Crown Boiler CWI172 user manual

User manual for the device Crown Boiler CWI172

Device: Crown Boiler CWI172
Category: Boiler
Manufacturer: Crown Boiler
Size: 1.32 MB
Added : 5/2/2014
Number of pages: 56
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Crown Boiler CWI172. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Crown Boiler CWI172.

For your convenience

If looking through the Crown Boiler CWI172 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Crown Boiler CWI172 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Crown Boiler CWI172 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Crown Boiler CWI172 User manual - Online PDF
Advertisement
« Page 1 of 56 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Crown Boiler CWI172 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Crown Boiler CWI172. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

D E S I G N E D T O L E A D
CWI Series
Gas-Fired Natural Draft Water Boilers
INSTALLATION INSTRUCTIONS
These instructions must be affixed on or adjacent to the boiler
Models:
WARNING: Improper installation,
adjustment, alteration, service or
• CWI069 • CWI207
maintenance can cause property
• CWI103 • CWI241
damage, injury, or loss of life. For
assistance or additional informa-
• CWI138 • CWI276
tion, consult a qualified installer,
• CWI172 • CWI310
service agency or the gas
supplier. Read

Summary of the content on the page No. 2

Table of Contents I. Product Description .................................................. 1 II. Specifications ............................................................. 2 III. Before Installing ......................................................... 3 IV. Locating the Boiler ...................................................... 3 V . Air for Combustion & Ventilation .............................. 4 VI. Venting ....................................................................

Summary of the content on the page No. 3

II Specifications FIGURE 1: CWI BOILERS - GENERAL CONFIGURA TION TABLE 1: CWI SPECIFICATIONS NATURAL OR LP GAS * BASIC NUMBER HEATING I=B=R NET AFUE (%) TANKLESS WATER BOILER OF INPUT CAPACITY RATING STNDG. INT. HTR. RATING DIMENSIONS (in.) VOL. MODEL SECTIONS (MBH) (MBH) (MBH) PILOT PILOT (Gal/min) "A" "B" "C" "D" (Gal) 50 CWI069 3 69 57 81.0 83.1 12 3/4 28 40 7/16 4 7.8 CWI103 4 103 86 75 81.3 83.1 2.50 16 28 40 7/16 5 10.0 100 CWI138 5 138 115 81.6 83.1 3.00 19 1/4 28 40 7/16 6 12.2 CWI17

Summary of the content on the page No. 4

III Before Installing 1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the requirements of the authority having jurisdiction. • In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the National Fuel Gas Code, ANSI Z223.1-latest edition. • Where required by the authority having jurisdiction, this installation must conform to the Standard for Co

Summary of the content on the page No. 5

“X” (RH CLEARANCE) ALL SIZES LESS TANKLESS HEATER - 18“ CWI103 - CWI241 WITH TANKLESS HTR. - 18“ CWI276 - CWI379 WITH TANKLESS HTR. - 21“ CWI207 - CWI379 WITH HIGH CAPY. TANKLESS HTR. - 24“ “X” FIGURE 2: CWI BOILERS - CLEARANCES TO ALL TYPES OF COMBUSTIBLE CONSTRUCTION AND NONCOMBUSTIBLE CEILINGS, WALLS, AND DOORS. • If the right side 24” service clearance is reduced, adequate clearance must be maintained to easily read and access the controls. Alternatively, access may be provided using a door

Summary of the content on the page No. 6

• Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings. For Buildings of Other than Unusually Tight Construction 1) Determine whether the boiler is to be installed in a confined space - A confined space is defined by the National Fuel Gas Code as having a volume less than 50 cubic feet per 1000 BTU/hr

Summary of the content on the page No. 7

FIGURE 3: BOILER INSTALLED IN CONFINED SPACE, ALL AIR FROM INSIDE FIGURE 4: ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC FIGURE 5: ALL AIR FROM OUTDOORS, VIA VENTILATED ATTIC 7 6

Summary of the content on the page No. 8

FIGURE 6: ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM FIGURE 7: ALL AIR FROM OUTDOORS, USING HORIZONTAL DUCTS INTO BOILER ROOM 8 7

Summary of the content on the page No. 9

• The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are used, they must be no finer than ¼” (4 x 4) mesh. VI Venting Vent installation must be in accordance with local building codes, or the local authority having jurisdiction, or the National Fuel Gas Code, NFPA 54/ANSI Z 223.1. A typical vent installation is illustrated by Figure 8. The components of vent installation are the vent damper, vent connector and chimney. 1) Acceptable

Summary of the content on the page No. 10

sealed tight. 13) Do not install the vent damper in any portion of the vent system which is used by appliances other than the boiler being installed. 14) Vent damper installation is mandatory on all CWI boiler models except the CWI310-CWI379. Install vent damper (see Figure 9) as follows: a) Open vent damper carton and remove installation instructions. Read the instructions thoroughly before proceeding. Verify that vent damper is same size as draft diverter outlet. See Figure 1. Unpack vent damp

Summary of the content on the page No. 11

FIGURE 8: CWI BOILER TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS FIGURE 9: VENT DAMPER INSTALLATION DETAILS 11 10

