Honeywell L6008 user manual

User manual for the device Honeywell L6008

Device: Honeywell L6008
Category: Thermostat
Manufacturer: Honeywell
Size: 1.49 MB
Added : 1/19/2014
Number of pages: 20
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Honeywell L6008. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Honeywell L6008.

For your convenience

If looking through the Honeywell L6008 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Honeywell L6008 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Honeywell L6008 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Honeywell L6008 User manual - Online PDF
Advertisement
« Page 1 of 20 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Honeywell L6008 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Honeywell L6008. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

L4006,7,8; L6006,7,8
®
Aquastat Controllers
PRODUCT DATA
FEATURES
FOR VERTICAL
• L4006, 7, and 8 provide Spst switching for high or low
MOUNTING AND
limit or circulator control.
HORIZONTAL
• L4006G includes two Spst switches that provide high
SENSOR
limit and circulator control.
INSERTION
• L4006,7; L6006,7 models are available for insertion in:
vertical or horizontal immersion well, vertical or
horizontal direct immersion, and surface mounting.
• L4008, L6008 include remote bulb for mounti

Summary of the content on the page No. 2

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS SPECIFICATIONS IMPORTANT NOTE: The following specifications are standard. Variances, The specifications given in this publication do not available as options, are listed in Tables 1 and 2. include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed Electrical Ratings (A): specifications. Also, this product is tested and Models with 2° F (1° C) fixed differential: calibrated under closely controlled conditions, and

Summary of the content on the page No. 3

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Approvals: Underwriters Laboratories Inc: 1 (25) Remote bulb devices and well-mounted devices shipped KNOCKOUT FOR 3/4 (19 ) without well are component recognized: 5/16 CONDUIT ON ALL MODELS. SIMILAR File No. MP466, Guide No. MBPR2. (8) KNOCKOUT ON BOTTOM FOR L4006A shipped with well, L4006G, L4007A,B; L6006C for HORIZONTAL INSERTION AND REMOTE BULB MODELS. surface mounting, L6006B for direct immersion mounting, and L6007A are listed: File No. MP

Summary of the content on the page No. 4

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS 1/2 — 14 IN. NPT 7/8 IN. (22 MM) STANDARD 7/16 KNOCKOUT (2) (11) M8789A 1-1/2 (38) 3 (76) 1 (25) Fig. 4. Approximate immersion well dimensions in inches C (mm) for all models except L4006C and L6006B. L 1/2 OR 3/4 — 14 IN. NPT 3/8 (10) 5-5/8 M8799A (136) 1-5/16 (33) 3 (76) Fig. 5. Approximate boiler fitting and bulb dimensions in inches (mm) for L4006C and L6006B. 2 (51) 2 (51) 2-3/4 (70) M8958A Fig. 3. Approximate installation dimensions in

Summary of the content on the page No. 5

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Standard Models: L4006,A,B,C,E,G; L4007,A,B; L4008A,B.E; L6006A,B,C; L6007A, L6008,A,G,H Table 1. L4006, L4007, L4008 Controller (SPST Switching) Specifications. Midscale Switching On Range Differential Temperature a Model Application °F (°C) °F (°C) Insertion Rise Available Options L4006A High or low 40° F to 180° F 2° F or 5° F fixed Horizontal Breaks — TRADELINE models limit (4° C to 82° C) (1° C or 3° C) available. or or — NPT brass spud 1/2 in

Summary of the content on the page No. 6

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Table 1. L4006, L4007, L4008 Controller (SPST Switching) Specifications. (Cont.) Midscale Switching On Range Differential Temperature a Model Application °F (°C) °F (°C) Insertion Rise Available Options L4006G High limit 100° F to 200° F 10° F (6° C) fixed Horizontal Two switches — External adjustment knob. and (38° C to 93° C) break — Insulation depth 4 in. circulator simultaneously (102 mm). control — Factory-set stop at 160° F (71° C). — Celsius

