ملخص المحتوى في الصفحة رقم 1 
                    
                        MODELS CG(N,L)150 & CG(N,L)200
COMMERCIAL GAS, GLASS-LINED, TANK-TYPE WATER HEATER
	 •		INST ALLA TION •		OPERA TION •		MAINTENANCE	•		LIMITED	W ARRANTY
Thank you for buying this energy efficient water heater. We 
appreciate your confidence in our products.
 CAUTION
TEXT IN BLACK BOLD TYPE OR UNDERLINED CONTAINS  
INFORMATION RELATIVE TO YOUR SAFETY.  PLEASE READ 
THOROUGHLY BEFORE INSTALLING AND USING THIS 
APPLIANCE.
300 Maddox Simpson Parkway
Lebanon, TN 37090
Phone: 615-889-8900 • Fax: 615-5
                    
                    ملخص المحتوى في الصفحة رقم 2 
                    
                        FIGURE 1 ROUGH-IN-DIMENSIONS TABLE 1 - HEATER PERFORMANCE DATA   Input Approx. RECOVERY RATING CAPACITIES (GPH) AT TEMPERATURE RISE SHOWN   Rate Tank Approx. F 20°F 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F  Model Btuh Cap. Eff. % C 11°C 17°C 22°C 28°C 33°C 39°C 44°C 50°C 56°C 61°C 67°C 72°C 78°C  CGN150032 150,000 NAT 32 Gal 80 GPH 727 485 364 291 242 208 182 162 145 132 121 112 104   44 kW/Hr. NAT 121 Litres  LPH 2752 1836 1378 1102 916 787 689 613 549 500 458 424 394  C
                    
                    ملخص المحتوى في الصفحة رقم 3 
                    
                        TABLE OF CONTENTS Page Page ROUGH-IN-DIMENSIONS ......................................................2 INSTALLATION DIAGRAMS .............................................. 11-17 FOREWORD ...........................................................................2 OPERATION ..........................................................................18 GENERAL SAFETY INFORMATION .......................................3  General .......................................................................
                    
                    ملخص المحتوى في الصفحة رقم 4 
                    
                        OPERATION OF THESE FANS CAN PRODUCE A NEGATIVE As elevation above sea level is increased, there is less oxygen  DRAFT IN THE AREA OF THE WATER HEATER PREVENTING per cubic foot of air.  Therefore, the heater input rate should be  THE PRODUCTS OF COMBUSTION FROM EXHAUSTING reduced at high altitudes for satisfactory operation with the reduced  THROUGH THE CHIMNEY OR VENT PIPE. oxygen supply.  Failure to make this reduction would result in an  overfiring of the heater causing sooting, poor combustio
                    
                    ملخص المحتوى في الصفحة رقم 5 
                    
                        possibility of changing the orientation by accidentally overtightening  EXHAUST INDUCER (BLOWER ASSEMBLY) the inlet supply.  Improper orientation of the Eliminator may cause  temperature buildup issues or spells of colder than usual water  All units are equipped with a exhaust inducer.  The inducer  temperatures. assists in drawing in fresh air to the unit for combustion and then  assists in dispensing the combustion by-products into the venting   HIGH LIMIT SWITCH leading outside. The digital t
                    
                    ملخص المحتوى في الصفحة رقم 6 
                    
                        LEVELING INSTALLATION INSTRUCTIONS If the unit is not level, insert the bolts which were used in crating  REQUIRED ABILITY into the legs to correct this condition. INSTALLATION OR SERVICE OF THIS WATER HEATER   CLEARANCES REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED  TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY,  These heaters are approved for installation on combustible flooring  VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED. in an alcove when the minimum clearance from any
                    