Summary of the content on the page No. 12

VII Gas Piping Gas piping to the boiler must be sized to deliver adequate gas for the boiler to fire at the nameplate input at a line pressure between the minimum and maximum values shown on the rating plate. For more information on gas line sizing, consult the utility or Chapter 2 of the National Fuel Gas Code. Figure 10 shows typical gas piping connection to the CWI boiler. A sediment trap must be installed upstream of all gas controls. Install a manual shut-off valve outside the jacket an

Summary of the content on the page No. 13

VIII System Piping CAUTION • INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED FROM WATER (DRIPPING, SPRAYING, RAIN, ETC.) DURING APPLIANCE OPERATION AND SERVICE (CIRCULATOR REPLACEMENT, ETC.). • OPERATION OF THIS BOILER WITH CONTINUOUS RETURN TEMPERATURES BELOW 120°F CAN CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE. • OPERATION OF THIS BOILER IN A SYSTEM HAVING SIGNIFICANT AMOUNTS OF DISSOLVED OXYGEN CAN CAUSE SEVERE HEAT

Summary of the content on the page No. 14

6) Low Water Cut-Off (Required in some situations) - A low water cutoff is required when the boiler is installed above radiation. In addition, some codes such as ASME CSD-1 require low water cutoffs. Codes may also require that this low water cutoff have a manual reset function. The low water cutoff may be a float type or probe type, but must be designed for use in a hot-water system. The low water cutoff should be piped into the boiler supply just above the boiler with no intervening valves

Summary of the content on the page No. 15

FIGURE 11: STANDARD BOILER PIPING FIGURE 12: INDIRECT WATER HEATER BOILER SIDE PIPING 15 14

Summary of the content on the page No. 16

5) Piping with a Chiller - If the boiler is used in conjunction with a chiller, pipe the boiler and chiller in parallel as shown in Figure 15. Use isolation valves to prevent chilled water from entering the boiler. 6) Air Handlers - Where the boiler is connected to air handlers through which refrigerated air passes, use flow control valves in the boiler piping or other automatic means to prevent gravity circulation during the cooling cycle. 7) Gravity Hot Water Systems - The CWI is suitable fo

Summary of the content on the page No. 17

FIGURE 14: ISOLATION OF BOILER FROM SYSTEM WITH A HEAT EXCHANGER FIGURE 15: BOILER PIPING WITH CHILLER 17 16

Summary of the content on the page No. 18

FIGURE 16: GRAVITY PIPING IX TANKLESS HEATER PIPING If the CWI is installed with an optional tankless heater, pipe the heater as shown in Figure 17. The components in this system and their functions are as follows: 1) Mixing Valve (Required) - During the heating season, the water exiting the tankless heater may be 180 degrees or more. The mixing valve blends hot water leaving the tankless heater with cold water so as to maintain the hot water supplied to the fixtures at a fixed temperature. T

Summary of the content on the page No. 19

WARNING A mixing valve does not eliminate the risk of scalding. • Set the mixing valve and boiler low limit adjustments as low as possible. • Feel water before showering or bathing. • If anti-scald or anti-chill protection is required, use devices specifically designed for such service. Install and maintain these devices in accordance with the manufacturer’s instructions. Do not use the mixing valve as a substitute for pressure balancing valves or other devices required by plumbing codes to prot

Summary of the content on the page No. 20

IX Wiring WARNING All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code (ANSI/NFPA 70). Single Zone Wiring 1) 120 Volt Wiring - The boiler should be provided with its own 15A branch circuit with fused disconnect. All 120 volt connections are made inside the L8148E or L8124E aquastat relay as follows (also see Figures 18-21): • Hot (“black”) - Terminal “L1” • Neutral (“white”) - Ter


Alternative user manuals
# User manual Category Download
1 Crown Boiler 24-03 User manual Boiler 0
2 Crown Boiler 24-08 User manual Boiler 0
3 Crown Boiler 24-06 User manual Boiler 0
4 Crown Boiler 24-09 User manual Boiler 0
5 Crown Boiler 24-07 User manual Boiler 0
6 Crown Boiler 24-11 User manual Boiler 0
7 Crown Boiler 24-05 User manual Boiler 0
8 Crown Boiler 24-10 User manual Boiler 0
9 Crown Boiler 32 User manual Boiler 0
10 Crown Boiler 32-475ECS User manual Boiler 0
11 Crown Boiler 24-12 User manual Boiler 0
12 Crown Boiler 32-380ECS User manual Boiler 0
13 Crown Boiler 50-003 User manual Boiler 0
14 Crown Boiler 24-04 User manual Boiler 0
15 Crown Boiler ABF-EID User manual Boiler 0
16 Sony HDV 1080I HVR-M15N/M15P User manual Boiler 67
17 Sony HDV 1080I HVR-M25N/M25P User manual Boiler 50
18 A.O. Smith 200 User manual Boiler 2
19 A.O. Smith 201 User manual Boiler 7
20 A.O. Smith 750 & 1000 User manual Boiler 6