Summary of the content on the page No. 1
INSTALLATION INSTRUCTIONS
SSDV Direct-Vent
Gas Fireplaces
P/N 700031M Rev. F 01/2011
This manual is one of a set of two supporting this product.
MODELS
Refer to P/N 725035M for Care and Operation Instructions.
MILLIVOLT: ELECTRONIC:
Ce manuel est disponible en francais, simplement
SSDVST-CNM-B SSDVST-CNE-B
en faire la demande. Numéro de la pièce 700031CF.
SSDVPF-CNM-B SSDVPF-CNE-B
Portland
US
OTL Report No. 116-F-32-5
INSTALLER: Leave this manual with the appliance.
CONSUMER:
Summary of the content on the page No. 2
PACKAGING GENERAL INFORMATION TABLE OF CONTENTS Packaging .........................................Page 2 The assembled vented gas fireplace heater is packaged with: Introduction ......................................Page 2 WARNING 1 - One log set located in firebox area. General Information ..........................Page 2 2 - One envelope containing the literature Young children should be care- Requirements for the package, located in the firebox which fully supervised when th
Summary of the content on the page No. 3
The appliance, when installed, must be electri- Note: Installation and repair should be done cally grounded and wired in accordance with WARNING by a qualified service person. The appliance local codes or, in the absence of local codes, should be inspected before use and at least with the National Electrical Code, ANSI/NFPA Improper installation, adjust- annually by a professional service person. 70 - latest edition, or the Canadian Electrical ment, alteration, service or More fre
Summary of the content on the page No. 4
O I O L I P T O IGNITER OFF ON CONTROL it TPTH TP TH L I P F LO F Gas Pressure - All Models Orifice Sizes - Sea Level to High Altitude ON / OFF Switch (All Models) Manifold Pressure Tables 3 and 4 show the appliances' gas Port Inlet These appliances are tested and approved for pressure requirements: Pressure installation at elevations of 0-4500 feet (0-1372 Port meters) above sea level using the standard Inlet Gas Supply Pressure burner orifice sizes (marked with an "*" in Table (all mo
Summary of the content on the page No. 5
COLD CLIMATE INSULATION For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other open- Offset Venting Vertical ings should be caulked or stuffed with unfaced (one end flush Venting with wall) fiberglass insulation. If the fireplace
Summary of the content on the page No. 6
VENT TERMINATION CLEARANCES Vertical Vent Termination Clearances Termination Heights For Vents These instructions should be used as a TERMINATION HEIGHTS FOR VENTS ABOVE Above Flat Or Sloped Roofs guideline and do not supersede local codes FLAT OR SLOPED ROOFS Ref. NFPA 54 / ANSI Z223.1 Horizontal Overhang in any way. Install venting according to local Roof Pitch * Feet * Meters codes, these instructions, the current National 2 FT Vertical MIN. Fuel Gas Code (ANSI-Z223.1) in the USA o
Summary of the content on the page No. 7
V EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS NOTE: Local Codes Or Regulations May Require Different Clearances. * See Item D in the Text Below. N P N NOTE: Location Of The Vent Termination Exterior Wall Inside Must Not Interfere With Access To The Corner Detail O Electrical Service. *18” V V G Q Horizontal Termination V 6” Ventilated Soffit A Inside Corner = 9” in U.S. � A = 12” in Canada Detail D H 3 ft. B B D E X C � A � A V V L Fixed Operable V Closed Window 3 ft. Window V
Summary of the content on the page No. 8
MINIMUM CLEARANCES TO COMBUSTIBLES Appliance and Vent Clearances Maintain clearances from appliance to Hearth Extension - A hearth extension is not required with this appliance. If a hearth extension is used, combustible materials as detailed in Table do not block the lower control compartment access door. Any hearth extension used is for appearance 6, with the following exception: When the only and does not have to conform to standard hearth extension installation requirements. appliance i
Summary of the content on the page No. 9
Step 1. FRAMING TYPICAL INSTALLATION SEQUENCE WARNING Frame these appliances as illustrated in Figures The typical sequence of installation is outlined Failure to position the parts in 12 and 13 on Pages 10 and 11. All framing below. However, each installation is unique accordance with these diagrams details must allow for a minimum clearance to and may result in variations to the steps or failure to use only parts specifi- combustible framing members as shown in described. c
Summary of the content on the page No. 10
FIREPLACE SPECIFICATIONS - SSDVST (SEE-THROUGH) • Inches (millimeters) SPECIFICATIONS • Minimum Framing Stud Size is 2 x 4 • See side views of fireplace below for Natural and Propane 37,500 gas line inlet location options. (MV Low 30,000) Gas BTU Input **25-1/4 11-3/8 (641) (289) 4-1/2" Inner 10-1/2 Co-axial DV Vent Size Vent Framing - 7-1/2" Outer (267) Dimension A Top Vent With Vent Center - Top Secure Vent 47-1/8 (1194) Vent with one 90 One 90º Elbow 10-1/2 Secure Flex 47-7/8 (1216
Summary of the content on the page No. 11
