Lochinvar SOLUTION 45000 user manual

User manual for the device Lochinvar SOLUTION 45000

Device: Lochinvar SOLUTION 45000
Category: Boiler
Manufacturer: Lochinvar
Size: 6.89 MB
Added : 9/18/2013
Number of pages: 52
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Lochinvar SOLUTION 45000. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Lochinvar SOLUTION 45000.

For your convenience

If looking through the Lochinvar SOLUTION 45000 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Lochinvar SOLUTION 45000 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Lochinvar SOLUTION 45000 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Lochinvar SOLUTION 45000 User manual - Online PDF
Advertisement
« Page 1 of 52 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Lochinvar SOLUTION 45000 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Lochinvar SOLUTION 45000. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

SBR-I-S Rev B
Installation & Service Manual
Models: 45,000 - 260,000 Btu/hr
 WARNING:
This manual supplies information for the installation,
operation, and servicing of the appliance. It is strongly
recommended that this manual be reviewed completely
before proceeding with an installation. Perform steps in
the order given. Failure to comply could result in severe
personal injury, death, or substantial property damage.
Save this manual for future reference.

Summary of the content on the page No. 2

Contents HAZARD DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 2 5. ELECTRICAL CONNECTIONS PLEASE READ BEFORE PROCEEDING . . . . . . . . . . . . 3-4 Boiler Operating Temperature Control . . . . . . . . . . . . . . . 34 RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Room Thermostat or Remote Thermostat Connection . . 34 THE SOLUTION --HOW IT WORKS . . . . . . . . . . . . . . . . . . . 6-8 Auxiliary Device Connection to Terminal Strip . . .

Summary of the content on the page No. 3

Installation & Service Manual Please read before proceeding Improper installation, adjustment, This is a gas appliance and should be NOTICE  WARNING alteration, service or maintenance can result installed by a licensed electrician and/or in severe personal injury, death, or certified gas supplier. Service must be substantial property damage. Refer to this performed by a qualified service installer, manual for assistance or additional service agency or the gas supplier. information, consult a

Summary of the content on the page No. 4

Installation & Service Manual Please read before proceeding To minimize the possibility of serious  WARNING personal injury, fire, or damage to your appliance, never violate the following safety rules: 1. Boilers are heat producing appliances. To avoid damage or injury, do not store materials against the appliance or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the appliance and vent-air intake components. 2. Never cover your applia

Summary of the content on the page No. 5

Installation & Service Manual Ratings Solution Boiler Other Specifications I=B=R Rating Net I=B=R Input Gross Model Number Ratings Boiler Water MBH Output Vent Water Gas Water, Content MBH Note: Change “N” to Connections Connections Size (Note 4) MBH Gallons “L” for L.P. gas models. (Note 1,5) (Note 1,5) Min Max (Note 3) CBN045 23 45 37 32 0.87 1 1/2" 1/2" 4" CBN075 38 75 62 54 0.91 1 1/2" 1/2" 5" CBN090 45 90 75 65 0.91 1 1/2" 1/2" 5" CBN135 68 135 112 97 0.95 1 1/2" 1/2" 6"

Summary of the content on the page No. 6

Installation & Service Manual The Solution - How it works... 1. Control panel cover 16. Sight Glass The control panel cover provides access to the thermostat, ignition The sight glass provides a view of the burner surface, burner flame, module, and transformer. and the pilot flame. 2. Burner (not shown) 17. Temperature and pressure gauge The burner is a cylindrical stainless steel tube used to regulate The temperature and pressure gauge monitors the outlet burner flame. temperature of the

Summary of the content on the page No. 7

Installation & Service Manual The Solution - How it works... (continued) 4 10 20 17 15 1 8 3 19 5 Models 45,000 - 90,000 Btu/hr Front View Models 45,000 - 90,000 Rear View 7 22 18 21 12 9 6 11 23 25 24 14 16 Models 45,000 - 90,000 Left Side (inside unit) Models 45,000 - 90,000 Right Side (inside unit) 7

Summary of the content on the page No. 8

Installation & Service Manual The Solution - How it works... 10 4 20 17 15 1 8 3 19 5 Models 135,000 - 260,000 Btu/hr Front View Models 135,000 - 260,000 Btu/hr Rear View 7 9 18 12 3 6 3 11 21 25 24 23 22 14 Models 135,000 - 260,000 Btu/hr Left Side (inside unit) Models 135,000 - 260,000 Btu/hr Right Side (inside unit) 8

Summary of the content on the page No. 9

Installation & Service Manual 1 Determine boiler location Location of unit Recommended Service Clearances: Left - 24” Front - 24” 1. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. Under no circumstances is the manufacturer to be held responsible for water damage in c

Summary of the content on the page No. 10

Installation & Service Manual 1 Determine boiler location Combustion and ventilation air requirements for conventionally vented appliances Provisions for combustion and ventilation air must be in accordance with, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. The room where the

Summary of the content on the page No. 11

Installation & Service Manual 1 Determine boiler location (continued) Under no circumstances should the room  CAUTION where the appliance is installed ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the appliance. The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Comm

Summary of the content on the page No. 12

Installation & Service Manual 1 Determine boiler location TABLE - 1B MINIMUM RECOMMENDED COMBUSTION AIR SUPPLY TO EQUIPMENT ROOM *Outside Air from *Outside Air from **Inside Air from 2 Openings Directly from 2 Ducts Delivered from 2 Ducts Delivered from *Outside Air from Input Outdoors Outdoors Interior Space 1 Opening Directly Btu/hr 2 from Outdoors, in Top Bottom Top Bottom Top Bottom 2 2 2 2 2 2 Opening, in Opening, in Opening, in Opening, in Opening, in Opening, in 12 12 15 23 23 100 100

