                        Phoenix 300 High Capacity Dehumidifier 
Part number TS-218
PO Box 8680 • Madison, WI 53708
Owner’s Manual   —   Phoenix 300
Installation, Operation and Service Instructions
Read and Save These Instructions
The Phoenix 300 Dehumidifier is designed to maximize the water removal capacity from a single 0V, 5 amp circuit. 
The multiple ducting options on the Phoenix 300 allows for ducting both the intake air and the filtered and 
dehumidified supply air. This makes it possible to easily combine th
                    
                    ملخص المحتوى في الصفحة رقم 2 
                    
                        Table of Contents  1 Specifications Introduction ................................................................ Part No. 4022599 1.  Specifications ........................................................2 Power 2 amps, 5 Vac, Grounded 2.  Operation .............................................................2 Water 76 pints/da  y @ AHAM 80°F, 60% RH   2.  T  ransporting the Phoenix 300 ..........................2 Removal 304 pints/day maximum @ 90°F, 90% RH  2.2  Location .............
                    
                    ملخص المحتوى في الصفحة رقم 3 
                    
                        2.3 Electrical Requirements 2.8 Pump Fail Light The Phoenix 300 can be plugged into a grounded 5 Amp If the condensate pump fails, water draining into the pump  circuit. At 80°F, 60% RH, it draws .e Amps. Due to the  reservoir will fill above its normal level. A safety float  high percentage of a 5 Amp circuit’s capacity that the switch will then turn on the pump fail light (located next  unit uses, the circuit should be dedicated to running it to the pump purge switch) and stop the compress
                    
                    ملخص المحتوى في الصفحة رقم 4 
                    
                        5.  Replace the cover. 3.3 Storage Change the timer pegs back to the original pattern for use  There are two issues to consider when the Phoenix 300 is  above 50°F. stored between uses and both pertain to the water trapped  in the unit: damage caused by freezing and biological  growth. The effect of the trapped water can be greatly  reduced if precautions are taken to remove as much as  possible before storage. .  Use the pump purge switch (see Sec. 2.7 and Fig. 3)  to  reduce the water level i
                    
                    ملخص المحتوى في الصفحة رقم 5 
                    
                        coil where it absorbs heat from the incoming air and 5. Defective compressor (Sec. 4.6). evaporates. 6. Defective relay (Sec. 4.9). 7. Defective time delay (Sec. 4.0). No dehumidification. Blower runs but compressor does not.  Pump fail light not lit. . Bad connection in compressor circuit (Fig. 3). 2. Defective compressor capacitor (Sec. 4.6A). 3. Defective compressor overload (Sec. 4.6A). 4. Defective compressor (Sec. 4.6). 5. Defective relay (Sec. 4.9). 6. Defective time delay (Sec. 4.0). 
                    
                    ملخص المحتوى في الصفحة رقم 6 
                    
                        Evaporator coil frosted continuously, low dehumidifying 4.6A Checking Compressor Motor Circuits capacity. Perform the following tests if the blower runs but the  compressor does not with the power switch ON. . Defrost thermostat loose or defective   (Sec. 2.0 and 4.7). . Turn the power switch OFF and unplug the unit, remove  the cabinet front (6 screws). 2. Defrost timer incorrectly set or defective  2. Plug in the unit and turn the power switch ON. Use   (Sec. 2.0 and 4.7).  a voltmeter to 
                    
                    ملخص المحتوى في الصفحة رقم 7 
                    
                        and water. These contaminants must be carefully removed running burn out has occurred, several filter/driers  otherwise even small residues will attack replacement may have to be replaced to remove all of the acid and  compressor motors and cause failures. moisture. The following procedure is effective only if the system is  monitored after replacing the compressor to insure that  NOTE: NEVER use the compressor to evacuate the system  the clean up was complete. or any part of it. .  This proced
                    
                    ملخص المحتوى في الصفحة رقم 8 
                    
                        4.9 Relay 4.10 Time Delay (HP model only) The contacts of the single pole, single throw relay The HP model has a time delay relay in the compressor  complete the power circuit to the compressor. The control circuit. This relay delays the compressor start  contacts are closed when power is provided to the relay about 2 minutes after the power switch is turned on.  coil via the control circuit. The control circuit includes the This reduces the unit’s starting amp draw by starting the  power switch
                    
                    ملخص المحتوى في الصفحة رقم 9 
                    
                        6 Service Parts Item  Part No. Qty. Description Items listed are not shown  40288   Accumulator  4022597  Wiring Diagram (on Cover)     (not shown)  2 4022636  Air Filter, Pleated, 2” x 20” x 20”  402950  Ground Fault Interrupter    402264  Air Filter, Pleated, 4” x 20” x 20”      (optional)     MERV-8  4023079  Coupling, Body,     4022624  Air Filter, Pleated, 4” x 20” x 20”      Quick Connect, .38 Tube    (90-95% EFFICIENT)  4023080  Coupling, Insert,   3 402083   Blower w/ Capa
                    
                    ملخص المحتوى في الصفحة رقم 10 
                    
                        This page intentionally left blank. Toll-Free 1-800-533-7533 0 www.thermastor.com • sales@thermastor.com                                                                                                                                                                                                                                                                                                                                                                                                           
                    
                    ملخص المحتوى في الصفحة رقم 11 
                    
                        Phoenix 300 Dehumidifier Limited Warranty Warrantor: Therma-Stor LLC  PO Box 8680  Madison, WI 53708  Telephone: -800-533-7533  Who Is Covered: This warranty extends only to the original end-user of the Phoenix 300  dehumidifier, and may not be assigned or transferred. First Year Warranty Therma-Stor LLC warrants that, for one () year the Phoenix 300 dehumidifier  will operate free from any defects in materials and workmanship, or Therma-Stor LLC will, at its  option, repair or replace the def