                         MODELS HW 300, 399, 420, 520, 610, 670 
GAS-FIRED COMMERCIAL COPPER BOILERS FOR 
HYDRONIC HEATING AND HOT WATER SUPPLY
UP-FLOW MODELS
•  INSTALLATION  •  OPERATION  •  MAINTENANCE  •  LIMITED WARRANTY
•  INDOOR ONLY
WARNING: If the information in this manual 
is not followed exactly, a fire or explosion 
may result causing property damage, 
personal injury or death.
— Do not store or use gasoline or other 
flammable vapors and liquids in the 
vicinity of this or any other appliance.
— WHAT TO D
                    
                    Resumen del contenido incluido en la página 2 
                    
                        SAFE INSTALLATION, USE AND SERVICE The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others  of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the  meaning of each safety message is understood by you and others who i
                    
                    Resumen del contenido incluido en la página 3 
                    
                        GENERAL SAFETY 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    
                    
                    Resumen del contenido incluido en la página 4 
                    
                        TABLE OF CONTENTS  SAFE INSTALLATION, USE AND SERVICE.......................................................................................................................................................................... 2 GENERAL SAFETY................................................................................................................................................................................................................ 3 TABLE OF CONTENTS ...............................
                    
                    Resumen del contenido incluido en la página 5 
                    
                        DIMENSIONS AND CAPACITY DATA EXTRA OPENING FOR THERMOMETER AND RELIEF VALVE HW-520, 610 AND HW--670 TABLE 1 MODELS DIMENSIONS IN INCHES PROPANE NATURAL HW-300 HW-399 HW-420 HW-520 HW-610/670 HW-610/670 A Overall height 65 (1651) 57-1/8 (1451) 57-1/8 (1451) 68-5/16 (1735) 67 (1702) 64-3/4 (1645) B Height to Top of Jacket 43-1/4 (1099) 45-1/8 (1146) 45-1/8 (1146) 56-1/4 (1429) 56-1/4 (1429) 56-1/4 (1429) C Floor to Center Line Water Inlet 36 (914) 38-3/4 (984) 38-3/4 (984) 46 (1168) 46 (1168) 46 (
                    
                    Resumen del contenido incluido en la página 6 
                    
                        TABLE 2, RECOVERY CAPACITIES Input °F 20 40 50 60 70 80 Model BTUH (kW) °C 11.1 22.2 27.7 33.3 38.8 44.4 GPH 1439 719 576 480 411 360 HW 300 300,000 (88) LPH 5448 2724 2179 1816 1556 1362 GPH 1914 957 765 638 547 478 HW 399 399,000 (117) LPH 7245 3623 2898 2415 2070 1811 GPH 2014 1007 806 671 576 504 HW 420 420,000 (123) LPH 7627 3813 3051 2542 2179 1907 GPH 2494 1247 998 831 713 624 HW 520 520,000 (152) LPH 9443 4721 3777 3148 2698 2361 GPH 2926 1463 1170 975 836 731 HW 610 610,000 (179) LPH 11
                    
                    Resumen del contenido incluido en la página 7 
                    
                        INTRODUCTION This design complies with the current edition of the ANSI Z21.13  IF THE BOILER HAS BEEN EXPOSED TO FLOODING, IT  low-pressure boiler standard. MUST BE REPLACED. Compliance under this standard implies that when the boiler LIQUEFIED PETROLEUM GAS MODELS underwent test, the gas manifold and control assembly prov ided  on the boiler met safe lighting and other performance criteria. Boilers for propane or liquefied petroleum gas (LPG) are different  from natural gas models. A natural ga
                    
                    Resumen del contenido incluido en la página 8 
                    
                        HIGH ALTITUDE INSTALLATIONS Ratings specified by manufacturers for most boilers apply for  elevations up to 2000 feet (600 m).  For elevations above 2000 feet  IN CANADA (600 m) ratings must be reduced by a rate of 4% for each 1000 feet  (300 m) above sea level. Acceptance of these models for use at altitudes above 2000 feet  (600 m) is based on field test of the individual installation by the  Example: If a boiler is rated at 610,000 Btu/hr. at sea level, to operate  provincial/state authority 
                    
                    Resumen del contenido incluido en la página 9 
                    
                        THERMAL BALANCER Figure 4 shows the internal wiring of the thermal balancer. The  device may be tested after disconnecting the four leads from their  respective terminals on the unit. 1. Apply a test light to the yellow and red leads.  • The lamp should light as the contact in this circuit is normally  closed when the resistor is cool. HIGH LIMIT SWITCH 2. Apply a light to the black and yellow leads.   FIGURE 5. • The lamp should not light as the contact in this circuit is normally  open when th
                    
                    Resumen del contenido incluido en la página 10 
                    
                        To adjust the flow rate setting:   CAUTION The switch is factory set at approximately the minimum flow rate, see  1. Remove the flow switch cover. Table 3 on page 9. It must not be set lower than the factory setting as  this may result in the switch failing to return at 'no flow' condition. 2. For higher flow rate - turn the range adjusting screw clockwise. 4. Replace flow switch cover. Where units are installed in multiples,  3. For lower flow rate - turn the range adjusting screw  each boiler 
                    