                    ملخص المحتوى في الصفحة رقم 7 
                    
                        FIGURE 6 - ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN ALCOVE CAUSING CARBONING OR SOOTING OF THE COMBUSTION Remove all soot or other obstructions from the chimney that will  retard a free draft. CHAMBER, BURNERS AND FLUE TUBES AND CREATES A  RISK OF ASPHYXIATION. Type B venting is recommended with these heaters.  Where an exhaust fan is supplied in the same room with a  This water heater must be vented in compliance with all local  heater, sufficient openings for air must be provided i
                    
                    ملخص المحتوى في الصفحة رقم 8 
                    
                         CAUTION A closed system will exist if a check valve (without bypass),  pressure reducing valve (without bypass), or a water meter  (without bypass) is installed in the cold water line between  the water heater and street main (or well).          Excessive pressure may develop in such closed systems,  FIGURE 7 causing premature tank failure or intermittent relief valve  operation.  This is not a warranty failure.  An expansion tank  • Where a separate vent connection is not available and the ven
                    
                    ملخص المحتوى في الصفحة رقم 9 
                    
                        To prevent damage, care must be taken not to apply too much  GAS PIPING torque when attaching gas supply pipe to gas valve inlet. Contact your local gas service company to ensure that adequate  Apply joint compounds (pipe dope) sparingly and only to the  gas service is available and to review applicable installation codes  male threads of pipe joints. Do not apply compounds to the first  for your area. two threads. Use compounds resistant to the action of liquefied  petroleum gases. Size the mai
                    
                    ملخص المحتوى في الصفحة رقم 10 
                    
                        Do not subject the combination gas valve to inlet gas  must conform to all local code authority having jurisdiction.  AN  pressures of more than 14.0” W.C. - natural gas.  A service ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF  regulator is necessary if higher gas pressures are encountered. ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION. Manifold gas pressure in inches of water column is 3.5. If any of the original wire as supplied with the appliance must be  0 0 The gas pressure specified refers
                    
                    ملخص المحتوى في الصفحة رقم 11 
                    
                        is installed on the heater.  The locations shown in the installation  INSTALLATION DIAGRAMS diagrams on the following pages are typical. GENERAL The discharge opening of the temperature and pressure relief  valve,  located in front of the heater must be piped to an open drain  and should not be subject to freezing temperatures. The type, size and location of the relief valves must be in  accordance with local codes.  The locations of the relief valves  Install in accordance with all local codes.
                    
                    ملخص المحتوى في الصفحة رقم 12 
                    
                        VERTICAL STORAGE TANK AND FORCED CIRCULATION  DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES.   SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20.  IF HIGHER PREHEAT  TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN  ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES. HORIZONTAL STORAGE TANK AND FORCED CIRCULATION 12                                                                                                                                   
                    
                    ملخص المحتوى في الصفحة رقم 13 
                    
                        TWO  TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE WITH RECIRCULATION OF SANITIZING LOOP  DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE  NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER TEMPERATURE AT FIXTURES.  SEE WATER TEMPERATURE CONTROL   CIRCULATION.  INSTALL ON OR CLOSE TO DISHWASHING  WARNING ON PAGE 20.  IF HIGHER PREHEAT TEMPERATURES ARE  MACHINE.  TOGGLE SWITCH MUST BE CLOSED (ON)  NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN   DURING THE RINSE OPERATION AND OPEN (
                    
                    ملخص المحتوى في الصفحة رقم 14 
                    
                        INSTALLATION DIAGRAMS-SIDE INLET/OUTLET USAGE A listed temperature and pressure relief valve of adequate  capacity is installed on the heater.  The locations shown in the  to freezing conditions.  DO NOT REDUCE, BLOCK OR PLUG  installation diagrams on the following pages are typical. THE DISCHARGE OPENING OF THE VALVE. The discharge opening of the temperature and pressure relief  valve must be piped to an open drain and should not be subject  TWO TEMPERATURE - TWO HEATERS,  ONE  PRE-HEATER/ONE -
                    
