Resumen del contenido incluido en la página 1 
                    
                        42" and 50" Wood Burning Masonry Fireplace
oWner’s opera Tion and insT alla Tion Manual
(V)G42/50 - Smooth Face with Insulation
(V)G42R/50R - Smooth Face with Insulation and Bottom Door Rail
(V)G42H/50H - Smooth Face with Insulation and Herringbone Refractory
(V)G42HR/50HR - Smooth Face with Insulation, Bottom Door Rail  
and Herringbone Refractory
SAVE THIS BOOK
This book is valuable. In addition to instructing you 
on how to install and maintain your appliance, it also 
contains information th
                    
                    Resumen del contenido incluido en la página 2 
                    
                        TaBle oF conTenTs Safety Information ...............................................  Glass Door Installation ...................................... 1 Specifications ...................................................... 3 Operation and Maintenance Guidelines ............ 13 Fireplace Installation............................................ 5 Technical Service............................................... 14 Venting Installation .............................................. 7 Replacement Par
                    
                    Resumen del contenido incluido en la página 3 
                    
                        speciFica Tions 42" MODELS ROUND TOP TERMINATION SQUARE CHASE-TOP  TERMINATION  2" CHIMNEY AIRSPACE  CLEARANCE TO  COMBUSTIBLE MATERIAL  NO COMBUSTIBLE MATERIAL ON FACE COMBUSTIBLE  WALL BOARD  1 1 /2" AIR SPACE  BACK AND SIDES  OUTSIDE AIR MINIMUM 18" TO  PERPENDICULAR  SIDEWALL  GAS LINE KNOCKOUTS HEARTH EXTENSION 66" X 20" 0" TO 12" EACH SIDE  BOTTOM 12" 30.5" 11" 67" 21.25" 58" 28.5" 49" 30" 0.625" 51" 42" 8" 51" 1" AIR KIT  KNOCK OUT   LEFT SIDE  24.25" GAS LINE  KNOCK OUTS  3.5" 10.5" 9.5"
                    
                    Resumen del contenido incluido en la página 4 
                    
                        speciFica Tions 50" MODELS ROUND TOP TERMINATION SQUARE CHASE-TOP  TERMINATION  2" CHIMNEY AIRSPACE  CLEARANCE TO  COMBUSTIBLE MATERIAL  NO COMBUSTIBLE  MATERIAL ON FACE  COMBUSTIBLE  WALL BOARD  1 1 /2" AIR SPACE  BACK AND SIDES  OUTSIDE AIR MINIMUM 18" TO  PERPENDICULAR  SIDEWALL  GAS LINE KNOCKOUTS HEARTH EXTENSION  74" X 20"  0" TO 12" EACH SIDE  BOTTOM 12" 38.5" 11" 67" 21.25" 58" 28.5" 49" 30" 0.625" 59" 50" 8" 59" 1" AIR KIT  KNOCK OUT   LEFT SIDE  32.75" GAS LINE  KNOCK OUTS  3.5" 10.5" 
                    
                    Resumen del contenido incluido en la página 5 
                    
                        and depth of the fireplace. Firea lp ce ins Taa ll Tion 3. Set the fireplace directly in front of this open- SELECTING LOCATION ing and slide the unit back until the nailing  To determine the safest and most efficient location  flanges touch the side framing. for the fireplace, you must take into consideration  4. Check the level of the fireplace and shim with  the following guidelines: sheet metal if necessary. 1. The location must allow for proper clearances  5. Before securing fireplace to pr
                    
                    Resumen del contenido incluido en la página 6 
                    
                        MANTELS Firea lp ce ins Taa ll Tion A mantel may be installed if desired (see Figure 4).  Continued Woodwork such as wood trims, mantels or any other  HEARTH ExTENSION combustible material projecting from the front face  A hearth extension projecting a minimum of 20"  must not be placed within 12" of the fireplace open- in front of and a minimum of 12" beyond each  ing. Combustible materials above 12" and projecting  1 side of the fireplace opening is required to protect  more than 1 / " from th
                    
                    Resumen del contenido incluido en la página 7 
                    
                        VenTing insT alla Tion LINEAL GAIN PART NO. DESCRIPTION GAIN OPTIONAL OUTSIDE AIR KIT  1 Georgian Fireplace 66 / "  (MODEL AK4/AK4F) 12-12DM 5 Pipe Section 10 / " 8 The installation of an outside air kit should be per- 12-12HT formed during the rough framing of the fireplace  18-12DM 5 Pipe Section 16 / " 8 due to the nature of it's location. Outside combus- 18-12HT tion air is accessed through a vented crawl space  24-12DM 5 (AK4F) or through a sidewall (AK4). Pipe Section 3 / " 8 24-12HT 36-
                    
                    Resumen del contenido incluido en la página 8 
                    
                        2. Chimney weight above offset rests on return  VenTing insT alla Tion elbow. Straps must be securely nailed to rafters  Continued or joists (see Figure 8, details a and b). USING ELBOW OFFSETS (30E-12DM) 3. Maximum length of pipe between supports  1. To achieve desired offset, you may install  (return elbow or 12S-12DM) is 6' of angle  combinations of 12", 18", 24", 36" and 48"  run. Maximum of two 6' angle run sections  length of double wall pipe (see offset chart  per chimney system (see Figu
                    
