                        INSTALLATION INSTRUCTIONS
EDV Direct-Vent 
™
Gas Fireplaces
P/N 850018M   Rev. H   01/2011 MODELS
MILLIVOLT: ELECTRONIC:
This manual is one of a set of two supporting this product.  
Refer to P/N 875022M for Care and Operation Instructions.
EDVSTNM-B EDVCRNM-B EDVSTNE-B
Ce manuel est disponible en francais, simplement  
en faire la demande. Numéro de la pièce 850018CF.
EDVSTPM-B EDVCRPM-B EDVPFNE-B
EDVPFNM-B EDVCLNM-B EDVCRNE-B
EDVPFPM-B EDVCLPM-B EDVCLNE-B
Portland
US
OTL Report No. 116-F-04-5
                    
                    Resumen del contenido incluido en la página 2 
                    
                        PACKAGING GENERAL INFORMATION TABLE OF CONTENTS  The  assembled vented gas fireplace heater  is  Packaging .........................................Page 2        WARNING  packaged with: Introduction ......................................Page 2 General Information ..........................Page 2 Young children should be care- 1 - one log set located within the firebox. Requirements for the  fully supervised when they are  2 - one plastic bag containing the literature     Commonwealth of Massachu
                    
                    Resumen del contenido incluido en la página 3 
                    
                        Note: Installation and repair should be done Misc. Codes / Standards - by a qualified service person. The appliance The Installation must conform to local codes or,         WARNING  should be inspected before use and at least in the absence of local codes, with the National  annually by a professional service person. Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest  Improper installation, adjust- edition (In Canada, the current CAN/CSA-B149.1  More frequent cleaning may be required  ment, alteration,
                    
                    Resumen del contenido incluido en la página 4 
                    
                        O W IGNITER OFF ON CONTROL T H N Gas Pressure - All Models Orifice Sizes -  Sea Level to High Altitude Manifold Pressure Port ON/OFF Switch (All Models) Tables 2 and 3 show the appliances' inlet and  manifold gas pressure requirements: These appliances are tested and approved for  installation at elevations of 0-4500 feet (0-1372  Inlet Inlet Gas Supply Pressure  meters) above sea level using the standard burner Pressure (all models) Port orifice sizes (marked with an "*" in Table 4 ).   Fuel # 
                    
                    Resumen del contenido incluido en la página 5 
                    
                        COLD CLIMATE INSULATION For cold climate installations, seal all cracks  around your appliance with noncombustible  material and wherever cold air could enter  the room. It is especially important to insulate  outside chase cavity between studs and under  floor on which appliance rests, if floor is above  ground level.  Gas line holes and other open- ings should be caulked or stuffed with unfaced  HORIZONTAL VENT fiberglass insulation.  VERTICAL VENT  - REAR If the fireplace is being installed o
                    
                    Resumen del contenido incluido en la página 6 
                    
                        Be aware that this is a heat producing ap- Vertical Vent Termination  Clearances pliance. Objects placed above the unit are  Termination Heights For Vents  exposed to elevated temperatures. TERMINATION HEIGHTS FOR VENTS ABOVE  Above Flat Or Sloped Roofs FLAT OR SLOPED ROOFS  Ref. NFPA 54 / ANSI Z223.1 Horizontal Overhang  Do not insulate the space between the appli- Roof Pitch * Feet * Meters ance and the area above it (see Figure 8 ). 2 FT  Vertical  MIN.  2 FT MIN. Wall  Flat to 6/12 1.0 0.3 L
                    
                    Resumen del contenido incluido en la página 7 
                    
                        V EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS  NOTE:  Local Codes Or Regulations May Require Different Clearances. * See Item D in the Text Below. P N N NOTE:  Location Of The Vent Termination Exterior Wall Inside Must Not Interfere With Access To The Corner Detail O Electrical Service. *18” V V G Q Horizontal Termination V 6” Ventilated Soffit A Inside Corner = 9” in U.S. A = 12” in Canada Detail D H 3 ft. B B D E X C A A V V Fixed Operable L V Closed Window 3 ft. Window V F C B
                    
