INSTALLATION AND SERVICE MANUAL 
 
MODELS: 
PGT5-100, PGT11-125, PGT16-160, 
PGL20-180, PGL33-250, PGL37-312, & PGL39-400 
 
 
 WARNING: IF YOU DO NOT FOLLOW THE SAFETY PRECAUTIONS BELOW AND IN THIS 
MANUAL, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, 
OR LOSS OF LIFE. 
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE 
VICINITY OF THIS OR ANY OTHER APPLIANCE. 
 
WHAT TO DO IF YOU SMELL GAS: 
 
• DO NOT TRY TO LIGHT ANY APPLIANCE. 
                    
                    ملخص المحتوى في الصفحة رقم 2 
                    
                          TABLE OF CONTENTS  SECTION                                               BEGINNING PAGE    WARNING AND INSTRUCTION LABELS                                 1    WARNINGS AND CAUTIONS                                            2       I. GENERAL INSTRUCTIONS                                       3      II. GENERAL INSTALLATION       3        A. CODES AND CLEARANCES                                   3        B.  CONSTRUCTION MATERIALS                                 3              a. COMBUSTIBLE M
                    
                    ملخص المحتوى في الصفحة رقم 3 
                    
                        All installations and services must be performed by qualified service personnel.    This page contains reproductions of the various warning and instruction labels placed on the Thermo Pride Power Gas  Furnaces. Please read and comply with the contents of these labels.                                                          1                                                                                                                                                                             
                    
                    ملخص المحتوى في الصفحة رقم 4 
                    
                        All installations and services must be performed by qualified service personnel.  This page contains various warnings and cautions reproduced from the Power Gas Furnace Manual. Please read  and comply with the statements below. CAUTION: When installing the burner, it should be noted that the loose fill insulation and fiber chambers are made with  ceramic fibers. Currently, there are no known chronic health effects in humans associated with long term exposure to  ceramic fibers. The International
                    
                    ملخص المحتوى في الصفحة رقم 5 
                    
                        All installations and services must be performed by qualified service personnel.  I. GENERAL INSTRUCTIONS    These instructions must be read in their entirety before installing the furnace. It is the installer's responsibility to do the  following:    1. Inform and demonstrate to the user, the correct operation and maintenance of the appliance.   2. Inform the user of the hazards of flammable liquids and vapors and to remove such liquids and vapors from the vicinity of  the appliance.    II. GEN
                    
                    ملخص المحتوى في الصفحة رقم 6 
                    
                        All installations and services must be performed by qualified service personnel.   - MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS -  MODEL NO. FROM SIDES FRONT TOP & SIDES FROM THE REAR BOTTOM OF FURNACE OF PLENUM FLUE OR VENT  PGT5-100  1 IN. 24 IN. 1 IN. 4 IN. 1 IN. 1 IN. PGT11-125  1 IN. 1 IN. 9 IN.  24 IN. 1 IN. 1 IN. PGT16-160  24 IN. 9 IN.  1 IN. 1 IN. 1 IN. 1  IN. 24 IN. PGL20-180 1 IN. 1 IN. 18 IN. 1 IN. N/A  PGL33-250  1 IN. 24 IN. 1 IN. 18 IN.  1 IN. N/A  PGL37-312  1 IN. 24 IN. 1 IN. 1
                    
                    ملخص المحتوى في الصفحة رقم 7 
                    
                        All installations and services must be performed by qualified service personnel.  EXAMPLE: 100,000 BTUH input furnaces requires "two" openings of 100 square inches each. A minimum opening of  100 square inches is required regardless of the input.  If the building is tightly constructed and or has an exhaust fan(s) that creates a negative pressure, air for combustion and  ventilation must be supplied from the outdoors or from spaces freely communicating with the outdoors. When  communicating dire
                    
                    ملخص المحتوى في الصفحة رقم 8 
                    
                        All installations and services must be performed by qualified service personnel.    Trim or remove nearby trees that could interfere with chimney draft.    5. In cases where the chimney flue extends to the basement floor, the draft can usually be improved by filling the base of the  chimney with sand to within 12" of the flue pipe after relocating the cleanout cover.     6. All joints of the vent must be tightly sealed. The inside of the vent should be free of all obstructions.    7. All vents a
                    
                    ملخص المحتوى في الصفحة رقم 9 
                    
                        All installations and services must be performed by qualified service personnel.    NOTE: If this furnace replaces an appliance with a vent that was originally installed in a common vent system serving other  appliances, the vent system is likely now too large to properly vent the remaining appliances only and must be modified  accordingly. Refer to Natural Fuel Gas Code Appendix G Category I vent tables for common venting a PG Series furnace  and another fan assisted or natural draft unit.    I
                    
                    ملخص المحتوى في الصفحة رقم 10 
                    
                        All installations and services must be performed by qualified service personnel.  temperature stability. If the chimney is on the homes exterior and condensing occurs, the chimney may be insulated  around its exterior to help the flue hold its temperature. Also, check to see if the chimney is too large for the flue  gases to heat, if so reduce to proper size by lining. Be sure to use stainless steel liners such as types 430, 304 or for  the toughest corrosion resistant type 316. If the chimney i
                    