Summary of the content on the page No. 13

Installation & Service Manual 2 Venting A Conventional Negative Draft Venting System The negative draft in a conventional vent in stal la tion must be TABLE - 2A within the range of a negative 0.02 to 0.05 inches water column to ensure proper operation. All draft read ings are VENT PIPE SIZES made while the appliance is in stable op era tion Input Btu/hr Flue Size (approximately 2 to 5 minutes). 45,000 4" Multiple appliance installations with combined vent ing or 75,000 5" common venting with

Summary of the content on the page No. 14

Installation & Service Manual 2 Venting Locate appliance as close as possible to a chimney or gas vent. (e) Test for spillage at the draft hood/relief opening after 5 minutes of main burner operation. Use the flame of a Avoid long horizontal runs of the vent pipe, 90° el bows, match or candle, or smoke from a cigarette, cigar or reductions and restrictions. Horizontal por tions of the pipe. venting system shall be supported to prevent sagging. Horizontal runs must slope upwar ds not less than

Summary of the content on the page No. 15

Installation & Service Manual 2 Venting (continued) Vertical Vent Termination Clearances 10' OR LESS 10' OR LESS 10' OR LESS CHIMNEY 2' MIN 2' MIN 3' MIN 2' MIN 3' MIN RIDGE CHIMMEY WALL OR CHIMMEY PARAPET Figure 2-2_Vent Termination from Peaked Roof 10' or Figure 2-4_Vent Termination from Flat Roof 10' or Less Less from Ridge from Parapet Wall 10' OR MORE MORE THAN 10' 3' 10' 2' MIN CHIMNEY RIDGE 3' MIN NOTE: NO HEIGHT ABOVE PARAPET REQUIRED WHEN DISTANCE FROM WALLS OR PARAPETS IS MORE THAN 1

Summary of the content on the page No. 16

Installation & Service Manual 2 Venting Masonry Chimney Installation The in duced draft fan MUST also be equipped with a prov ing switch, properly interlocked into the ap pli ance’s con trol circuit A masonry chimney must be properly sized for the to prove fan operation before the main burn ers are allowed to installation of a gas fired appliance. Venting of an appliance fire. A vertical or sidewall vent termination for an induced draft into a cold or oversized masonry chimney can result in fa

Summary of the content on the page No. 17

Installation & Service Manual 2 Venting (continued) VENT DAMPER Automatic Vent Damper This heating boiler is design certified for use with the automatic vent damper (FIG. 15) part number printed on the boiler’s rating plate. A vent damper must be installed on all residential heating boilers with inputs of less than 300,000 Btu/hr to comply with minimum efficiency requirements. A vent damper is factory supplied with residential heating boilers with inputs of 45,000 thru 260,000 Btu/hr. The v

Summary of the content on the page No. 18

Installation & Service Manual 3 Gas connections Gas Supply Gas Pressure Test Verify that the appliance is supplied with the type gas 1. The appliance must be disconnected from the gas supply spec i fied on the rating plate. This appliance is orificed for piping system during any pressure testing of that system at operation up to 2000 feet altitude. The ap pli ance will be a test pressure in excess of 1/2 PSIG (3.5kPa). derated 4% per 1000 feet above 2000 feet el eva tion. Consult 2. The app

Summary of the content on the page No. 19

Installation & Service Manual 3 Gas connections (continued) TABLE - 3E GAS PIPING SIZE CHART Nominal Length of Pipe in Straight Feet Maximum Iron Pipe Capacity of Pipe Size in Thousands of Inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200 Btu/hr per hour for gas pressures 3/4 369 256 205 174 155 141 128 121 113 106 95 86 79 74 of 13.5 Inches Water Column 1 697 477 384 328 292 267 246 226 210 200 179 164 149 138 (0.5 PSIG) or less and a pressure 1 1/4 1,400 974 789 677 595 543 502 472 441 41

Summary of the content on the page No. 20

Installation & Service Manual 3 Gas connections 1. Turn the power “OFF” at the main dis con nect switch. WHEN FLANGE IS USED 2. Turn gas valve control knob to “OFF” po si tion. 3. Remove the 1/8" hex plug located on the out let side of the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. See FIG. 3-3. Minimum WHEN FLANGE IS NOT USED range of scale should be up to 5" w.c. for Natural gas APPLY WRENCH mod els and 10" w.c. for L.P. gas models. TO FLANGE


Alternative user manuals
# User manual Category Download
1 Lochinvar 000 - 260 User manual Boiler 4
2 Lochinvar 051-211 User manual Boiler 0
3 Lochinvar 1 User manual Boiler 0
4 Lochinvar 000 through 2 User manual Boiler 2
5 Lochinvar 000 BTU/HR User manual Boiler 5
6 Lochinvar 1.3 User manual Boiler 0
7 Lochinvar 0402-0752 User manual Boiler 1
8 Lochinvar 1.5 User manual Boiler 0
9 Lochinvar 2001 User manual Boiler 0
10 Lochinvar 2 User manual Boiler 0
11 Lochinvar 151 User manual Boiler 0
12 Lochinvar 1701 User manual Boiler 0
13 Lochinvar 151-286 User manual Boiler 0
14 Lochinvar 2.5 User manual Boiler 0
15 Lochinvar 45 User manual Boiler 0
16 Sony HDV 1080I HVR-M15N/M15P User manual Boiler 67
17 Sony HDV 1080I HVR-M25N/M25P User manual Boiler 50
18 A.O. Smith 200 User manual Boiler 2
19 A.O. Smith 201 User manual Boiler 7
20 A.O. Smith 750 & 1000 User manual Boiler 6