Resumen del contenido incluido en la página 1 
                    
                        ®
Combat
UHD-Series
Tubular Duct Furnace
(Standard Range)
Installation, Operation
& Service Manual
Models UHD[X][S][R]
150, 175, 200, 225
250, 300, 350, 400
Installer
	
 !	
 
 	
	
 
!
Please take the time to read and understand
	
 "
#
these instructions prior to any installation.
$
	
	
Installer must give a c
                    
                    Resumen del contenido incluido en la página 2 
                    
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    Resumen del contenido incluido en la página 3 
                    
                        TABLE OF CONTENTS SECTION 1: Heater Safety......................................................1 SECTION 10: Operation and Maintenance ..........................21 1.1 Manpower Requirements .............................................1 10.1 Pre-Start-Up Checks ................................................21 SECTION 2: Installer Responsibility .....................................2 10.2 Begin Start-Up .........................................................21 2.1 Wall Tag ..................
                    
                    Resumen del contenido incluido en la página 4 
                    
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    Resumen del contenido incluido en la página 5 
                    
                        TABLE OF FIGURES Figure 1: Clearances to Combustibles ......................................3 Figure 2: Air Flow Direction.......................................................7 Figure 3: Suspension Methods .................................................8 Figure 4: Vent and Roof Detail ................................................ 11 Figure 5: Standard Vented Heater - Vertical and Horizontal  Vent Termination...................................................... 12 Figure 6: Standard Vente
                    
                    Resumen del contenido incluido en la página 6 
                    
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    Resumen del contenido incluido en la página 7 
                    
                        SECTION 1: HEATER SAFETY SECTION 1: HEATER SAFETY Your Safety is Important to Us! This symbol is used throughout  the manual to notify you of  possible fire, electrical or burn  hazards. Please pay special  attention when reading and  following the warnings in these  sections. Installation, service and quarterly  inspection of heater must be done by a contractor  qualified in the installation and service of gas-fired  heating equipment. Read this manual carefully before installation,  operation 
                    
                    Resumen del contenido incluido en la página 8 
                    
                        UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL SECTION 2: INSTALLER RESPONSIBILITY The installer is responsible for the following: 2.2 Corrosive Chemicals • To install the heater, as well as the gas and Caution: Do not use heater in an area containing  corrosive chemicals. Avoid the use of corrosive  electrical supplies, in accordance with applicable  chemicals to ensure a longer life of the burner, heat  specifications and codes. Roberts-Gordon  exchanger and other parts. r
                    
                    Resumen del contenido incluido en la página 9 
                    
                        SECTION 3: CRITICAL CONSIDERATIONS SECTION 3: CRITICAL CONSIDERATIONS 3.1 Basic Information 3.5 Clearances to Combustibles UHD[X][S][R] heaters have automatic ignition  WARNING burners for ON/OFF operation only. 3.2 Manufactured Units Gas-fired, power-vented duct furnace with tubular  heat exchanger. Units shall have a minimum of 82%  thermal efficiency. The standard unit shall consist of  a non-separated combustion design with an  Fire Hazard aluminized heat exchanger. Design and heat  exchange
                    
                    Resumen del contenido incluido en la página 10 
                    
                        UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL 3.6 Ventilation 3.8 Electrical Supply WARNING WARNING Carbon Monoxide Hazard Heaters may be installed  vented or unvented. Vented heaters must be  vented outdoors. Electrical Shock Hazard Unvented heaters must be  Disconnect electrical and gas supply before  installed in buildings with  servicing. ventilation rates as per  section 6.4. This appliance must be connected to a  properly grounded electrical source. Failure to follow 
                    
                    Resumen del contenido incluido en la página 11 
                    
                        SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES 4.1 Gas Codes 4.3 Parking Structures and Repair Garages The type of gas appearing on the name plate Installation in garages must be in accordance  must be the type of gas used. Installation must with the following codes: comply with national and local codes and  United States: Standard for Parking Structures  requirements of the local gas company. NFPA 88A - latest revision or the Code for  Unit
                    
                    Resumen del contenido incluido en la página 12 
                    
                        UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL 4.6 High Altitude These heaters are CSA-approved (without  modifications) for installations up to 2000' (610  m) in US and Canada. CSA approved heaters  installed above 2000' (610 m) must be de-rated.  For installations above 2000' (610 m) in US,  consult factory for information on burner de- rating. For installations from 2000' (610 m) to  4500' (1370m) in Canada, high altitude  conversion kits are available. Heaters installed 
                    