                    ملخص المحتوى في الصفحة رقم 11 
                    
                        All installations and services must be performed by qualified service personnel.  Piping from the natural gas meter to the furnace shall be in accord with requirements of the local   utility. Piping from the LP tank to the furnace must follow the recommendations of the gas supplier.    1. A readily accessible, certified manual shut off valve with a non-displaceable rotor member should be installed  within six feet of the gas equipment it serves. A union or flanged connection shall be provided do
                    
                    ملخص المحتوى في الصفحة رقم 12 
                    
                        All installations and services must be performed by qualified service personnel.  EXAMPLE: A line must supply a furnace of 110,000 BTU/hr input, a hot water heater of 40,000 BTU/hr input and  gas range with a 30,000 BTU/hr input capacity. The total BTU/hr input loading on the line is 180,000 BTU/hr. The  200,000 BTU/hr column on the chart must be used in sizing the pipe.    - BLACK PIPE SIZE FOR NATURAL GAS -  ┌─────────────┬──────────────────────────────────────────────── ┐ │BURNER FIRING │ FEE
                    
                    ملخص المحتوى في الصفحة رقم 13 
                    
                        All installations and services must be performed by qualified service personnel.  - COPPER TUBING SIZE FOR LIQUIFIED PETROLEUM GASES -            All black pipe sizes shown are I.D.     Seamless copper tubing may only be used with gases that are not corrosive to it. See note below and check with your  LP gas supplier before using. Seamless copper tubing must comply with standard type K or L for seamless copper  water tube, ASTM B 88; or seamless copper tube for air conditioning field service, AS
                    
                    ملخص المحتوى في الصفحة رقم 14 
                    
                        All installations and services must be performed by qualified service personnel.  TWO PIECE MOUNTING PLATE      When mounting the burner, the upper mounting plate must be removed to provide access to the area in front of the  combustion chamber. The combustion chamber can then be moved forward or backward slightly to allow for  adjustment in positioning the burner tube. Do not allow the burner tube or end cone to physically touch the chamber,  as excessive heat transfer could result in distortio
                    
                    ملخص المحتوى في الصفحة رقم 15 
                    
                        All installations and services must be performed by qualified service personnel.  to have the possibility of being carcinogenic to humans. IARC has also classified these fibrous materials as group 2A  0 carcinogens when they have undergone long term exposure to temperatures greater than 1800 F. A group 2A agent  is considered to have the probability of being carcinogenic to humans. For these reasons, we suggest the use of a 3M  9900, 3M 8710, or equivalent mask when working with any ceramic fibe
                    
                    ملخص المحتوى في الصفحة رقم 16 
                    
                        All installations and services must be performed by qualified service personnel.  Furnace Model                   Orifice Size                       Manifold Gas Pressure                    No. Turns Closed*    ** PGL16-160 Nat                #J (.277)                                     2.4” W.C.                                        24    PGL16-160 LP                      #8(.199)                                      2.9”                                                 24    PGL20-180Nat     
                    
                    ملخص المحتوى في الصفحة رقم 17 
                    
                        All installations and services must be performed by qualified service personnel.  In summary, setting the combustion air on the Thermo Pride Midco RE32 power gas conversion burner is  extremely critical.  This adjustment should only be made by following these instructions and confirming the  set-up with the proper CO or O combustion analyzer and a carbon monoxide reading of less than 50 PPM.  2 2      L. REQUIREMENTS AND SIZING OF DUCT WORK    The duct system must be sized and installed by a qua
                    
                    ملخص المحتوى في الصفحة رقم 18 
                    
                        All installations and services must be performed by qualified service personnel.  EXAMPLE: Heating output of furnace is 100,000 x 1.4  100 = 1400 CFM. Air conditioning installed is 4 tons x  400 CFM = 1600 CFM or 48,000 BTU's. NOTE: The duct system must be sized for the larger CFM requirement for  cooling. If only 3 tons 36,000 BTU's of cooling x 400 CFM = 1200 CFM was installed, the duct would have to be  sized for the 1400 CFM heating requirement.    To insure obtaining the necessary air hand
                    
                    ملخص المحتوى في الصفحة رقم 19 
                    
                        All installations and services must be performed by qualified service personnel.    DUCT WORK/AIR CONDITIONING:  If the furnace is used in connection with summer air conditioning (cooling), the furnace should be installed parallel  with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger. If the  cooling unit is installed with a parallel flow arrangement, dampers or other means used to control flow of air should  be provided to prevent chilled air f
                    
                    ملخص المحتوى في الصفحة رقم 20 
                    
                        All installations and services must be performed by qualified service personnel.  A. 400 CFM X 3 TON (36,000 BTU'S) = 1,200 CFM FOR COOLING                B. 400 CFM X 2.5 TON (30,000 BTU'S) = 1,000 CFM FOR COOLING    NOTE: To obtain the proper 50°F to 80°F temperature rise for heating an air conditioning coil is installed, the speed  of the blower motor may have to be changed. This depends on the static resistance of an individual duct system and  the size of the air conditioner.    M. FILTERS