                    ملخص المحتوى في الصفحة رقم 15 
                    
                        ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURE   STORAGE WITH OR WITHOUT RECIRCULATION HEATER WITH OR WITHOUT MIXING VALVE   DANGER TEMPERATURE SETTING SHOULD NOT  EXCEED SAFE USE TEMPERATURE AT  FIXTURES. SEE WATER TEMPERATURE  CONTROL WARNING ON PAGE 20. IF HIGHER  PREHEAT TEMPERATURES ARE NECESSARY  TO OBTAIN ADEQUATE BOOSTER OUTPUT,  ADD AN ANTI-SCALD VALVE FOR HOT  WATER SUPPLIED TO FIXTURES. HEATER WITH MIXING VALVE AND RECIRCULATED SANITIZING LOOP NOTE 1: TOGGLE SWITCH CONTROLS 180
                    
                    ملخص المحتوى في الصفحة رقم 16 
                    
                        TWO TEMPERATURE - TWO PRE-HEATERS WITH MIXING VALVE OR BOOSTER HEATER  WITH OR WITHOUT BUILING RECIRCULATION TWO PRE-HEATERS WITH MIXING VALVE  DANGER TEMPERATURE SETTING SHOULD NOT  EXCEED SAFE USE TEMPERATURE AT  FIXTURES.  SEE WATER TEMPERATURE  CONTROL WARNING ON PAGE 20.  IF  HIGHER PREHEAT TEMPERATURES ARE  NECESSARY TO OBTAIN ADEQUATE  BOOSTER OUTPUT, ADD AN ANTI-SCALD  VALVE FOR HOT WATER SUPPLIED TO  FIXTURES. TWO PRE-HEATERS WITH BOOSTER HEATER 16                                       
                    
                    ملخص المحتوى في الصفحة رقم 17 
                    
                        MEDIUM TEMPERATURE - ONE HEATER WITH AUXILIARY STORAGE TANK FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION VERTICAL STORAGE TANK  * PIPE RELIEF VALVE TO OPEN  DRAIN.  **WHEN USING AN LOCHINVAR T-140, -200,    -350 OR -400 STORAGE TANK, USE         LOWER 3/4” OPENING FOR TANK     TEMPERATURE CONTROL.  IF BUILDING CIRCULATING LOOP IS USED,  CONNECT TO AN OPENING NEAR THE  BOTTOM OF THE TANK.  HORIZONTAL STORAGE TANK CAUTION: IF BUILDING COLD WATER SUPPLY HAS A  BACKFLOW PREVENTER, CHECK
                    
                    ملخص المحتوى في الصفحة رقم 18 
                    
                        into lockout.  After the controller tries three times, it will wait one  OPERATION hour before trying to light the unit again.  This cycle will continue  until the main burners are ignited or the unit is shut down. IMPORTANT A qualified person must perform the initial firing of the heater.  At ADJUSTMENTS this time the user should not hesitate to ask the individual any  ON INITIAL STARTUP SOME ADJUSTMENTS ARE NECESSARY. questions which they may have in regard to the operation and  maintenance of
                    
                    ملخص المحتوى في الصفحة رقم 19 
                    
                        FOR YOUR SAFETY READ BEFORE OPERATING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION  WARNING MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. A. This appliance does not have a pilot.  It is equipped with •	 I f 	 yo u 	 can n o t 	 reach 	 yo u r 	 g as 	 su p p l i er, 	 cal l 	 t h e 	 f i re  an ignition device which automatically lights the burner.  department. Do not try to light the burner by hand. C. Use only your hand to push in or turn the gas c
                    
                    ملخص المحتوى في الصفحة رقم 20 
                    
                          be set for 120° to 180°F water temperature, but 120°F is the  WATER TEMPERATURE CONTROL recommended starting point.  It is suggested the dial be placed  on the lowest setting which produces an acceptable hot water  supply.  This will always give the most energy efficient operation.   The temperature control has a 4°F (2°C) fixed differential. PREVENTIVE MAINTENANCE CHECK THE IGNITOR ASSEMBLY At least once a year, check the ignitor assembly, see Figure 11,  and the main burner, see Figure 12, f