ملخص المحتوى في الصفحة رقم 1 
                    
                        Owners & 
™
L676 Sunrise Gas Fireplace
Installation Manual
www.regency-fi re.com
MODELS:   L676S-NG1 Natural Gas   L676S-LP1 Propane
WARNING:  
FOR YOUR SAFETY
If the information in these instructions are not followed exactly, 
What to do if you smell gas:
a fi re or explosion may result causing property damage, 
 Do not try to light any appliance
personal injury or loss of life. 
 Do not touch any electrical switch: 
do not use any phone in your 
FOR YOUR SAFETY
building.
Do not store or use gaso
                    
                    ملخص المحتوى في الصفحة رقم 2 
                    
                        To the New Owner: Congratulations!  ® You are the owner of a state-of-the-art Gas Fireplace by REGENCY . The L676S has been  designed to provide you with all  the warmth and charm of a fi replace at the fl ick of a switch.   The model L676S has been approved by Warnock Hersey for both safety and effi ciency.  As  it also bears our own mark, it promises to provide you with economy, comfort and security  for many trouble free years to follow.  Please take a moment now to acquaint yourself with  ® the
                    
                    ملخص المحتوى في الصفحة رقم 3 
                    
                        TABLE OF CONTENTS Gas Line Installation ....................................................28 SAFETY LABEL Pilot Adjustment ...........................................................28 Gas Pipe Pressure Testing ..........................................28 Copy of Safety Decal .....................................................4 SIT 820 Valve Description ...........................................28 Aeration Adjustment ....................................................29 REQUIREMENTS Wiring
                    
                    ملخص المحتوى في الصفحة رقم 4 
                    
                        Model/Modele: Model/Modele: L676S-LP1 L676S-NG1 SAFETY LABEL This is a copy of the label that accompanies  each L676S-NG1 and L676S-LP1 Direct Vent  342 Gas Fireplace. We have printed a copy of the  contents here for your review.  DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ETIQUETTE ® NOTE: Regency units are constantly being  improved. Check the label on the unit and if  342 there is a difference, the label on the unit is  the correct one. Serial No. / No de serie Listed: VENTED GAS FIREPLA
                    
                    ملخص المحتوى في الصفحة رقم 5 
                    
                        INSTALLATION REQUIREMENTS MA Code - CO Detector (for the State of Massachusetts only) 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.3 by adding the following additional requirements:  (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for  residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than  seven (7) feet above
                    
                    ملخص المحتوى في الصفحة رقم 6 
                    
                        UNIT DIMENSIONS 6 6 Regency® L676S-1 Direct Vent Gas Fireplace INSTALLATION                                                                                                                                                                                                                                                                                                                                                                                                                                         
                    
                    ملخص المحتوى في الصفحة رقم 7 
                    
                        INSTALLATION INSTALLATION 12) Installation and any repairs to this appliance  YOUNG CHILDREN SHOULD BE  IMPORTANT MESSAGE   should be done by an authorized service  CAREFULLY  SUPERVISED WHEN  person. A professional service person should  SAVE THESE  THEY ARE IN THE SAME ROOM AS  be called to inspect this appliance annually.  THE APPLIANCE. Make it a practice to have all of your gas  INSTRUCTIONS appliances checked annually. The L676S Direct Vent Fireplace must be  CLOTHING OR OTHER FLAMMABLE  1
                    
                    ملخص المحتوى في الصفحة رقم 8 
                    
                        INSTALLATION 9) Test Gas Pressure (Refer to "Gas Pipe Pres- 3) The L676S Direct Vent Gas Fireplace can  HEAT RELEASE KIT  sure Testing" section). be installed in a recessed position or framed  out into the room as in A, B, C and D. See  The Heat  Release Kit expels warm air from the  Diagram 1. 10) Install standard and optional features.  Refer  fi replace to the outside of the building, allowing  to the following sections:  the fi replace to be operated with less heat entering  the room. The kit 
                    
                    ملخص المحتوى في الصفحة رقم 9 
                    
                        INSTALLATION INSTALLATION CLEARANCES The clearances listed below are Minimum distances unless otherwise stated: A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest  importance that this fi replace and vent system be installed only in accordance with these instructions. Caution Requirements The top, back and sides of the fi replace are defi ned by  standoffs. The metal ends of the standoff may NOT be  recessed 
                    
                    ملخص المحتوى في الصفحة رقم 10 
                    
                        INSTALLATION MANTEL CLEARANCES Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing  are shown in the diagram below. Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible  board. Note: Ensure the paint that is used  on the mantel and the facing is  "heat resistant" or the paint may  discolour. MANTEL LEG CLEARANCES Combustible ma
                    