                    Resumen del contenido incluido en la página 13 
                    
                        SECTION 5: DUCT HEATER INSTALLATION SECTION 5: DUCT HEATER INSTALLATION range shown on Page 7 , Section 5.1.2. The minimum  inlet duct lengths shown on Page 7, Section 5.1.1  5.1 General  must be observed. Pressure drop through the heat  To connect the inlet and outlet ducts to the heater,  exchanger at various air flows is shown on Page 7,  Duct-Mate or similar flanges may be slid over the  Section 5.1.2. duct connector flanges supplied on the unit and  Figure 2: Air Flow Direction secured with
                    
                    Resumen del contenido incluido en la página 14 
                    
                        UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL 5.1.3 Air Flow And Temperature Rise Ranges Model Rate Air Flow Temperature Rise (Btu/h) Minimum (CFM) Maximum (CFM) Minimum (°F) Maximum (°F) UHD[X][S][R] 150 150,000 1,360 5,800 20 83 UHD[X][S][R] 175 175,000 1,400 6,850 20 95 UHD[X][S][R] 200 200,000 2,050 7,750 20 73 UHD[X][S][R] 225 225,000 2,100 8,300 20 80 UHD[X][S][R] 250 250,000 2,350 8,850 22 80 UHD[X][S][R] 300 300,000 2,700 10,200 23 86 UHD[X][S][R] 350 350,000 3,120 
                    
                    Resumen del contenido incluido en la página 15 
                    
                        SECTION 6: VENTING SECTION 6: VENTING tape or silicone sealant must be used to seal all  joints. WARNING Aluminum tape shall have a minimum temperature  Carbon Monoxide Hazard rating of 400° F (204° C) and meet SMACNA AFTS- 100-73 standards. High temperature silicone sealant  Heaters may be installed  must have a minimum temperature rating of 480° F  vented or unvented. (250° C). Vented heaters must be  vented outdoors. 6.2.1 United States Requirements Unvented heaters must be  Vent must termina
                    
                    Resumen del contenido incluido en la página 16 
                    
                        UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL Vents and air intakes must be adequately States); 3 cfm per 1000 Btu/h firing rate (Canada). supported so that the heater does not bear the  weight of the pipes. WARNING: Combustion by-products contain a  For vent termination See Page 11, Figure 4 through chemical known to the State of California to cause  Page 14, Figure 9. cancer and birth defects or other reproductive harm. 6.3.1 Standard Vented Heaters  6.5 Horizontal Ventin
                    
                    Resumen del contenido incluido en la página 17 
                    
                        SECTION 6: VENTING The entire vent should be insulated with foil faced 4. Follow the lighting instructions. Place the  fiberglass insulation (1/2" thick, 1-1/2# density appliance being inspected in operation.   minimum). Adjust thermostat so that the appliance will  operate continuously. 6.7.1 Maximum Vent Lengths 5. For any appliance having a draft hood, test for  draft hood appliance spillage at the draft hood  Model UHD[X][S][R] 150 - 400 Number of Elbows 40 ft (12.2 m) 1 relief opening after
                    
                    Resumen del contenido incluido en la página 18 
                    
                        UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL Figure 5: Standard Vented Heater - Vertical and Horizontal Vent Termination               Model Vent Diameter Part Number UHD[X][R] 150 - 400 4" (10 cm) 90502102 Figure 6: Standard Vented Heater  - Common Vertical Vent Termination 12                                                                                                                                                                                                       
                    
                    Resumen del contenido incluido en la página 19 
                    
                        SECTION 6: VENTING Figure 7: Separated Combustion Heater - Vertical and Horizontal Vent Termination 12" (31 cm) Minimum from air inlet to  vent termination (may be horizontal NOTE: Vent supports not or vertical clearance). shown. Duct supports    not shown. Duct and   12" (31 cm)  vent supports not   Minimum from   provided by the    wall to vent  manufacturer. termination.  Vent 12" (31 cm) Air Intake* Minimum from  air inlet to vent Vertical termination (may be  Option Horizontal horizontal or
                    
                    Resumen del contenido incluido en la página 20 
                    
                        UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL Figure 9: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater  Description Part Number Qty. Model Vent Diameter Concentric Vent Kit (150 - 250) UHVK1 UHD[X]S[R] 150 - 400 4" (10 cm) Concentric Vent Box Top & Side Assembly 90504113 1 Model *Air Intake Diameter Concentric Vent Box Bottom Assembly 90504112 1 UHD[X]S[R] 150 - 250 4" (10 cm) Screw #6 x 3/8 Self Drilling 91119100 14 UHD[X]S[R] 300 - 400 5