                        LF414 /LF610 
Field Intelligent Device – Mount-Anywhere Series - Wafer 
LF414 /LF612 
 
 
Electromagnetic Flowmeter 
1/2" to 8" (15 to 200 mm) 
 
 
 
Introduction 
The electromagnetic flowmeter uses Faraday’s Law of 
electromagnetic induction to measure the process flow. 
The device consists of two units: a detector, through 
which the fluid to be measured flows and in which 
low-level signals proportional to flow rates are 
obtained; and a converter, which supplies excitation 
current to the de
                    
                    Resumen del contenido incluido en la página 2 
                    
                        TIC-LF414C  Linings —   Power consumption:   1/2” to 4” (15 to 100mm):   17W(27VA) or less  Ceramic tube (std.) & Teflon PFA (opt.)  19W(29VA) or less (with PROFIBUS)  6” to 8” (150 and 200mm): Teflon PFA  Conformance to European Community Directives:  Electrodes —   EMC directive 89/336/EEC  Type-Super smooth, polished with self cleaning  The low voltage 93/68/EEC  finish, and non stick shape  PED 97/23/EC (Note 1)  316 stainless steel (std.)  Note : See Table 1 for detail.  Hastelloy C equival
                    
                    Resumen del contenido incluido en la página 3 
                    
                        TIC-LF414C  Note 1: Two outputs (DO1 and DO2) are needed for  Digital input DI (opt.)  4-range switching and forward/reverse 2-range  Signal type:  20 to 30Vdc voltage signal  switching.  Input resistance: 2.7k Ω  Note 2:  Normal Open (default set) or Normal Close is  Number of inputs: one point  selected for alarm outputs when programming.  DI function — One of the following functions can be  When power failure occurs, unit will be fault to  assigned to the optional DI signal.  Normal Open.  Ra
                    
                    Resumen del contenido incluido en la página 4 
                    
                        TIC-LF414C  Conditions when power fails:  Dimensions and Weights:   Parameter setting values are stored in non–volatile  See Figure 9 (for Separate type)  memory and the values will be restored when the  MTBF:  power returns to normal condition. The outputs and  Converter: 220,000 hours (25 years) at 77 °F (25 °C)  display will remain as follows when power fails.   based on strict military specification  • Current output:  0mAdc  MIL-HDBK-217F  • Digital output:  OFF  Detector: 350,000 hours (40
                    
                    Resumen del contenido incluido en la página 5 
                    
                        TIC-LF414C      Installation     Dimensions     Unit : inch( mm)                                                                  Unit : inch( mm)      1.42(36)  1.42(36)  8.86(225) 5.63(143) 8.86(225) 5.63(143)    5.16(131) 5.16(131) 2.52(64)  L1 3.43(87) L1             ANSI class 150 and class 300 dimensions:  ANSI class 150 and class 300 dimensions:  Meter size L1 L2 D1 Weight  Meter size L1 L2 D1 Weight  (inch) (inch) (inch) (inch) (lb)  (inch) (inch) (inch) (inch) (lb)  1/2 2.76 9.92 1.93 a
                    
                    Resumen del contenido incluido en la página 6 
                    
                        TIC-LF414C     ANSI class 150 and class 300 dimensions    Meter size L1 L2 D1 Weight   (inch) (inch) (inch) (inch) (lbs)  Unit : inch(mm) 1-1/2 3.94 10.39 3.35 approx. 13  2 4.33 11.02 4.02 approx. 15  8.86(225) 1.42(36) 5.63(143)   3 4.33* 12.04 5.00 approx. 18  5.16(131)  4 4.72* 13.30 6.26 approx. 22  6 9.06 16.02 8.50 approx. 49  8 11.81 18.03 10.51 approx. 70    BS16, DIN PN16 and JIS 10K dimensions  Meter size L1 L2 D1 Weight  (mm) (mm) (mm) (mm) (kg)  40 100 264 85 approx. 6  50 110 280 1
                    
                    Resumen del contenido incluido en la página 7 
                    
                        TIC-LF414C                  ANSI class 150 and class 300 dimensions:  Unit : inch(mm)  Meter size L1 L2 D1 Weight  R (PT)1/2Male Screw (Two Places)  (inch) (inch) (inch) (inch) (lb)  3.46(88) 4.96(126)  1/2 2.76 7.05 1.93 approx. 7  1.38(35)  1.57(40)  3.58(91)   BS16, DIN PN16 and JIS 10K dimensions:  Meter size L1 L2 D1 Weight  (mm) (mm) (mm) (mm) (kg)  15 70 179 49 approx. 3    The dimension of L1 is changed when the material of   grounding ring is chosen Pt-Ir or Ta  Meter size L1  1/2”(15mm
                    
                    Resumen del contenido incluido en la página 8 
                    
                        TIC-LF414C                    ANSI class 150 and class 300 dimensions:  Unit : inch(mm)  Meter size L1 L2 D1 Weight  R(PT)½ Male Screw (Two places)    (inch) (inch) (inch) (inch) (lb)  3.46(88) 4.96(126)  1 3.15 6.61 2.60 approx. 7  1.57(40) 1.38(35) 3.58(91)    BS16, DIN PN16 and JIS 10K dimensions:  Meter size L1 L2 D1 Weight  (mm) (mm) (mm) (mm) (kg)  25 80 168 66 approx. 3    The dimension of L1 is changed when the material of   grounding ring is chosen Pt-Ir or Ta  Meter size L1  3.43(87)  
                    