                    Resumen del contenido incluido en la página 8 
                    
                        MINIMUM CLEARANCES TO COMBUSTIBLES Hearth Extension - A hearth extension is not  required with this appliance. If a hearth exten- Appliance And Vent Clearances sion is used, do not block the lower control  compartment door. Any hearth extension used  The appliance is approved with zero clearance to combustible materials on all sides (as detailed  is for appearance only and does not have to  in Table 5), with the following exception: When the unit is installed with one side flush with a conform t
                    
                    Resumen del contenido incluido en la página 9 
                    
                        DETAILED INSTALLATION STEPS MINIMUM CLEARANCES*     Inches (millimeters) The appliance is shipped with all gas controls  Back and Sides 1/2 in. (13) and components installed and pre-wired.  0 (0) from Spacers Or Dimples ** 1 - Remove the shipping carton.  Top Spacers 0 (0) 2 - Remove the top radiant panel (refer to  Floor 0 (0) Figure 11 ).  3 -  Lift the pressure relief plates and remove  From Bottom of Unit To Ceiling 64 (1626) the cardboard from underneath each of  Vent 3 (76) Top* / 1 (25.4)
                    
                    Resumen del contenido incluido en la página 10 
                    
                        Step 2. (Page 14) Route gas supply line to Step 10. (Page 34) Install glass door as- appliance location. sembly. Pressure Relief  Plates Step 3.  Preparing the appliance vent collar Step 11. (Page 34) Adjust burner to ensure  (Page 14). proper flame appearance. Step 4. (Page 15) Install the vent system and Step 12. (Page 36) Install the hoods.  exterior termination.   Step 13. (Page 37) Attach Safety in Operation  Step 5. (Page 27) Field Wiring Warnings. Remove Cardboard Before a. Millivolt Appl
                    
                    Resumen del contenido incluido en la página 11 
                    
                        FIREPLACE FRAMING SPECIFICATIONS  11-3/8 inches (millimeters) inches (millimeters) EDVST 11-3/8 EDVPF (289) Minimum Framing Minimum Framing (See-Through) (Peninsula) 10-1/2 10-1/2 Stud Size is 2x4 Stud Size is 2x4 (267) (267) VENT FRAMING - VENT FRAMING - TOP VENT WITH TOP VENT WITH ONE 90º ELBOW ONE 90º ELBOW VENT FRAMING - VENT FRAMING - 7 REAR VENT WITH 7 REAR VENT WITH (178) (178) NO ELBOWS NO ELBOWS 12-1/8 12-1/8 (308) (308) 7 7 (178) (178) 5-1/8 5-1/8 (130) (130) 12-1/8 12-1/8 (308) (308) 
                    
                    Resumen del contenido incluido en la página 12 
                    
                        FIREPLACE SPECIFICATIONS 10 FINISH WALL BRACKET EDVST (See-Through) (254)  (Front and back edge of unit top) Figure 17 12 (305) FRAMING SPACERS 1/2 (Top and Both Sides) (13) NOTE - Unit has a factory-installed vent seal cap and vent cover plate (see Figures 22 and FLUE 23 on page 15) in each flue outlet. The vent (Top or Side) seal cap is not shown in this figure. 5/8 (16) DETAIL OF 40-1/8 FINISH WALL BRACKET Stepped to Accept Drywall (1019) 3-1/2 (89) 3-1/2 (89) on All 4 Corners TOP VIEW 2-1/2 
                    
                    Resumen del contenido incluido en la página 13 
                    
                        FIREPLACE SPECIFICATIONS CONTINUED EDVCL (Corner-Left) 9-1/4 OPTIONAL GAS INLET (235) 10 Figure 19 (254) FRAMING SPACERS (Top, Side and Back) NOTE - Unit has a factory-installed vent seal FLUE cap and vent cover plate (see Figures 22 and 12 (305) (Top or Side) 23 on page 15) in each flue outlet. The vent DETAIL OF seal cap is not shown in this figure. FINISH WALL BRACKET 1/2 (13) FINISH WALL BRACKET 5/8 (Front and left edge of unit top) (16) 40-1/8 Stepped to (1019) 3-1/2 Accept Drywall TOP VIEW
                    
