Streszczenie treści zawartej na stronie nr. 1
INSTALLATION
2011 Lennox Industries Inc. INSTRUCTIONS
Dallas, Texas, USA
®
Elite Series XP13 Units
HEAT PUMPS
506728−01
These instructions are intended as a
Litho U.S.A.
06/11
general guide and do not supersede
Supersedes 04/11
local codes in any way. Consult
authorities having jurisdiction before
TABLE OF CONTENTS
installation.
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . 1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Model Num
Streszczenie treści zawartej na stronie nr. 2
Model Number Identification X P 13 −036 −230 −08 Refrigerant Type Minor Revision Number X = HFC−410A Voltage 230 = 208/230V−1ph−60hz Unit Type P = Heat Pump Outdoor Unit Nominal Cooling Capacity 018 = 1.5 tons Series 024 = 2 tons 030 = 2.5 tons 036 = 3 tons 042 = 3.5 tons 048 = 4 tons 060 = 5 tons Unit Dimensions − Inches (mm) LIQUID LINE CONNECTION C ELECTRICAL INLETS A SUCTION LINE CONNECTION 4−3/4" 4−1/4" (121) (107) B TOP VIEW SIDE VIEW UNIT SUPPORT UNIT SUPPORT FEET FEET 9−1/2 13−7/8 8−1/2
Streszczenie treści zawartej na stronie nr. 3
Typical Unit Parts Arrangement CONTROL PANEL CAPACITOR (C12) CONTACTOR− DEFROST CONTROL 1POLE (K1−1) (CMC1) THERMAL PROTECTION SWITCH (S173) GROUND LUG SWITCH COVER ONLY ON UNITS USING EXTERNAL SWITCH COMPRESSOR MUFFLER 5−TON UNIT EXAMPLED HERE DEFROST TRUE SUCTION THERMOSTAT (S6) PORT CHECK EXPANSION VALVE REVERSING VALVE REVERSING VALVE SOLENOID CRANKCASE HEATER (−042, −048 AND 060 LIQUID LINE FILTER UNITS ONLY) DRIER (BI−FLOW) CRANKCASE HEATER THERMOSTAT (S40) LOW PRESSURE (−042, −048 AND 060
Streszczenie treści zawartej na stronie nr. 4
Caps and Fasteners Torque Requirements Operating Gauge Set and Service Valves IMPORTANT IMPORTANT To prevent stripping of the various caps used, the Only use Allen wrenches of sufficient hardness (50Rc − appropriately sized wrench should be used and fitted Rockwell Harness Scale minimum). Fully insert the snugly over the cap before tightening. wrench into the valve stem recess. OPERATING SERVICE VALVES Service valve stems are factory−torqued (from 9 ft−lbs for The liquid and vapor line service
Streszczenie treści zawartej na stronie nr. 5
Operating Angle−Type Service Valve: 1. Remove stem cap with an appropriately sized wrench. INSERT HEX−HEAD 2 2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" EXTENSION HERE for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open the service valve. SERVICE PORT CAP TO INDOOR UNIT SERVICE PORT CORE TO OUTDOOR SERVICE PORT UNIT CORE (VALVE STEM SHOWN OPEN) VALVE STEM INSERT HEX WRENCH HERE SHOWN CLOSED TO INDOOR RE
Streszczenie treści zawartej na stronie nr. 6
Recovering Refrigerant from Existing System CONNECT MANIFOLD GAUGE SET DISCONNECT POWER Connect a manifold gauge set, clean recovery cylinder and a Disconnect all power to the existing outdoor unit at the disconnect 2 1 recovery machine to the service ports of the existing unit.. switch and/or main fuse box/breaker panel. NOTE Use the recovery machine instructions to make the correct manifold gauge set connections for recovery MAIN FUSE refrigerant. The illustration below is a typical connecti
Streszczenie treści zawartej na stronie nr. 7
New Outdoor Unit Placement higher ground will not collect around the unit. The slab CAUTION should have a slope tolerance as described in figure 5, detail B. In order to avoid injury, take proper precaution when lift- NOTE If necessary for stability, anchor unit to slab as ing heavy objects. described in figure 5, detail D. Remove existing outdoor unit prior to placement of new ELEVATING THE UNIT outdoor unit. See Unit Dimensions on page 2 for sizing Units are outfitted with elongated support
Streszczenie treści zawartej na stronie nr. 8
Outside Unit Placement DETAIL A Slab Mounting at Ground Level DETAIL B Install unit away from windows. Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure. BUILDING STRUCTURE MOUNTING SLAB GROUND LEVEL TWO 90° ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION. Elevated Slab Mounting Slab Side Mounting DETAIL D DETAIL C using Feet Extenders #10 1/2" LONG SELF−DRILLING SHEET
Streszczenie treści zawartej na stronie nr. 9
Removing and Installing Panels LOUVERED PANEL REMOVAL IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR Remove the louvered panels as follows: ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL. 1. Remove two screws, allowing the panel to swing open PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR slightly. ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL. 2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinged corner p