Summary of the content on the page No. 7

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Table 2. L6006, L6007, L6008 Controller (SPDT Switching) Specifications. Midscale Range Differential a Model Application °F (°C) °F (°C) Insertion Available Options L6006A Circulator and low 100° F to 240° F 5° F (3° C) fixed Horizontal — SUPER TRADELINE model limit or high limit (38° C to 116° C) or available. or 5° F to 30° F — Modified dial with stop. 100° F to 290° F (3° C to 17° C) — NPT brass spud 1/2 in. or 3/4 (38° C to 143° C) adjustable i

Summary of the content on the page No. 8

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS The manufacturer usually provides a tapping for insertion of INSTALLATION the controller sensing element. This tapping is located at a point where typical water temperature can be measured. Depending on the model, the element is inserted in an When Installing This Product… immersion well, through a boiler fitting, or directly immersed. 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous Insta

Summary of the content on the page No. 9

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS 2. Insert the immersion sensing bulb through the bulb compression fitting. Adjust the adapter clamp so that the clamp fits over the groove at the opening of the bulb compression fitting. SETPOINT INDICATING DIAL 3. Tighten the adapter clamp screws so that the Aquastat Controller is firmly attached to the bulb compression DIFFERENTIAL fitting. ADJUSTMENT WHEEL Mounting Remote Bulb Models ADAPTER CLAMP SCREWS (L4008A,B,E; L6008A,G,H) INSERTION 1 Th

Summary of the content on the page No. 10

240 220 200 ® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS CLAMP B CLAMP SCREWS (2) CLAMP A BULB BULB COMPRESSION SEALING FITTING WASHER JAWS SPREAD JAWS TO FIT OVER RIDGE ON WELL SPUD INSERTION LENGTH SCREWDRIVER APPROX. 3-3/16 IN. (81 MM) SPLIT SLEEVE M8815A MOUNTING CLAMP Fig. 10. Bulb compression fitting. DRAW NUT MOUNTING Use with L4006A,B; L6008A. SPUD CLAMP WELL BULB B 5. Place clamps A and B on the assembly so that the sleeve is drawn into the fitting when the screws are tightened. N

Summary of the content on the page No. 11

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Mounting Remote Bulb Models For Outdoor Air Sensing These models have a 5 ft (1.5 m) capillary that establishes the maximum distance between the case and the outdoor mounting. Install the bulb on the outside of the building in the shield provided (See Fig. 15) where it can be exposed to representative air temperature, but not to direct sunlight. Mount M8970A the bulb high enough so that accumulated snow, leaves, or other debris cannot obstruct c

Summary of the content on the page No. 12

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Mounting on Suction Line Wiring 1. In cooling units with more than one suction line, place Disconnect power supply before beginning installation to the sensing bulb on the common line. prevent electrical shock or equipment damage. 2. Make certain the bulb is at least 2 ft (0.6 m) from the point at which the suction line leaves the cooler. This All wiring must comply with local codes and ordinances prevents the outside temperature from being transm

Summary of the content on the page No. 13

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS 24 VOLT PROTECTORELAY THERMOSTAT L1 1 CONTROL L4006A OR L4007A 1 (HOT) HIGH LIMIT RA832A L1 L2 ® AQUASTAT L4006A OR L4007A HIGH 1 SWITCHING RELAY (HOT) CONTROLLER LIMIT CONTROLLER 2 L2 TT 1 2 4 2 24 VOLT THERMOSTAT 1 IGNITION IGNITION 3 4 4 XX CIRCULATOR T L4006B OR L4007B 3 CIRCULATOR BURNER OIL VALVE T ® AQUASTAT MOTOR (IF USED) CONTROLLER BURNER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS T M1054B 2 AND OVERLOAD PROTECTION AS REQUIRED. L4006A OR L40

Summary of the content on the page No. 14

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS L4006 L1 HIGH LIMIT (HOT) L2 1 SERIES 80 CONTROLLER THERMOSTAT MILLIVOLTAGE THERMOSTAT L6006 R L1 L2 T T CIRCULATOR 2 MILLIVOLTAGE AND VALVE OPERATOR LOW LIMIT 3 W SAFETY CONTROL SHUTOFF B PILOT B PILOTSTAT¨ OPERATOR BURNER POWER UNIT COIL L8148A R M1156A POWER UNIT COIL C1 C2 B1 B2 Fig. 27. Typical Powerpile System wiring diagram. LOW VOLTAGE 1 2 HEATING LOAD LINE VOLTAGE L2 NO. 1 1 CIRCULATOR L6008G L1 (HOT) 12 1 2 WW HEATING LOAD BB NO. 2 RR 21 P

