Honeywell MICRONIK 200 R7426C user manual

User manual for the device Honeywell MICRONIK 200 R7426C

Device: Honeywell MICRONIK 200 R7426C
Category: Thermostat
Manufacturer: Honeywell
Size: 0.64 MB
Added : 6/7/2013
Number of pages: 20
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Honeywell MICRONIK 200 R7426C. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Honeywell MICRONIK 200 R7426C.

For your convenience

If looking through the Honeywell MICRONIK 200 R7426C user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Honeywell MICRONIK 200 R7426C on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Honeywell MICRONIK 200 R7426C to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Honeywell MICRONIK 200 R7426C User manual - Online PDF
Advertisement
« Page 1 of 20 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Honeywell MICRONIK 200 R7426C but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Honeywell MICRONIK 200 R7426C. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

HONEYWELL

R7426A,B,C
TEMPERATURE CONTROLLER
MicroniK 200
WITH AND WITHOUT REAL-TIME CLOCK
INSTALLATION & START-UP INSTRUCTIONS

GENERAL
This document provides instructions and procedures for
installing and starting up the Micronik 200 R7426A,B,C
controllers. No special tools are required for mounting and
installation. The user interface and liquid-crystal display allow
accurate and easy parameter setting and output adjustment.

BEFORE INSTALLATION NOTE
• Visually inspect equipme

Summary of the content on the page No. 2

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK WIRING Screwless type, spring loaded terminals are provided on the controllers for panel and field wiring. These terminals are suitable for solid conductors as well as tinned or with 2 multicore cable end, stranded wires up to 1.5 mm . To make a termination, push the wire into the terminal or insert a small screwdriver from the front of the controller into the spring-release hole and insert the wire. Check for proper W30

Summary of the content on the page No. 3

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK CONFIGURATION AND CONTROL PARAMETERS *) The controllers R7426A,B,C include two groups of settings (I and II) for control and configuration parameters that are automatically selected during programming. For parameter Ctrltyp = Lo, setting I is selected, and for parameter Ctrltyp = Hi1/Hi2, setting II is selected. config. par. R7426 default actual description setting value no. name A B C C.01 DIR/REVY1 Selects the output a

Summary of the content on the page No. 4

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK config. par. default R7426 actual description setting value no. name A B C I / II 0 x x x C.12 T2ext Enable / Disables the T1 sensor input to be used for both T1 and T2 inputs. 0 T2 installed 1 T1 signal used for T2 x x x C.13 LimTyp Limitation type determines whether the limit function is low or high. 0 / 1 0 Low limit 1 High limit 0 x x x C.14 Senstyp Sensor type determines automatic detection or

Summary of the content on the page No. 5

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK control par. setting I / setting II R7426 reso- actual description unit lution value no. name low high def. A B C 50 / 21 / P.01 W1 Main setpoint for input T1 0 0.5 °C x x x 130 70 5 / 50 / 16 / P.02 Wlim Limit setpoint (low or high) for input T2 1 °C x x x 30 130 90 P.03 Wcomp Compensation changeover point for input T3 -5 40 20 1 °C x x x P.04 Wi Winter compensation authority -350 +3500 2 % x xx P.05 Su Summer c

Summary of the content on the page No. 6

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK CONFIGURATION SETTINGS The controllers R7426A,B are supplied with unconfigured Table 6. Selection of CPA/SPA Type outputs to avoid damage of installed final control devices by CPA / SPA sensor / CPATYP supply of not applicable output signals if the controller power range remote setpoint unit type supply is turned on. CPATYP 0 internal CPA: ±5 K All configuration parameters must be set to select the correct CPATYP 1

Summary of the content on the page No. 7

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK Output Signal Mode YMode (C.11) Supply of Temperature Signal T2 Sequence Operation T2ext (C.12) The controllers R7426B,C are supplied from the factory If sensor T1 is used also for high or low limit control, the con- configured for sequence operation of heating, mixed air, and figuration parameter T2ext must be set to 1. This inter- cooling control. connects the T1 and T2 input internally and the sensor has to The seque

Summary of the content on the page No. 8

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK Summer / Winter Time Change Default Programming DefProg (C.23) Setting the control parameter DefProg to 1 resets all control AddHour / SubHour (C.16 / C.17) and configuration parameters to defaults (see Table 4 and These configuration parameters are only available on Table 5). Default programming is indicated by a display of def. controllers with RTC. The configuration parameter AddHour After default programming, the pa

Summary of the content on the page No. 9

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK limit or cascade sensor (T2) to operate the output device from Setting Guidelines for Proportional Band of P and full open (100%) to full closed (0%) or vice versa. P+I Control Xp1 is the throttling range for the main control loop, Xp2 is To estimate the proportional band (throttling range X ) for p used if limitation or cascade control (submaster control loop) stable control under all different load conditions, the con

Summary of the content on the page No. 10

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK Table 12. Calculation of summer/winter compensation Setting Guidelines for Reset Time of P+I Control outdoor air The reset time tr should be adjusted to 2...3 times of the control room temp. throttling temp. response time T , which is the time interval between the u schedule (T1) range (X ) P (T3/T ) beginning of a sustained disturbance (e.g. rapid step change comp of valve position) and the instant when the resulting

