MITSUBISHI ELECTRIC AUTOMATION, INC 
 
UNINTERRUPTIBLE POWER SUPPLY SYSTEM 
 
9800A SERIES 
 
OWNERS / TECHNICAL MANUAL 
(For parallel operation possible model only.) 
Revision 2.03 Apr. 15, 05 
ALN-H0776 
 MITSUBISHI ELECTRIC 9800A SERIES UPS                                                                                                                                                                                                                                                           
                    
                    ملخص المحتوى في الصفحة رقم 2 
                    
                         Page Number: MITSUBISHI 9800A SERIES UPS  i     ELECTRIC OWNERS / TECHNICAL MANUAL    Preface                                                                               MITSUBISHI ELECTRIC 9800A SERIES UPS                                                                                                                                                                                                                                                                                                   
                    
                    ملخص المحتوى في الصفحة رقم 3 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS  ii   ELECTRIC OWNERS / TECHNICAL MANUAL    TABLE OF CONTENTS    LIST OF TABLES ................................................................................................ iii  LIST OF FIGURES .............................................................................................. iv  HOW TO USE THIS MANUAL ............................................................................ v    1.0  INTRODUCTION .....................................
                    
                    ملخص المحتوى في الصفحة رقم 4 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS  iii   ELECTRIC OWNERS / TECHNICAL MANUAL    List of Tables    Table 1.1 Power Specifications..................................................................... 1-13  Table 1.2 UPS Module Information............................................................... 1-13  Table 1.3 Detail of Specifications ................................................................. 1-13  Table 1.4 Rating of Contactor and Fuses........................................
                    
                    ملخص المحتوى في الصفحة رقم 5 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS  iv   ELECTRIC OWNERS / TECHNICAL MANUAL    List of Figures    Figure 1.1 Single Line Diagram-Normal Operation.................................................... 1-5  Figure 1.2 Single Line Diagram-Bypass Operation ................................................... 1-6  Figure 1.3 Single Line Diagram-Battery Operation.................................................... 1-7  Figure 1.4 UPS Parts Location.................................................
                    
                    ملخص المحتوى في الصفحة رقم 6 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS  v   ELECTRIC OWNERS / TECHNICAL MANUAL    How to use this Manual    This manual is designed for ease of use, giving the user easy and quick reference to  information.   This manual uses notice icons to draw attention to the user important information regarding the  safe operation and installation of the UPS. The notice icons used in this manual are explained  below, and should be taken into account and adhered to whenever they appear in the text of  th
                    
                    ملخص المحتوى في الصفحة رقم 7 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-1   ELECTRIC OWNERS / TECHNICAL MANUAL    1.0 INTRODUCTION    Your Mitsubishi Uninterruptible Power System (UPS) is designed to provide many years of  reliable protection from power failure, brown-outs, line noise, and voltage transients. To ensure  optimum performance of the equipment, follow the manufacturer's instructions. This manual  contains descriptions required to operate the UPS. Please read this manual carefully and retain  it for future 
                    
                    ملخص المحتوى في الصفحة رقم 8 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-2   ELECTRIC OWNERS / TECHNICAL MANUAL        WARNING  2        This UPS does not include a Bypass input circuit breaker (MCCB) to  protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be  field supplied and installed. Recommended Breaker (MCCB)'s  Specifications are as follows:    Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac) Breaker (A)  100 480 120 150   600 96 125  150 480 180 225   600 144 200  225 480 271 350   600 
                    
                    ملخص المحتوى في الصفحة رقم 9 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-3   ELECTRIC OWNERS / TECHNICAL MANUAL        1.1  GENERAL    The Mitsubishi 9800A SERIES UPS is designed to provide continuous and clean electrical  power to a critical load. Additionally the UPS monitors power conditions affecting the load.   In the event of an input power failure, the UPS will supply power to the critical load for the  specified battery time.    If the input power is not restored promptly, back up power from the UPS battery perm
                    
                    ملخص المحتوى في الصفحة رقم 10 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-4   ELECTRIC OWNERS / TECHNICAL MANUAL    1.2  Definitions    UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS  Module Cabinet and associated batteries that function as a system to provide continuous,  conditioned AC power to a load. This is sometimes referred to as the "System".     UPS MODULE CABINET - The metal enclosure which contains the Rectifier, the Inverter,  the Chopper, the Static Transfer Switch, the Internal By
                    
                    ملخص المحتوى في الصفحة رقم 11 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-5   ELECTRIC OWNERS / TECHNICAL MANUAL    1.3  Overview     The UPS provides two power paths between the utility source and the critical load.   Figure 1.1 shows the path for normal operation, with the load powered from the inverter.  Figure 1.2 shows the path for bypass operation, with the load supplied through the static  bypass line.    A) Normal operation: Load power supplied by each system UPS inverter.    Figure 1.1  Single Line Diagram - Nor
                    
                    ملخص المحتوى في الصفحة رقم 12 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-6   ELECTRIC OWNERS / TECHNICAL MANUAL    The Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field  supplied and field installed. (See WARNING 2 on page 1-2)        B) Bypass Operation: Load Power supplied through each system UPS internal static  bypass line.    FIGURE 1.2  Single Line Diagram - Bypass Operation: Load fed through Internal static  bypass line.      CB  Static Transfer   AC Bypass    Input Switch  CB3 Us
                    
