, or optional baseboard radiation. Sequencing Logic (optional) This application has the additional capability to sequence the flow and mechanical heating when heated supply air is available. Control Te

Summary of the content on the page No. 17

Siemens BACnet VAV Actuator Owner’s Manual Calibration Air Velocity Sensor - Calibration of the controller's internal air velocity sensor is periodically required to maintain accurate air velocity readings. Calibration may be set to take place automatically or manually. Autozero Module (AZM) – Used when damper cannot be closed and constant airflow is needed. • For a controller used with an AZM, calibration occurs without closing the damper. Application 2560, 2561, 2562, 2563. • For a

Summary of the content on the page No. 18

Applications Hot Water Reheat CAUTION: • Do not set HTG FLOW MIN to 0 cfm (0 lps). A minimum airflow should be provided across the heating coils when the heating valve is open. When the controller is in cooling mode, the heating valve(s) are closed. The heating loop modulates the heating valve(s) to warm up the room. In cooling mode, the heating valve is closed. Electric Reheat CAUTION: Verify that the equipment is supplied with safeties by others to ensure that there is ai

Summary of the content on the page No. 19

Siemens BACnet VAV Actuator Owner’s Manual Application 2560 VAV Cooling Only Overview In Application 2560, the controller modulates the supply air damper of the terminal box for cooling. In order for it to work properly, the central air-handling unit must provide cool supply air. See Figure 5. Supply Air Damper 3 to 5 Straight Duct Diameters required for proper sensor reading Supply Air SAFETIES BY OTHERS Air Velocity Sensor Modulating Damper Actuator Spare DO or Autozero Module (Opt.)

Summary of the content on the page No. 20

Applications Application 2561 VAV Cooling or Heating Overview In Application 2561, the controller modulates the supply air damper of the terminal box for cooling and heating. In order for it to work properly, the central air-handling unit must provide cool supply air in cooling mode and warm air in heating mode. See Figure 6. Supply Air Damper 3 to 5 Straight Duct Diameters required for proper sensor reading Supply Air SAFETIES BY Air OTHERS Velocity Sensor Modulating Damper Actuator Spare


Alternative user manuals
# User manual Category Download
1 Siemens S120 User manual Automobile Parts 9
2 Siemens BA 2030 User manual Automobile Parts 10
3 Siemens SIPART PS2 6DR53xx User manual Automobile Parts 382
4 Siemens HIPATH 8000 User manual Automobile Parts 4
5 Siemens SIMATIC Distributed I/O System DP/ASi Link EWA 4NEB 710 6055-02b User manual Automobile Parts 13
6 Siemens SITRANS F M MAGFLO MAG 5100 W User manual Automobile Parts 834
7 Siemens SIPART PS2 6DR52xx User manual Automobile Parts 7
8 Siemens SIPART PS2 6DR51xx User manual Automobile Parts 6
9 Siemens SQM5 User manual Automobile Parts 126
10 Siemens SQK33.00 User manual Automobile Parts 34
11 Siemens SIPART PS2 6DR50xx User manual Automobile Parts 334
12 Siemens SQL33.0 User manual Automobile Parts 53
13 Siemens SQU83 User manual Automobile Parts 1
14 Sony BP-GL95 User manual Automobile Parts 25
15 Sony BP-GL65 User manual Automobile Parts 2
16 Philips Epic 50PF9966 User manual Automobile Parts 3
17 Philips HTS3011 User manual Automobile Parts 2
18 Philips SDJ6040W User manual Automobile Parts 1