Summary of the content on the page No. 15

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Low Limit Controller R-B terminals provide low limit switching function (contacts open at set point on temperature rise). Maintains minimum boiler temperature for domestic hot water. Turns on boiler at BREAKS R-B temperature setting, less differential. MAKES R-W LEFT SWITCH ON RISE TEMPERATURE DIFFERENTIAL RISE Circulator Controller 2 BREAKS R-W MAKES R-B R-W terminals provide circulation control function (contacts ON FALL close at set point on tem

Summary of the content on the page No. 16

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Adjust the control point to correspond with the boiler Table 3. Temperature Adjustments. manufacturer recommendations. To adjust, insert a screwdriver in the slotted screw type head located beneath the Difference Between Desired window in the cover. Turn the scale to the desired control point. Room Temperature and Case Temperature Reduce Dial Setting °F °C °F °C Adjusting L6008G Interstage Differential The L6008G Controller has an adjustable inters

Summary of the content on the page No. 17

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Check to make certain that the Aquastat Controller is properly CHECKOUT installed and adjusted. Put the system into operation and observe the action of the controller through several cycles to make certain it provides proper control of the system as described in the OPERATION section. Make any additional WARNING adjustments necessary for assuring comfort requirements. Explosion Hazard. Can cause serious injury, death or property damage. This prod

Summary of the content on the page No. 18

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS MATERIAL SAFETY DATA SHEET Manufacturer: Honeywell Inc., 1985 Douglas Drive North, Section 1. Product And Company Minneapolis, MN 55422. Identification Date Released: October 8, 1999 Product Name: Heat Conductive Compound NFPA Ratings: MSDS ID: DS9021 Health 0; Flammability 1; Reactivity 0; Personal Protection B Synonyms: MS1699 Section 2. Composition, Product Use: Heat conductive material used to enhance contact and heat transfer in temperature se

Summary of the content on the page No. 19

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Reactivity: Hazardous polymerization will not occur. Section 6. Accidental Release Measures Scrape up and dispose of as solid waste in accordance with Incompatibilities: Strong oxidizing agents and halogens. state and federal regulations. Hazardous Decomposition Products: Carbon dioxide, carbon monoxide. Section 7. Handling and Storage Store in dry place. Keep container closed when not in use. Section 11. Toxicology Information. No data available. Se

Summary of the content on the page No. 20

® L4006,7,8; L6006,7,8 AQUASTAT CONTROLLERS Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2006 Honeywell International Inc. 60-2104—10 J.I. Rev. 12-06


Alternative user manuals
# User manual Category Download
1 Honeywell 191108AJ User manual Thermostat 629
2 Honeywell 42011076-003 User manual Thermostat 204
3 Honeywell 69-0786-2 User manual Thermostat 57
4 Honeywell 69-1776EFS-01 User manual Thermostat 56
5 Honeywell 72838 User manual Thermostat 42
6 Honeywell 69-2485EFS-03 TH8320ZW1000 User manual Thermostat 48
7 Honeywell 5-2-DAY DELUXE RTH6300B User manual Thermostat 50
8 Honeywell 7300 User manual Thermostat 20
9 Honeywell 69-1490 User manual Thermostat 10
10 Honeywell 8000 User manual Thermostat 90
11 Honeywell 8160 User manual Thermostat 9
12 Honeywell 9820i User manual Thermostat 8
13 Honeywell 8162 User manual Thermostat 3
14 Honeywell 7351F User manual Thermostat 30
15 Honeywell AC-220-7 User manual Thermostat 3
16 Edelbrock 2116 User manual Thermostat 0
17 A&D MF-50 User manual Thermostat 8
18 A&D ML-50 User manual Thermostat 8
19 A&D MS-70 User manual Thermostat 15
20 Acu-Rite D1523 User manual Thermostat 2