                    Resumen del contenido incluido en la página 9 
                    
                        PENETRATING THE ROOF VenTing insT alla Tion To maintain a 1" clearance to the pipe on a roof  Continued with a pitch, a rectangular opening must be cut. 1. Determine the center point through which the  pipe will penetrate the roof. 2. Determine the center point of the roof. Pitch  Screws is the distance the roof drops over a given  B span, usually 12". A 6/12 pitch means that  the roof drops 6" for each 12" one measure  horizontally down from the roof rafters. 3. Use the roof opening chart (Figu
                    
                    Resumen del contenido incluido en la página 10 
                    
                        VenTing insT alla Tion  CAUTION: Do not seal open- Continued ings on the rooftop flashing. Fol- Storm  low the installation instructions  Overlap  Collar Shingles Top  provided with the termination  Flashing and Sides Only being used. Cone Nail Only  RTL-10D Outer  Stainless  Perimeter  Level of  Inner Flue  of Flashing Flue Gas  Pipe Outlet Secure  Termination  to Outer Waterproof  Pipe with 3 Caulking Underlap  Screws Storm  Shingles  Collar at Bottom Flashing Figure 13 - Flashing Installation
                    
                    Resumen del contenido incluido en la página 11 
                    
                        3. Run a 1/2" black iron gas line into the fireplace  VenTing insT alla Tion through the rear at gas line conduit sleeve (if  Continued using a raised platform, add height). Provide  10 FOOT RULE sufficient gas line into fireplace chamber for  All flue gas outlet chimney terminations must fitting connection (see Figure 19). Note:  Secure incoming gas line to wood framing to  extend a minimum of 3 feet in height above the  highest point where it passes through the roof and provide rigidity for th
                    
                    Resumen del contenido incluido en la página 12 
                    
                        opTional gas ine l glass door  insT alla Tion insT alla Tion Continued IMPORTANT: Install glass door  frame before installing glass   CAUTION: All gas piping  door. and connections must be tested  for leaks after the installation  INSTALLING DOOR FRAMES is completed. After ensuring  1. Remove screws from smoke shelf (see  that the gas valve is on, apply  Figure 20). soap and water solution to all  2. Mount top door frame and secure with screws  removed in step 1. connections and joints. Bubbles 
                    
                    Resumen del contenido incluido en la página 13 
                    
                        glass door opera Tion and  insT alla Tion MainTenance  Continued guidelines INSTALLING GLASS DOORS GLASS DOORS Spring clips have been installed but some adjust- Glass doors are optional with the fireplace. When  ments may be needed. If doors do not close properly  fireplace is in operation, doors must be fully  or do not appear straight, see Door Adjustment. opened or fully closed position only or a fire hazard  1. With bi-fold doors completely folded, insert  may be created (see Figure 24). bot
                    
                    Resumen del contenido incluido en la página 14 
                    
                        opera Tion and  Damper  MainTenance  Weight uidelines g Continued Cleaning Glass Clean glass with any commercial glass cleaner or  soap and water. Do not use any abrasive material  To Close  to clean glass. Do not clean glass with any cool  Damper water if glass is still hot from the fire and smoke. A gas line or gas log lighter may be installed for the  purpose of installing a vented or vent-free deco- rative gas appliance incorporating an automatic  shutoff device and complying with the Standa
                    
                    Resumen del contenido incluido en la página 15 
                    
                        replaceMenT p ar Ts HERRINGBONE BRICK LINER Bottom Front Brick Refractory 111509-01 - VG42H Models 111509-02 - G42H Models STANDARD BRICK LINER 111515-01 - VG50H Models Bottom Front Brick Refractory  111515-02 - G50H Models 111425-01 - VG42 Models Bottom Rear Brick Refractory 111425-02 - G42 Models 111510-01 - VG42H Models 111430-01 - VG50 Models 111510-02 - G42H Models  111430-02 - G50 Models 111512-01 - VG50H Models Bottom Rear Brick Refractory  111512-02 - G50H Models 111426-01 - VG42 Models 
                    
                    Resumen del contenido incluido en la página 16 
                    
                        accessories OPTIONAL OUTSIDE AIR KIT FOR  SIDEWALL INSTALLATION - AK-4  PN 01576 BI-FOLD GLASS DOOR STORM COLLAR - SC2-1 BDG42 - 42" Black Finish BDG42B - 42" Brushed Brass Finish BDG42P - 42" Platinum Finish FIRESTOP SPACER  BDG42PB - 42" Polished Brass Finish FS-10 BD50 - 50" Black Finish BD50B - 50" Brushed Brass Finish BD50P - 50" Platinum Finish BD50PB - 50" Polished Brass Finish ROOF FLASHING V6F-10DM - 0 to 6/12 Pitch V12F-10DM - 6/12 to 12/12  Pitch DOUBLE WALL PIPE - 12-12DM,  18-12DM,