Summary of the content on the page No. 11

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK If the controller is in OFF mode, the time schedule program Y (%) overrides the minimum position by the ON/OFF input for plant/system shut off and the damper is driven into the fully 100 closed position at OFF condition together with the heating and UNOCCUPIED cooling valve actuators. OCCUPIED Runtimex, x = Y1, Y2, or Y3 (P.21...P.23) The control parameters Runtimex (x = Y1 for R7426A; x = Y1, Y2 or Y3 for R7426B) ar

Summary of the content on the page No. 12

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK Changing Operating Modes Fig. 7 shows the six operating modes. After power-up the Pushing the SET and SEL button simultaneously for approx. controller version is displayed and the controller enters the 1 sec causes the controller to leave the standard display standard display mode. In this mode, selected input or output mode and to enter the output data selection mode (Fig. 11). values and on controllers with real-time clo

Summary of the content on the page No. 13

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK Time Out After approximately 10 min of inactivity (no button has been by the SET button are ignored by the controller and old pressed: time out), each mode returns automatically to parameter values will be retained. standard display mode. Inputs that have not been confirmed A B A °C TIME & SUBMASTER / LIMIT SETPOINT WEEKDAY CTRP2 We ON CONTROLLERS WITH REAL-TIME CLOCK, ONLY Date °C COMPENSATION DATE TEMPERATURE T3 We °C %

Summary of the content on the page No. 14

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK Displaying Actual Values °C In the standard display mode, one of nine actual values, the actual time, or the date can be selected and displayed by pushing the SEL button. The icons of the permanently displayed controller mode are °C described in the following table: Table 13. Icons controller mode / status display Off OFF - icon FIRST DISPLAYED CONFIGURATION 1) PARAMETER: ACTUAL Night Moon - icon FOR R7426C PARAMETER V

Summary of the content on the page No. 15

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK • To release the manual override (fixed) of the output, select the output, enter output adjustment mode and push the + and - button simultaneously. Pushing the SEL button leads back to standard display mode. WITH : MANUAL OVERRIDE IS ACTIVE % % R7426B WITHOUT : AND R7426C, CONTROL LOOP ONLY IS ACTIVE % Fig. 11. Output Selection Mode % % OUTPUT OUTPUT SELECTION SELECTION % % TO ADJUST OUTPUT O

Summary of the content on the page No. 16

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK Using the Schedules (with RTC, only) a normal day (day type = H0 is default). The function is Two schedules, one for programming the schedule points and described as follows: one for holiday programming, are available. • H0: no holiday - the weekday schedule applies The standard schedule is used to switch the controller mode (off, night, standby or comfort) at programmed schedule • H1: free programmable as for a weekday,

Summary of the content on the page No. 17

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK Selecting Clock and Schedules (with RTC, only) Programming Standard Schedule (with RTC, only) The standard schedule programming is used to program up to DATE & TIME DATE & TIME 6 schedule points for each weekday as well as for three SELECTION ADJUSTMENT holiday types. The controller mode (off, night, standby or comfort) will be switched at these programmed schedule points. The first step of the schedule programming (see Fi

Summary of the content on the page No. 18

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK Programming Holiday Schedule (with RTC, only) Interpreting Error Messages The holiday schedule programming is used to program each Different analog input errors can be identified by the controller day of the year (01.01 ... 31.12.) as a holiday (day type = H1, (Error handling). The defective analog input (T1, T2, T3 or H2 or H3) or as a normal day (day type = H0 is default). X ) will be displayed in the standard display m

Summary of the content on the page No. 19

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK NOTES (WITH RTC, ONLY) ) day Jan. Feb. March April May June July August Sept. Oct. Nov. Dec. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21.

Summary of the content on the page No. 20

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK point 1 point 2 point 3 point 4 point 5 point 6 1) day 2) 2) 2) 2) 2) 2) time SMode time SMode time SMode time SMode time SMode time SMode Mo Tu We Th Fr Sa Su H1 H2 H3 1) 2) Weekday or holiday type; Programmed controller mode (schedule mode) Table 17. Weekly schedule and holiday types


Alternative user manuals
# User manual Category Download
1 Honeywell 191108AJ User manual Thermostat 629
2 Honeywell 42011076-003 User manual Thermostat 204
3 Honeywell 69-0786-2 User manual Thermostat 57
4 Honeywell 69-1776EFS-01 User manual Thermostat 56
5 Honeywell 72838 User manual Thermostat 42
6 Honeywell 69-2485EFS-03 TH8320ZW1000 User manual Thermostat 48
7 Honeywell 5-2-DAY DELUXE RTH6300B User manual Thermostat 50
8 Honeywell 7300 User manual Thermostat 20
9 Honeywell 69-1490 User manual Thermostat 10
10 Honeywell 8000 User manual Thermostat 90
11 Honeywell 8160 User manual Thermostat 9
12 Honeywell 9820i User manual Thermostat 8
13 Honeywell 8162 User manual Thermostat 3
14 Honeywell 7351F User manual Thermostat 30
15 Honeywell AC-220-7 User manual Thermostat 3
16 Edelbrock 2116 User manual Thermostat 0
17 A&D MF-50 User manual Thermostat 8
18 A&D ML-50 User manual Thermostat 8
19 A&D MS-70 User manual Thermostat 15
20 Acu-Rite D1523 User manual Thermostat 2