                    Resumen del contenido incluido en la página 9 
                    
                        TIC-LF414C       ANSI class 150 and class 300 dimensions:    Meter size L1 L2 D1 Weight   (inch) (inch) (inch) (inch) (lbs)  Unit : inch(mm) 1-1/2 3.94 7.48 3.35 approx. 9  2 4.33 8.15 4.02 approx. 11  R(PT)½Male Screw (Two places)  3 4.33* 9.13 5.00 approx. 13  4.96(126)  3.46(88)  4 4.72* 10.39 6.26 approx. 20  1. 38(35)  3.58(91)  1.57(40)  6 9.06 12.76 8.50 approx. 47  8 11.81 15.16 10.51 approx. 78    BS16, DIN PN16 and JIS 10K dimensions:  Meter size L1 L2 D1 Weight  (mm) (mm) (mm) (mm) (k
                    
                    Resumen del contenido incluido en la página 10 
                    
                        TIC-LF414C  4 – 4 - φ φ0. 1143( φ 11) Unit : inch(mm)    3.23(82) 5.94(151) 0.98(25) 0.51(13) 1 51 25 82 13 A 取付金具 ttachment  Weight: Approx. 7 lb (3.5 kg)  2.91(74) LCD display  74 ±0. 3 LCD 表示器 Excitation cable ground  励磁 ケ ー ブ ル グ ラ ン ド I/ 電流出力ケ O cable gr ー ou ブ nd ル グ ラ ン ド Ground terminal 接地端子 (M4)  (M4) 取付金具   Power supply cable ground Signal cable ground 信号ケ ー ブ ル 電源ケ ー ブ ル グ ラ ン ド グラ ン ド Blind screw  封止栓 IR Switch  赤外線 ス イ ッ チ 矢視A   Note: Cable glands are not provided for LF612F cFMus a
                    
                    Resumen del contenido incluido en la página 11 
                    
                        TIC-LF414C  ・Separate type LF410/LF612 and LF414/LF612F flowmeters    Terminal board  IV wire  2 5.5 mm or more  Thick walled steel conduit  Grounded with 100 Ω or less  ground resistance  Power switch (External double-pole power switch )  [Instrument panel : ordered separately]  Grounded with 100 Ω or less  Signal cable  ground resistance  (2-wire shielded hard-rubber    Power supply  sheathed cable)  Current output (4~20mAdc)  or PROFIBUS  Digital output 1  Signal common for DI and DO Connecte
                    
                    Resumen del contenido incluido en la página 12 
                    
                        TIC-LF414C  (7) Only one PROFIBUS-PA cable goes through a   Wiring Precautions  cable gland of the Electromagnetic Flowmeter.  (1) Explosion proof type flowmeters are not provided  Please use the junction box at system  cable glands.   configuration.  Refer to the part Cable connection port at detector    and converter.  300 (2) Connect the grounding wire (IV wire 5.5mm² or  200 100 more) to a good earth ground (100 Ω or less ground  resistance). Make the wire as short as possible. Do  50 30 not
                    
                    Resumen del contenido incluido en la página 13 
                    
                        TIC-LF414C   Meter Size  About establishment environment  To select the meter size: Do not store or install the flowmeter :  See Table 3 to 4 and find meter sizes within the  • Where there is direct sunlight.  velocity of 0.3 to 32.8 ft/s (0.1 to 10m/s) for a  • Where excessive vibration or mechanical shock  specified full-scale (measuring range high limit)  occurs.  flow. Select one that has its full-scale velocity  • Where high temperature or high humidity  between 3.0 and 10 ft/s (1 and 3m/s)
                    
                    Resumen del contenido incluido en la página 14 
                    
                        TIC-LF414C  Table 6.  Specification Code (Wafer type detector LF410 Series)  Detector category  Model Specification Code  Description  Normal type  Ex. type  1 2 3 4 5 6 7 8 9 10 11 12 13 14 Gr.-A Gr.-B Gr.-C Gr.-D  L F 4 1 0          Normal specification type    √ √  L F 4 1 4          Hazardous location certification type (Note 1)    √ √                Meter size           D         ½"(15mm) √  √        E         1"(25mm) √  √        F         1½"(40mm) √  √        G         2"(50mm) √  √     
                    
                    Resumen del contenido incluido en la página 15 
                    
                        TIC-LF414C      Table 7.  Specification Code for converters  Model Specification Code  Contents LF610 LF612  1 2 3 4 5 6 7 8 9 10 11 12 13 14  type type  L F 6 1           Electromagnetic flowmeter converter      0          Combined (Integral) type  –      2          Separate (Remote) type –                 Purpose         A         Standard    F cFMus class I, Division 2 approved                  Shape    A Integral type with case  –  –  B Separate type with case                 Converter mount
                    
                    Resumen del contenido incluido en la página 16 
                    
                        TIC-LF414C                      Specifications are subject to change without notice. ISO9001 and ISO14001 are certified.  Printed in Japan 2008-6 (TDOC) © TOSHIBA Corporation 2008 Misuse of this product can result in damages to property or human injury.   All Rights Reserved. Read related manuals carefully before using this product.  http://www.toshiba.com/ind/ TIC-LF414C