Raypak 1001 user manual

User manual for the device Raypak 1001

Device: Raypak 1001
Category: Boiler
Manufacturer: Raypak
Size: 1.47 MB
Added : 9/18/2013
Number of pages: 76
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Raypak 1001. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Raypak 1001.

For your convenience

If looking through the Raypak 1001 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Raypak 1001 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Raypak 1001 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Raypak 1001 User manual - Online PDF
Advertisement
« Page 1 of 76 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Raypak 1001 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Raypak 1001. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Catalog No.: 3400.52D
Effective: 04-01-03
Replaces: 02-15-03
OPERATING AND
INSTALLATION
INSTRUCTIONS
Model 751, 1001, 1501
TYPE H, WH, P
ADVANCED
DESIGN
BOILER
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids or other combustible materi-
als in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause prop-
erty damage, personal injury or los

Summary of the content on the page No. 2

DANGER: Make sure the gas on which the boiler will operate is the same type as that specified on the boiler model and rating plate. WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the boiler. Instead, shut off the gas supply at a location external to the appliance. WARNING: Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any

Summary of the content on the page No. 3

TABLE OF CONTENTS PAGE NO. 4 SECTION A: BEFORE INSTALLING THE BOILER 7 SECTION B: BOILER INSTALLATION 10 SECTION C: COMBUSTION AND VENTILATION AIR 12 SECTION D: WATER PIPING - GENERAL 13 SECTION E: HYDRONIC HEATING PIPING 17 SECTION F: DOMESTIC HOT WATER PIPING 19 SECTION G: POOL HEATING 22 SECTION H: GAS SUPPLY CONNECTIONS 24 SECTION I: ELECTRICAL POWER CONNECTIONS 27 SECTION J: VENTING CONNECTIONS 49 SECTION K: CONDENSATE DRAIN 50 SECTION L: CONTROLS 56 SECTION M: GENERAL SAFETY PRECAUTION

Summary of the content on the page No. 4

Pay attention to these terms: DANGER indicates the presence of immediate hazards which will cause severe personal injury, death or substantial property damage if ignored. WARNING indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored. CAUTION indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored. NOTICE indicates special instruc

Summary of the content on the page No. 5

MODEL IDENTIFICATION The model identification number and boiler serial number are found on the boiler data plate located on the left inside jacket of the boiler. The model number will have the form H4 0500A ADB or similar depending on the boiler size and configuration. The first character of the model number identifies application (H = Hydronic Heating System, W = Hot Water Supply System, P = Pool Application). The second character identifies the firing mode (4 = On-Off firing). The next four pl

Summary of the content on the page No. 6

Figure A-1 ADVANCED DESIGN BOILER COMPONENT LOCATIONS 6

Summary of the content on the page No. 7

SECTION B: BOILER INSTALLATION INSTALLATION CODES Installations must follow these codes: · Local, state, provincial, and national codes, laws, regulations and ordinances. · National Fuel Gas Code (NFGC), ANSI Z223.1- latest edition. · National Electrical Code (NEC), ANSI/NFPA 70 - latest edition. · Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required. · For Canada only: CAN/CGA B149.1 and .2 Installation Code and C.S.A. C22. 1 C.E.C. Part 1. EQ

Summary of the content on the page No. 8

CLEARANCES TABLE 1 MINIMUM CLEARANCES FROM COMBUSTIBLE SURFACES (INDOOR ALCOVE INSTALLATIONS) Boiler Size Boiler Side 751, 1001, 1501 Floor See Note 1. Rear 1” Right 12” (Water side) Left 1” Top 0” Vent 1” Note 1. Do not install on carpeting. Figure B-1 MINIMUM CLEARANCES FROM COMBUSTIBLE SURFACES AND FOR EASY SERVICING 8

Summary of the content on the page No. 9

Raypak Advanced Design Boilers are design certified by AGA/CGA for outdoor installation. Roof water drainage must be diverted away from boilers installed under overhangs. TABLE 2 OUTDOOR INSTALLATION MINIMUM CLEARANCES Boiler Size Boiler Side 751, 1001, 1501 Rear 6" Right 36” (Water side) Left 36" Top 0" Vent 1" WARNING: Combustion air inlet (blower air inlet) should have 6" minimum clearance from any obstruction, i.e. walls or other appliances. 9

Summary of the content on the page No. 10

SECTION C: COMBUSTION AND VENTILATION AIR COMBUSTION AND VENTILATION AIR (Indoor Units) The boiler must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be supplied via conventional venting, where combustion air is drawn from the area immedi- ately surrounding the boiler, or via direct vent, where combustion air is drawn directly from outside. All installations must comply with the requirements of NFGC for

Summary of the content on the page No. 11

All Air from Outdoors. If all combustion air is drawn from the air outside the building (the mechanical equipment room directly communicates with the outdoors), either of the following two methods can be used: Method 1: 1. The mechanical equipment room must be provided with two permanent openings, one commencing within (twelve) 12 inches of the top, and one commencing within twelve (12) inches of the bottom of the room. 2. The openings must communicate directly, or by ducts, with the outdoors. 3

