Resumen del contenido incluido en la página 1 
                    
                        ReSidential and OutdOOR W OOdbuRning FiReplace
OWneR’S OpeRatiOn and inStallatiOn Manual
MOdelS S36, S36H, S36R, S36RH, VS36(1) and VS36H(1)
SAVE THIS BOOK
This book is valuable. In addition to instructing you 
on how to install and maintain your appliance, it also 
contains information that will enable you to obtain re-
placement parts or accessory items when needed. Keep 
it with your other important papers.
This fireplace is approved for use as a wood burning 
fireplace or for use with a vent
                    
                    Resumen del contenido incluido en la página 2 
                    
                        WARNING: Improper installation, adjustment, altera- tion, service or maintenance can cause injury, property  damage or loss of life. Refer to this manual for assis- tance or additional information. Consult a qualified  installer or local distributor. t able OF cOntentS Safety Information ............................................... 2 Operation and Maintenance Guidelines ............ 12 Specifications ...................................................... 3 Technical Service...................
                    
                    Resumen del contenido incluido en la página 3 
                    
                        SpeciFicatiOnS 1" AIRSPACE ELECTRICAL OUTLET TO COMBUSTIBLE RIGHT SIDE GAS LINE 0" TO MATERIAL KNOCK OUTS TOP SPACERS NO COMBUSTIBLE MATERIAL ON FACE 8.125" 2.5" 7.092" 8.717" 11.217" AIR KIT  KNOCK OUT LEFT SIDE GAS LINE COMBUSTIBLE KNOCK OUTS WALL BOARD 3/4" AIR SPACE BACK AND SIDES 10.435" 8.125" 2.5" NOT LESS THAN 12" TO PERPENDICULAR SIDEWALL OUTSIDE AIR 8.717" (LEFT SIDE ONLY) 14.437" HEARTH EXTENSION 66" X 20" 12" 0" TO EACH SIDE BOTTOM 29" 22" 14.25" 21 12.5" 32.5" 0.625" 41" ROUND TOP T
                    
                    Resumen del contenido incluido en la página 4 
                    
                        FRAMING FiRelp ace inStallati On 1. Frame the opening for the fireplace using the  SELECTING LOCATION dimensions shown in Figures 1 and 2. To determine the safest and most efficient location  2. If the fireplace is to be installed directly on  for the fireplace, you must take into consideration  carpeting, tile (other than ceramic) or any  the following guidelines: combustible material other than wood floor- 1. The location must allow for proper clearances  ing, the fireplace must be installed u
                    
                    Resumen del contenido incluido en la página 5 
                    
                        MANTELS FiRelp ace inStallati On A mantel may be installed if desired (see Figure  Continued 4). Woodwork such as wood trims, mantels or  DRAIN PAN (DP36) any other combustible material projecting from  For outdoor installations, the fireplace enclosure  the front face must not be placed within 12" of  must allow for adequate drainage and fresh air  the fireplace opening. Combustible materials  1 ventilation. It is recommended that a sealed, corro- above 12" and projecting more than 1 / " from t
                    
                    Resumen del contenido incluido en la página 6 
                    
                        Venting inStallatiOn LINEAL GAIN PART NO. DESCRIPTION GAIN OPTIONAL OUTSIDE AIR KIT  36" Fireplace 40" (MODEL AK4/AK4F) 12-8DM  Pipe Section 10 / " 8 The installation of an outside air kit should be per- 12-8HT formed during the rough framing of the fireplace  18-8DM  Pipe Section 16 / " 8 due to the nature of it's location. Outside combus- 18-8HT tion air is accessed through a vented crawl space  24-8DM  (AK4F) or through a sidewall (AK4). Pipe Section 23 / " 8 24-8HT 36-8DM  Pipe Section 3
                    
                    Resumen del contenido incluido en la página 7 
                    
                        Venting inStallatiOn OFFSET RISE CHIMNEY LENGTH A B 48" 36" 24" 18" 12" Continued 3 3 4 /8" 16 /8" ELBOW SET ONLY Continue to assemble chimney sections as outlined,  3 1 9 /4" 2 /2" 1 making sure that both the inner and outer pipe sec- 3 3 12 / " 30 / " 1 4 4 tions are locked together. When installing double  3 1" 34 / " 1 4 wall snap-lock chimney together, it is important  18" 40" 1 1 to assure the joint between the chimney sections  1 1 21 / " 46 / " 1 4 4 is locked. Check by pulling chimney
                    
                    Resumen del contenido incluido en la página 8 
                    
                        Existing  Venting inStallatiOn Ceiling  Continued Frame See Detail A Firestop  2" Min. Spacer Screws or  Staples  (Min. of 8) Straps Figure 10 - Firestop Spacer with Living  Straps Space Above Ceiling Detail B See Detail B Angle Firestop Screws or Staples  Firestop  (Min. of 8) Spacer Existing  Ceiling  Straps Straps Frame Detail A Return Elbow Figure 8 - Ceiling Support Pipe   12S-8DM Figure 11 - Firestop Spacer with Attic  Space Above Ceiling PENETRATING THE ROOF To maintain a 1" clearance to 
                    