                    Resumen del contenido incluido en la página 11 
                    
                        Code, Section IV or CSA B51, as applicable.  Select a relief valve with TANK TEMPERATURE CONTROL a discharge NOT less than the boiler input, and a pressure rating NOT  exceeding the working pressure of any component in the system. The water temperature in the storage tank is controlled by the Tank  Temperature Control. The sensing element is mounted inside the  A. O. Smith supplies a 125 psi relief valve for hot water supply systems hot water storage tank. and 50 psi relief valve for space heati
                    
                    Resumen del contenido incluido en la página 12 
                    
                        THERMOMETERS Time to Produce 2nd & 3rd  Water Temperature Degree Burns on Adult Skin Thermometers should be obtained and field installed as shown  in the installation diagrams. OVER: 170°F (77°C) Nearly Instantaneous 160°F (71°C) About 1/2 second Thermometers are installed in the system as a means   150°F (65°C) About 1-1/2 seconds of detecting a possible liming condition in the boiler.   140°F (60°C) Less than 5 seconds An increase of 5°F (3°C) over the normal temperature   130°F (54°C) About 3
                    
                    Resumen del contenido incluido en la página 13 
                    
                        PERMIT OPERATION OF GAS APPLIANCES IF INSTALLED  If the confined space is within a building of tight construction,  18 INCHES OR MORE ABOVE THE FLOOR. THIS MAY  air for combustion, ventilation, and draft hood dilution must be  REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT  obtained from outdoors. When directly communicating with the  BE AVOIDED. outdoors or communicating with the outdoors through vertical  ducts, two permanent openings, located in the above manner,  shall be provided. Each 
                    
                    Resumen del contenido incluido en la página 14 
                    
                        INSTALLATION CLEARANCES Sufficient area should be provided at the front and rear of the unit  for proper servicing.  Clearances of  24 inches (609.4mm) in the  rear and 48 inches (1,219mm)  in the front are required by code.   These boilers are approved for installation on combustible flooring  In a utility room installation, the door shall be wide enough to allow  in an alcove with minimum clearance to combustibles of: the boiler to enter or to permit the replacement of another appliance  such 
                    
                    Resumen del contenido incluido en la página 15 
                    
                        Building materials must not come in contact with combustion Vent connectors serving appliances vented by natural draft shall not  products from stack or chimney, due to the degradating properties be connected into any portion of mechanical draft systems operating  of flue products. under positive pressure. Flue products must have a minimum clearance of 4 feet (1.22m) 3. CONNECTING BOILER TO A COMMON VENT horizontally from, and in no case above or below, unless a 4-foot  (1.22m) horizontal distan
                    
                    Resumen del contenido incluido en la página 16 
                    
                        4. MULTIPLE VENT TABLE 1. Turn off the electrical power (main manual gas shutoff and pilot  valves, if applicable). Table 5 on page 17 has been compiled to show the material  sizes in a Type B doublewall combined vent system. Refer to    Allow boiler parts and vent to cool before disassembly. CAN/CSA B149 .1 (current edition), or the ASHRAE 1983 Equipment  Volume for further information. 2. Remove the boiler draft diverter and vent pipe running to the chimney.  • Check parts and chimney for obst
                    
                    Resumen del contenido incluido en la página 17 
                    
                        TABLE 5, COMBINED VENT SIZING TABLES MODEL HW-610 BOILER MODEL HW-300 BOILER Input: 610,000 Btuh Draft Hood Outlet 12" Input: 300,000 Btuh Draft Hood Outlet 8" Required Connector or Smoke Pipe Diameter Required Connector or Smoke Pipe Diameter Total Vent Height (Measured in Feet Above Draft Hood) Total Vent Height (Measured in Feet Above Draft Hood) Connector  Connector  10 15 20 30 40 50 60 80 100 10 15 20 30 40 50 60 80 100 Rise in Feet Rise in Feet Connector Diameter (in Inches) Connector Dia
                    
                    Resumen del contenido incluido en la página 18 
                    
                        SYSTEM INSTALLATIONS 1. CONVENTIONAL INSTALLATIONS All modern hydronic type boilers are exceptionally fast heating units.   The low water volumes in relation to firing rates require special  attention to water flow rates for smooth, efficient operation. These  considerations for the A. O. Smith copper heat exchanger boilers  are covered below. 0 0 Conventional 20 F (10 C) drop in systems for a fully loaded boiler  will maintain the following approximate flow rates: MODELS GPM (LPM) HW-300 23 (87
                    
                    Resumen del contenido incluido en la página 19 
                    
                        NO. SUGGESTED ITEMS FOR INSTALLATION Short pipe nipple and pair of boiler loop tees in piping  1 between system supply and return. One set per each group  of boilers. 2 Boiler pipe loop. See piping sizing data. 3 Boiler circulator. See pump sizing data. 4 Thermometer. 5 Theraltimeter. 6 Plug cock to control flow rate. Safety flow switches. For interlock with other systems or  7 instead of low water cutoff. 8 Relief valve. With one -300, -399 or -420 item 9 is - sensing element of  remote control
                    
                    Resumen del contenido incluido en la página 20 
                    
                        5. VENT VALVES If the boiler is connected to chilled water piping or its heating coils  are exposed to refrigerated air, the boiler piping system must be  It is recommended that automatic, loose key or screwdriver type  equipped with flow valves or other automatic means to prevent gravity  vent valves be installed at each convector or radiator. circulation through the boiler during the cooling cycle. 6. MANIFOLD HEADERS 8. CIRCULATING PUMP Split systems with individual supply and return lines fr