Summary of the content on the page No. 12

SECTION D: WATER PIPING - GENERAL The boiler should be located so that any water leaks will not cause damage to the adjacent area or structures. All units should be plumbed in accordance with the appropriate diagram from Section E, F or G or per a suitable engineered piping arrangement. CAUTION: This boiler requires forced water circulation when the burner is operating. See Table D-1 for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the boiler to p

Summary of the content on the page No. 13

SECTION E: HYDRONIC HEATING PIPING PUMP SELECTION In order to insure proper performance of your boiler system, you must install a properly sized pump. Raypak recommends using a 20°F Delta T as design Delta T. (Delta T is the temperature difference between the inlet and outlet water when the boiler is firing at full rate). If a Delta T larger than 20°F is necessary, the bypass must be installed and adjusted to insure proper hydraulics through the boiler while still allowing minimum flow to satisf

Summary of the content on the page No. 14

PRESSURE DROP IN FEET OF HEAD FEEDWATER REGULATOR Raypak recommends that a feedwater regulator be installed and set at 12 PSIG minimum pressure at the highest point of system. Install a check valve or back flow device upstream of the regulator, with a manual shut off valve as required by local codes. PIPING - HEATING BOILERS All high points should be vented. Purge valves and a bypass valve should be installed. A boiler installed above radiation level must be provided with a low water cutoff devi

Summary of the content on the page No. 15

Figure E-2b SINGLE BOILER - PRIMARY/SECONDARY PIPING WITH CHX Figure E-3a DUAL-BOILER PIPING 15

Summary of the content on the page No. 16

Figure E-3b DUAL BOILER - PIPING WITH CHX Figure E-4a SINGLE BOILER - LOW TEMPERATURE APPLICATION (HEAT PUMP) PRIMARY/SECONDARY PIPING 16

Summary of the content on the page No. 17

SECTION F: DOMESTIC HOT WATER PIPING When designing the water piping system for domestic water applications, water hardness should be considered. Table D- 1 indicates the suggested flow rates for soft, medium and hard water. Hardness is specified as grains per gallon. TABLE F-1 DOMESTIC W ATER HEA TING BOILER FLOW RATE REQUIREMENTS Delta T = Temperature rise in °F GPM = Gallons per minute See Table D-1 for Pressure Drop Figure F-1a SINGLE BOILER DOMESTIC HOT WATER WITH ONE STORAGE TANK Figure F

Summary of the content on the page No. 18

Figure F-1bb SINGLE BOILER DOMESTIC HOT WATER WITH ONE STORAGE TANK AND CHX (2 pump system) Figure F-1c SINGLE BOILER DOMESTIC HOT WATER WITH ONE STORAGE TANK, ONE PRE-HEAT TANK AND CHX 18

Summary of the content on the page No. 19

SECTION G: POOL HEATING CAUTION: Power to the heater should be interlocked with the main system pump to make sure the heater does not fire without the main system pump in operation. Improper flow control can damage the heater. Uncontrolled flow (too high) or restricted flow (too low) can seriously affect heater operation. Follow these instructions to make sure your heater is properly installed. The ADB unit is equipped with an external pump and bypass arrangement that blends outlet water with

Summary of the content on the page No. 20

POOL AND SPA WATER CHEMISTRY NOTE: Chemical imbalance can cause severe damage to your heater and associated equipment. Maintain your water pH between 7.4 and 7.8 and total alkalinity between 100 and 150 p.p.m. If the mineral content and dissolved solids in the water become too high, scale forms inside the heat exchanger tubes, reducing heater efficiency and also damaging the heater (max TDS at 3000 p.p.m.). If the pH drops below 7.2, the heater will be severely damaged. NOTE: Heat exchanger d


Alternative user manuals
# User manual Category Download
1 Raypak 0090B 0135B User manual Boiler 32
2 Raypak 1000 .19C User manual Boiler 1
3 Raypak 181-401 User manual Boiler 5
4 Raypak 1501 User manual Boiler 9
5 Raypak 0180B Type H User manual Boiler 3
6 Raypak 133 User manual Boiler 0
7 Raypak 180B User manual Boiler 1
8 Raypak 2100-4001 User manual Boiler 7
9 Raypak 240692 User manual Boiler 0
10 Raypak 241275 User manual Boiler 0
11 Raypak 182-400 User manual Boiler 6
12 Raypak 2342BE User manual Boiler 0
13 Raypak 1000 User manual Boiler 0
14 Raypak 302BD-902BD User manual Boiler 0
15 Raypak 30B User manual Boiler 0
16 Sony HDV 1080I HVR-M15N/M15P User manual Boiler 67
17 Sony HDV 1080I HVR-M25N/M25P User manual Boiler 50
18 A.O. Smith 200 User manual Boiler 2
19 A.O. Smith 201 User manual Boiler 7
20 A.O. Smith 750 & 1000 User manual Boiler 6