                    Resumen del contenido incluido en la página 14 
                    
                        Step 2. ROUTING GAS LINE Installing a gas supply line from the fuel supply to IMPORTANT: If propane is used, be aware that  the appliance involves numerous considerations if tank size is too small (i.e. under 100-lbs, if  Route a 1/2" (13 mm) gas line to the left side  of materials, protection, sizing, locations, con- this is the only gas appliance in the dwelling.  of the appliance as shown in Figure 21.  Gas  trols, pressure, sediment, and more. Certainly no Ref. NPFA 58), there may be loss of
                    
                    Resumen del contenido incluido en la página 15 
                    
                        Step 4. INSTALL THE VENT SYSTEM  Securing Screws Top Vent Vent Seal Cap General Information (OUTSIDE of  Appliance) These instructions should be used as a guideline and do not supersede  Insulation local codes in any way. Install venting according to local codes, these  Cabinet Top instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the  USA or the current standards of CAN/CSA-B149.1 in Canada.  Ensure clearances are in accordance with local installation codes and  the requirements
                    
                    Resumen del contenido incluido en la página 16 
                    
                        VERTICAL TERMINATION SYSTEMS (ROOF) VENT SECTION LENGTH CHART VENT SECTION LENGTH CHART Nominal T T Nominal Section 62142638 4 Section Length 62142638 4 O O Length (inches) See Figure 25 and Figures 35 through 39  (inches) T T Net Section A A on Pages 19 and 20 and their associated    42 -1/212 0-1/22 2-1/32 4-1/ 46-1/ Net Section Length (inches) 42 -1/212 0-1/22 2-1/32 4-1/ 46-1/ L L Length (inches) Vertical Vent Tables which illustrate the various  Hs eight of Vent Number of Vent Section Hs ei
                    
                    Resumen del contenido incluido en la página 17 
                    
                        Vertical (Offset) Installation B. Attach vent components to appliance - C. Attach vent components to each other  - Other vent sections may be added to the  Secure Vent SV4.5 direct vent system compo- Analyze the vent routing and determine the nents are unitized concentric pipe components previously installed section in accordance with  the requirements of the vertical vent figures  quantities of vent sections and number of featuring positive twist lock connections (see  and tables.  To add anoth
                    
                    Resumen del contenido incluido en la página 18 
                    
                        F. Change vent direction to horizontal/inclined H. Frame roof opening - Identify location for  run - At transition from or to a horizontal/in- vent at the roof. Cut and/or frame opening per  Storm clined run, install the SV4.5E45 and SV4.5E90 Roof Framing Chart and Figure 31. Collar elbows in the same manner as the straight vent  sections.  The elbows feature a twist section to  allow them to be routed about the center axis  of their initial collar section to align with the  required direction o
                    
                    Resumen del contenido incluido en la página 19 
                    
                        VERTICAL VENT FIGURES/TABLES      Table A Note:  Secure  Vent  (rigid vent pipe)  is shown  in the figures; Secure Flex (flexible vent pipe) V Minimum H Maximum  u Ceiling Firestop / Spacer (SV4.5VF) may also be used. feet (meter) feet (meter) Note:  It is very important that the horizontal/ 2 (0.610) 1 (0.305) inclined run be maintained in a straight (no  4 (1.219) 2 (0.610) dips) and recommended to be in a slightly  6 (1.829) 3 (0.914) V elevated plane, in a direction away from the  fireplace 
                    
                    Resumen del contenido incluido en la página 20 
                    
                        VERTICAL VENT FIGURES / TABLES (CONTINUED) Table C H1 H+H Maximum H Maximum V Minimum 1    feet (meter) feet (meter) feet (meter) u Ceiling Firestop /  5 (1.524) 2 (0.610) 1 (0.305) Spacer (SV4.5VF) 10 (3.048) 4 (1.219) 2 (0.610) 15 (4.572) 6 (1.829) 3 (0.914) 20 (6.096) 8 (2.438) 4 (1.219) V + V + H + H = 40 feet (12.2 m) Max vWall Firestop/ 1 1 H = 8 feet (2.438 meters) Max. Spacer (SV4.5HF) V1 H + H = 20 feet (6.096 meters) Max. 1 Ceiling Firestop /   u  Spacer (SV4.5VF) u When using Secure F