                    ملخص المحتوى في الصفحة رقم 13 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-7   ELECTRIC OWNERS / TECHNICAL MANUAL    C) Battery operation: Load Power supplied by each system UPS battery and inverter.    FIGURE 1.3  Single Line Diagram - Battery Operation      CB  Static Transfer   AC Bypass    Switch Input  CB3 User supplied   MCCB  RECTIFIER INVERTER 52S   AC input   Output  CB1 52C     CB2 Power Flow    Not in Use    Battery cabinet UPS Module        Referring to Figure 1.3: In the event of AC input source failure or in
                    
                    ملخص المحتوى في الصفحة رقم 14 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS    1-8   ELECTRIC OWNERS / TECHNICAL MANUAL  FIGURE 1.4-a  UPS Parts Location (100kVA, 150kVA, 225kVA)    UPS module   FRONT VIEW   Inverter     AC capacitors  Chopper   unit    DC     capacitors Rectifier unit    1. CPM     52S    CB3    CB1  3. External I/F    circuit PCB  IOAU-04          2. Grounding Bar  52C      FIGURE 1.4-b  UPS Parts Location (300kVA,375kVA)    UPS module   FRONT VIEW 52S  2. Grounding  52C     Bar  3. External I/F   CB1    circ
                    
                    ملخص المحتوى في الصفحة رقم 15 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS      1-9   ELECTRIC OWNERS / TECHNICAL MANUAL    FIGURE 1.4-c  UPS Parts Location (500kVA)      UPS module   FRONT VIEW     3. External I/F circuit PCB  IOAU-04    1. CPM    52S  2. Grounding Bar  AC capacitors      52C     CB1        Rectifier    unit    AC capacitors        CB3        DC   Inverter     Capacitors Chopper  unit       MITSUBISHI ELECTRIC 9800A SERIES UPS                                                                                    
                    
                    ملخص المحتوى في الصفحة رقم 16 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS      1-10  ELECTRIC OWNERS / TECHNICAL MANUAL  FIGURE 1.4-d  UPS Parts Location (750kVA)      UPS module   FRONT VIEW    3. External I/F circuit PCB  IOAU-04 AC capacitors    2. Grounding Bar    52C 52S      CB1      1. CPM         CB3        AC capacitors      DC    Capacitors Rectifier  Inverter     unit  Chopper  unit       MITSUBISHI ELECTRIC 9800A SERIES UPS                                                                                            
                    
                    ملخص المحتوى في الصفحة رقم 17 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS      1-11  ELECTRIC OWNERS / TECHNICAL MANUAL    FIGURE 1.5 UPS Parts Location (Continued)    UPS module     REAR OF FRONT DOOR (Right side)                                                    SYNC.LED   5 6  INVERTER INVERTER    START STOP  | |                      | | | |    FAULT MAINTENANCE TEST BOOT  SWITCH RESET SWITCH SWITCH    10 9  7 8        FIGURE 1.6  External I/F circuit PCB IOAU-04      3. External contact signal terminal    IOAU-04 4. RS23
                    
                    ملخص المحتوى في الصفحة رقم 18 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS      1-12  ELECTRIC OWNERS / TECHNICAL MANUAL    Description of Figures 1.4, 1.5, and 1.6:    1. CPM - Circuit protector for control power supply.  2. Grounding bar (G)  3. External contact signal terminal block (FIGURE 1.6) - Terminal block to connect  contact signal input/output lines to and from the external devices. Refer to Figure 2.15  section 2.4 for details.  4. RS232C communication connector (FIGURE 1.6) - Refer to Figure 2.18 section 2.5 for  
                    
                    ملخص المحتوى في الصفحة رقم 19 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS      1-13  ELECTRIC OWNERS / TECHNICAL MANUAL    1.4  Specifications    The UPS name plate displays the rated kVA as well as nominal voltages and currents. The  name plate is located on the inside of the UPS front door.      TABLE 1.1  Power Specifications  Rated output Input voltage Bypass input voltage Output voltage  Power 3 phase / 3 wire 3 phase / 4 wire 3 phase / 3 or 4 wire  100kVA /  80kW 480V 480V or 600V 480V or 600V  150kVA / 120kW 480V 480V 
                    
                    ملخص المحتوى في الصفحة رقم 20 
                    
                          Page Number: MITSUBISHI 9800A SERIES UPS      1-14  ELECTRIC OWNERS / TECHNICAL MANUAL    TABLE 1.3  Detail of Specifications     Rated Output kVA 100 150 225 300 375 500 750  Rated Output kW 80 120 180 270 338 450 675  AC INPUT  Configuration 3 phase, 3 wire  Voltage 277/480 V, 346/600 V    +15% to -15%  Frequency 60 Hz +/-5%  Reflected Current THD 6% max. at 100% load;  9% max. at 50% load  STATIC BYPASS INPUT  Configuration 3 phase, 4 wire   Voltage 277/480 V, 346/600 V    +/-10%  Frequency