FIREPLACE SPECIFICATIONS - SSDVPF (PENINSULA VIEW) Fireplace Framing Specifications • Inches (millimeters) SPECIFICATIONS • Minimum Framing Stud Size is 2 x 4 • See right side viewsof fireplace below for gas line inlet location options. Natural & Propane 37,500 inches (millimeters) **25-1/4 11-3/8 (MV Low 30,000) Gas BTU Input (641) Minimum Framing Stud Size is 2 x 4 10-1/2 Dimension A 4-1/2" Inner (267) Co-axial DV Vent Size Vent Center - Top Secure Vent 47-1/8 (1194) Vent Framing - Top Vent 7
Summary of the content on the page No. 12
Step 2. ROUTING GAS LINE Proper Sizing of Gas Line Notes: • All appliances are factory-equipped with a Properly size and route the gas supply line Route a gas line along the inside of the right flexible gas line connector and 1/2 inch shutoff from the supply regulator to the area where side framing as shown in Figure 14. Gas valve (see Figure 47 on Page 27). the appliance is to be installed per require- lines must be routed, constructed and made • See Massachusetts Requirements on Page men
Summary of the content on the page No. 13
Step 3. INSTALL THE VENT SYSTEM Vent Seal Cap Insulation General Information These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada. CROSS SECTION (INSIDE of (OUTSIDE of Ensure clearances are in accordance with local installation codes and Appliance) Appliance) the requirements
Summary of the content on the page No. 14
VERTICAL TERMINATION SYSTEMS (ROOF) VENT SECTION LENGTH CHART VENT SECTION LENGTH CHART T Nominal 6 12 24 36 48 Nominal Section 6 12 24 36 48 VENT SECTION LENGTH CHART See Figure 18 and Figures 27 to 31 (Pages 17 T O Length (inches) Section Length O T Nominal Section and 18) and their associated Vertical Vent Tables T VENT SECTION LENGTH CHART 6 12 24 36 48 (inches) T O Length (inches) A Net Section 4 ½ 10 ½ 22 ½ 34 ½ 46 ½ Nominal illustrate the vertical venting configurations that T T A Net Se
Summary of the content on the page No. 15
Vertical (offset) Installation D. Install firestop / spacer at ceiling - When B. Attach vent components to appliance - Se- cure Vent SV4.5 direct-vent system compo- using Secure Vent, use SV4.5VF firestop / Analyze the vent routing and determine the nents are unitized concentric pipe components spacer at ceiling joists; when using Secure number of vent sections and elbows required. featuring positive twist lock connections (see Flex, use SF4.5VF firestop / spacer. If there is Refer to Ver
Summary of the content on the page No. 16
Use a carpenter’s level to measure from a SV4.5CGV-1 SV4.5FA or constant surface and adjust the support straps Termination SV4.5FB Flashing Storm as necessary. and SV4.5SC Collar Storm Collar It is important to maintain the required clear- 1” (25.4 mm) ances to combustibles: 1" (25 mm) at all sides vWhen using Minimum for all vertical runs; and 3" (76 mm) at the top, secure Flex, use Clearance to 1" (25 mm) at sides, and 1" (25 mm) at the Firestop/Spacer Combustibles bottom for all ho
Summary of the content on the page No. 17
VERTICAL VENT FIGURES/TABLES Table A u When using Secure Flex, use Firestop Notes: V Minimum / Spacer SF4.5VF H Maximum • Secure Vent™ (rigid vent pipe) is shown in the Figures; Secure Flex™ (flexible vent feet (meter) feet (meter) pipe) may also be used. 2 (0.610) 1 (0.305) • It is ver y important that the horizontal/ inclined run be maintained in a straight (no 4 (1.219) 2 (0.610) dips) and recommended to be in a slightly u Ceiling Firestop / Spacer (SV4.5VF) 6 (1.829) 3 (
Summary of the content on the page No. 18
VERTICAL VENT FIGURES / TABLES (CONTINUED) Table C H1 H+H Maximum H Maximum V Minimum 1 feet (meter) feet (meter) feet (meter) u Ceiling Firestop / Spacer 5 (1.524) 2 (0.610) 1 (0.305) (SV4.5VF) 10 (3.048) 4 (1.219) 2 (0.610) 15 (4.572) 6 (1.829) 3 (0.914) 20 (6.096) 8 (2.438) 4 (1.219) Wall Firestop/ v V + V + H + H = 40 feet (12.2 m) Max 1 1 Spacer (SV4.5HF) H = 8 feet (2.438 meters) Max. V1 H + H = 20 feet (6.096 meters) Max. u Ceiling Firestop / 1 Spacer (SV4.5VF) u When using Secure
Summary of the content on the page No. 19
Push the vent component against the previous Support Horizontal / Inclined Run Building section until it fully engages, then twist the Brackets Support component clockwise running the dimples Framing down and along the incline channels until they SV4.5HT-2 SV4.5E90 seat at the end of the channels. This seating Termination Elbow Shown position is indicated by the alignment of the arrow and dimple as shown in Figure 20 on Page 15. SV4.5L6/12/24/36/48 Vent Sections Exterior Firestop / Spac
Summary of the content on the page No. 20
J. Assemble vent run to exterior wall - If not previously measured, locate the center of the To help minimize water infiltration it is recommended that the Firestop/Spacer vent at the exterior wall. Prepare an opening (SV4.5HF) be installed on the exterior as described in Step B. Assemble the vent side of the wall. system to point where the terminus of the last SV4.5 HT-2 Termination section is located relative to the exterior surface 7" (178) to which the termination is to be attached as