Streszczenie treści zawartej na stronie nr. 10
Line Set Requirements This section provides information on: installation of new or Model (XP13) and size of unit (e.g. −036). replacement line set. Line set diameters for the unit being installed as listed Adding Polyol ester oil requirements in table 2 and total length of installation. New or replacement line set installation Number of elbows vertical rise or drop in the piping. Using existing line set. USING EXISTING LINE SET ADDING POLYOL ESTER OIL REQUIREMENTS Things to consider:
Streszczenie treści zawartej na stronie nr. 11
Line Set Isolation The following illustrations are examples of proper refrigerant line set isolation: REFRIGERANT LINE SET TRANSITION REFRIGERANT LINE SET INSTALLING VERTICAL RUNS (NEW CONSTRUCTION SHOWN) FROM VERTICAL TO HORIZONTAL NOTE Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the ANCHORED HEAVY NYLON temperature of the liquid line or when pressure drop is equal to or greater WIRE TIE OR AUTOMOTIVE AUTOMOTIVE
Streszczenie treści zawartej na stronie nr. 12
Brazing Connections Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves. WARNING IMPORTANT Polyol Ester (POE) oils used with HFC−410A Allow braze joint to cool before removing the wet rag refrigerant absorb moisture very quickly. It is very from the service valve. Temperatures above 250ºF can important that the refrigerant system be kept closed damage valve seals. as much as possible. DO NOT remove line set caps or service valve stub caps until you ar
Streszczenie treści zawartej na stronie nr. 13
CAP AND CORE REMOVAL CUT AND DEBUR Cut ends of the refrigerant lines square (free from nicks or dents) Remove service cap and core from both the suction / vapor and 2 1 and debur the ends. The pipe must remain round. Do not crimp end liquid line service ports. of the line. CUT AND DEBUR SERVICE PORT SERVICE PORT CAP CORE LINE SET SIZE MATCHES SERVICE VALVE CONNECTION SERVICE VALVE SERVICE CONNECTION PORT COPPER TUBE CORE STUB REDUCER SUCTION / VAPOR LINE SERVICE VALVE (BALL−TYPE FOR −060 AND AN
Streszczenie treści zawartej na stronie nr. 14
WRAP SERVICE VALVES To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use 4 additional water saturated cloths underneath the valve body to protect the base paint. FLOW NITROGEN Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and 5 out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set conne
Streszczenie treści zawartej na stronie nr. 15
VAPOR LIQUID Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 16. TYPICAL EXISTING FIXED ORIFICE TYPICAL EXISTING EXPANSION VALVE REMOVAL REMOVAL PROCEDURE (UNCASED OR PROCEDURE (UNCASED COIL SHOWN) 1B 1A COIL SHOWN) STUB END TWO PIECE PAT
Streszczenie treści zawartej na stronie nr. 16
Installing New Indoor Metering Device This outdoor unit is designed for use in HFC−410A systems that use a check / expansion valve metering device (purchased separately) at the indoor coil. See the Lennox XP13 Engineering Handbook for approved check / expansion valve kit match−ups. The check / expansion valve device can be installed either internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the check / expansion v
Streszczenie treści zawartej na stronie nr. 17
Leak Test Line Set and Indoor Coil IMPORTANT Leak detector must be capable of sensing HFC refrigerant. CONNECT GAUGE SET A Connect an HFC−410A manifold gauge set high pressure hose to the LOW HIGH vapor valve service port. NOTE Normally, the high pressure hose is connected to the liquid MANIFOLD GAUGE SET line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage. B With both manifold valves closed, connect the cylinder of HFC−410A ref
Streszczenie treści zawartej na stronie nr. 18
Evacuating Line Set and Indoor Coil Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts. CONNECT GAUGE SET LOW HIGH NOTE Remove cores from service valves (if not already done). 1
Streszczenie treści zawartej na stronie nr. 19
Electrical IMPORTANT In the U.S.A., wiring must conform with current local codes Use a thermocouple or thermistor electronic vacuum and the current National Electric Code (NEC). In Canada, gauge that is calibrated in microns. Use an instrument wiring must conform with current local codes and the current capable of accurately measuring down to 50 microns. Canadian Electrical Code (CEC). Refer to the furnace or air handler installation instructions for additional wiring application diagrams and re
Streszczenie treści zawartej na stronie nr. 20
Figure 14. Typical Unit Wiring Diagram 506728−01 Page 20