                    ملخص المحتوى في الصفحة رقم 11 
                    
                        INSTALLATION INSTALLATION FRAMING  1) Frame in the enclosure for the unit with framing material. The framed  Note: When constructing the framed opening, please ensure    opening for the assembled kit is 45-7/8" high x 43" wide x 24-1/2"  there is access to install the gas lines when the unit is  deep (1143mm x H 1092mm W x 622mm D). See Diagram 1. Also  installed. See Diagram 3 for details.  see Diagram 2 for corner installations.    IMPORTANT: Header must be metal stud.  All other framing may  
                    
                    ملخص المحتوى في الصفحة رقم 12 
                    
                        INSTALLATION  FINISHING 1) Finishing material such as tile, river rock, etc. must not  protrude  beyond the front facing fl anges on all 4 sides of the fi rebox opening. NON-COMBUSTIBLE REQUIREMENTS Metal 44-1/2" 2)   If material such as brick, stone, etc. extends past the faceplate depth,  Stud (1130mm) when fi nishing around the faceplate, the minimum opening dimension  noted below (Diagram 3) must be adhered to - to ensure the faceplate  can be removed. Non-combustible 36 -1/4” Material 31-5/8" 
                    
                    ملخص المحتوى في الصفحة رقم 13 
                    
                        INSTALLATION INSTALLATION To accommodate various thicknesses of facing material - the  faceplate is adjustable to a maximum of 1-1/4" and a minimum  of 1/2" . See chart below and page 35 for detailed instructions. Finished Facing Thickness Faceplate Adjustment 1/2" Factory Setting 1/2" - 7/8" (or less) Adjusted to  + 3/8" 7/8" - 1-1/4" (or less) Adjusted to  + 3/4" Diagram 5 Regency® L676S Direct Vent Gas Fireplace 13                                                                               
                    
                    ملخص المحتوى في الصفحة رقم 14 
                    
                        INSTALLATION SIDE NAILING STRIPS The Finishing Template uses two magnets to  UNIT ASSEMBLY  attach itself to the fl ange on the left or right  side of the unit (see diagram below). Install the  The side nailing strips come attached to the unit.  PRIOR TO  facing material up to the outside edge (when  There are 2 plates on each side, one on the top  INSTALLATION facing the unit) of the fi nishing template.  This  and bottom that can be folded out as required. template may be discarded after the fac
                    
                    ملخص المحتوى في الصفحة رقم 15 
                    
                        INSTALLATION INSTALLATION VENT RESTRICTOR POSITION Latch Vent restriction is required for certain venting  installations, see the diagrams in the "Venting Arrangements" section to determine if they are  required for your installation. The Vent Restrictor plate is located on the inside  top of the fi rebox. 2- ½” Vent Restrictor Plate Vent Restrictor Set 1  b.  Swing the door out from the top and release    the hinge on the left side of the  door and  lift out. Factory Set Vent Restrictor Set (no 
                    
                    ملخص المحتوى في الصفحة رقم 16 
                    
                        INSTALLATION EXTERIOR VENT TERMINATION REQUIREMENTS 1 2 Canada USA Minimum Clearance Requirements A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm) B Clearance to window or door that may be opened 12"(30cm) 9" (23cm) C Clearance to permanently closed window ** D Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm) 24"(60cm)) 24"(60cm)) E Clearance to unventilated soffi t 24"(60cm) 24"(60cm) F Clearance to outs
                    
                    ملخص المحتوى في الصفحة رقم 17 
                    
                        INSTALLATION INSTALLATION VENTING ARRANGEMENTS  HORIZONTAL TERMINATION (FLEX) ® Regency Direct  Vent System  These venting systems, in combination with the L676S, have been tested and listed as a direct vent system by Warnock Hersey. The location of the  termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section. FPI Direct Vent (Flex) System Termination Kits include all the  parts needed to install the L676S usi
                    
                    ملخص المحتوى في الصفحة رقم 18 
                    
                        INSTALLATION RIGID PIPE VENTING SYSTEMS BASIC HORIZONTAL & VERTICAL TERMINATIONS Vertical Terminal Rigid Pipe Vent Systems offer a complete line  of component parts for installation of both  horizontal and vertical installations. Many  Storm Collar items are offered in decorative black, as well  as galvanized fi nish.  Flashing The minimum components required for a basic  horizontal termination are: Ceiling Firestop  1 AstroCap XL Vinyl Siding o  1 90 Elbow  Standoff (Optional) Vent Guard - if re
                    
                    ملخص المحتوى في الصفحة رقم 19 
                    
                        INSTALLATION INSTALLATION 5” X 8” RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed.  Not All Rigid Pipe components are available directly from FPI. Regency® L676S Direct Vent Gas Fireplace 19                                                                                                                                                                                                                                                                            
                    
                    ملخص المحتوى في الصفحة رقم 20 
                    
                        INSTALLATION 20 Regency® L676S Direct Vent Gas Fireplace INSTALLATION