                    Resumen del contenido incluido en la página 9 
                    
                        Storm Collar Installation (SC1 or SC2) Venting inStallatiOn Place storm collar over pipe and slide down until  Continued it is snug against the open edge of the flashing (see  Figure 14). Use SC1 for all round terminations and  3 14 /8" Min. SC2 for all terminations with slip sections. Apply  30" Min. (365 mm) 1" Min. (762 mm) waterproof caulk around the perimeter of the collar  (25 mm) 1" Min. to provide a proper seal. (25 mm) Chimney Waterproof  Pipe Caulk 1" Min. (25 mm) Storm  Flashing Colla
                    
                    Resumen del contenido incluido en la página 10 
                    
                        10 FOOT RULE Venting inStallatiOn All flue gas outlet chimney terminations must  Continued extend a minimum of 3 feet in height above the  Terminations with 16" slip pipe sections are avail- highest point where it passes through the roof and  able. The RTT-8DM and RTTL-8DM are approved  must be at least 2 feet above the highest point of  for flashing installations. When needed, these  the roof that is within a horizontal distance of 10  adjustable terminations may be used in combina- feet (see F
                    
                    Resumen del contenido incluido en la página 11 
                    
                        Venting inStallatiOn Continued EFFECTIVE HEIGHT OF EFFECTIVE HEIGHT OF TERMINATION CAP TERMINATION CAP MINIMUM HEIGHT OF 22 FT. (WITH TWO ELBOW SETS) MAXIMUM HEIGHT OF 50 FT. MAXIMUM EFFECTIVE HEIGHT OF EFFECTIVE HEIGHT OF  HEIGHT 50 FT. TERMINATION CAP TERMINATION CAP (ANY SYSTEM) 14.5 FT. 14.5 FT. MINIMUM MINIMUM HEIGHT HEIGHT UP TO 6 FT. MAXIMUM UP TO 6FT. MAXIMUM 30E-8DM 30E-8DM Figure 18 - Typical Residential Installations 4. Repack insulation around gas line and into  OptiOnal gaS line  sl
                    
                    Resumen del contenido incluido en la página 12 
                    
                        OptiOnal a g S line   WARNING: To avoid the risk of  inStallatiOn damaging the fireplace materials  Continued and increasing the risk of spread- ing a fire, do not use the fireplace   CAUTION: All gas piping  to cook or warm food. and connections must be tested  for leaks after the installation   WARNING: If the fireplace  is completed. After ensuring  has been used for wood burning,  that the gas valve is on, apply  the firebox and chimney must be  soap and water solution to all  cleaned of soo
                    
                    Resumen del contenido incluido en la página 13 
                    
                        OPEN CLOSE If you wish to install an unvented (vent-free) gas  OpeRatiOn and  log set, only unvented gas log sets which have been  Maintenance  found to comply with the standard for unvented  room heaters, ANSI Z21.11.2 are to be installed  guidelineS in this fireplace. Continued A fireplace equipped with glass doors operates OUTSIDE AIR AND DAMPER  mush differently than a fireplace with an open  HANDLE OPERATION front. A fireplace with glass doors has a limited  The damper handle, which opens a
                    
                    Resumen del contenido incluido en la página 14 
                    
                        illuStRated p aRtS bReakdOWn WOODBURNING FIREPLACE MODELS  S36, S36H, S36R, S36RH, VS36(1) AND VS36H(1) 35 29 2 1 21 5 8 15 17 28 20 30 25 9 18 11 19 37/38 7 12 3 36 34 31 4 24 10 32 6 26 33 22 16 13 27 14 16 23 27 14 www.desatech.com 111026-01C                                                                                                                                                                                                                                                               
                    
                    Resumen del contenido incluido en la página 15 
                    
                        a p R tS liSt WOODBURNING FIREPLACE MODELS S36, S36H, S36R, S36RH, VS32(1)  AND VS32H(1) This list contains replaceable parts used in your fireplace. When ordering parts, see Replacement Parts  on page 16 of this manual. KEY  KEY  NO. PART NO. DESCRIPTION QTY. NO. PART NO. DESCRIPTION QTY. 1 106638-01 Insulation Pan 1 22 10777-01 Access Panel 1 2 ** Fireplace Top 1 23 10784-01  Right Refractory Bracket 1 3 106641-01 Fireplace Surround 1 24 10784-02  Left Refractory Bracket 1 4 106642-01 Air R
                    
                    Resumen del contenido incluido en la página 16 
                    
                        ReplaceMent p aRtS STANDARD BRICK LINER HERRINGBONE  EMBER PROTECTOR  Right Side  BRICK LINER  Rear  Bottom  GRATE  EP-36  PN 111028-01  Front Bottom  Left Side  See Parts List on page 17 for part numbers. acceSSORieS DOUBLE WALL PIPE  OPTIONAL OUTSIDE AIR KIT ADJUSTABLE HOOD  12-8DM 12-8HT  REQUIRED WHEN INSTALLING FOR SIDE WALL INSTALLATION  18-8DM 18-8HT  A VENT-FREE GAS LOG  24-8DM 24-8HT IN THIS FIREPLACE  HEARTH EXTENSION HE-36 ANTIQUE BRASS FINISH GA6053  POLISHED BRASS FINISH GA6052  36-
                    
                    Resumen del contenido incluido en la página 17 
                    
                        nOteS _____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ 
                    
                    Resumen del contenido incluido en la página 18 
                    
                        nOteS _____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ 
                    
                    Resumen del contenido incluido en la página 19 
                    
                        nOteS _____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ 
                    
                    Resumen del contenido incluido en la página 20 
                    
                        2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com 111026-01 111026 01 Rev. C NOT A UPC 01/06