                        Sierra Series 220 and 221
™
Innova-Flo Vortex Flow Meters
Instruction Manual 
Part Number IM-22 
05/03 Revision C 
IMPORTANT: This manual is for use with 220/221 Vortex Products 
 purchased during 1997 through January 2006
CORPORATE HEADQUARTERS 
5 Harris Court, Building L   Monterey, CA 93940 
Phone (831) 373-0200   (800) 866-0200    Fax (831) 373-4402 
www.sierrainstruments.com 
EUROPE HEADQUARTERS 
Bijlmansweid 2  1934RE  Egmond a/d Hoef  The Netherlands 
Phone +31 72 5071400   Fax +31 72 507
                    
                    Résumé du contenu de la page N° 2 
                    
                          Table of Contents Series 220/221 Instruction Manual Customer Notice  Unless you have specifically ordered Sierra’s optional O cleaning, this flow meter  2 may not be fit for oxygen service. Sierra Instruments, Inc., is not liable for any  damage or personal injury, whatsoever, resulting from the use of Sierra Instru- ments standard mass flow meters for oxygen gas. You are responsible for clean- ing the mass flow meter to the degree required for your oxygen flow application.                    
                    
                    Résumé du contenu de la page N° 3 
                    
                          Series 220/221 Instruction Manual Table of Contents Table of Contents  Chapter 1 Introduction  ™ Innova-Flo Vortex Flow Meters........................................................ 1-1   Using this Manual ......................................................................... 1-1   Note and Safety Information ......................................................... 1-2   Receipt of System Components .................................................... 1-2   Technical Assistance ..........
                    
                    Résumé du contenu de la page N° 4 
                    
                          Table of Contents Series 220/221 Instruction Manual Chapter 4  Troubleshooting and Repair  Hidden Diagnostics Menus..................................................................4-1   Column One Hidden Diagnostics Values......................................4-2   Column Two Hidden Diagnostics Values .....................................4-2  Analog Output Calibration ..................................................................4-3  Troubleshooting the Flow Meter ........................
                    
                    Résumé du contenu de la page N° 5 
                    
                          Series 220/221 Instruction Manual Table of Contents Warnings and Cautions      Warning!  Agency approval for hazardous location installations varies between flow meter models.  Consult the factory for specific flow meter approvals before any hazardous location instal- lation. For explosion proof installations, you must use solid metal conduit and follow  NFPA (or your local code) approved wiring methods.    Hot tapping must be performed by a trained professional. U.S. regulations often require
                    
                    Résumé du contenu de la page N° 6 
                    
                          Table of Contents Series 220/221 Instruction Manual   0-6 IM-22-C                                                                                                                                                                                                                                                                                                                                                                                                                                                 
                    
                    Résumé du contenu de la page N° 7 
                    
                          Series 220/221 Instruction Manual Chapter 1 Introduction Chapter 1  Introduction  Innova-Flo™ Vortex Flow Meters  The Sierra Instruments’ Series 220 In-Line and the Series 221 Insertion  Innova-Flo™ Vortex Flow Meters provide a reliable solution for process  flow measurement. From a single entry point in the pipeline, Innova-Flo  meters offer precise measurements of mass or volumetric flow. The ve- locity sensor reduces the effects of pipeline vibration by incorporating a  unique piezoelectric
                    
                    Résumé du contenu de la page N° 8 
                    
                          Chapter 1 Introduction Series 220/221 Instruction Manual Note and Safety Information  We use note, caution and warning statements throughout this book to  draw your attention to important information.         Caution! Note  Warning!  This statement appears with This statement appears with This statement appears with a  information that is important to information that is important short message to alert you to  protect people and equipment for protecting your equipment an important detail.  fr
                    
                    Résumé du contenu de la page N° 9 
                    
                          Series 220/221 Instruction Manual Chapter 1 Introduction How the Innova-Flo Vortex Flow Meter Operates      Figure 1-1. Series 220 In-Line Vortex Flow Meter    ™ Sierra Series 220 and 221 Innova-Flo Vortex Flow Meters use a unique  velocity sensor head to monitor volumetric flow rate. The built-in flow  computer calculates mass flow rate based on a constant value of fluid  density stored in the instrument’s memory.  To measure fluid velocity,  the flow meter incorporates a bluff body (shedder 
                    
                    Résumé du contenu de la page N° 10 
                    
                          Chapter 1 Introduction Series 220/221 Instruction Manual Vortex Shedding Frequency  Von Karman vortices form downstream of a shedder bar into two distinct  wakes. The vortices of one wake rotate clockwise while those of the  other wake rotate counterclockwise. Vortices generate one at a time, al- ternating from the left side to the right side of the shedder bar. Vortices  interact with their surrounding space by over-powering every other  nearby swirl on the verge of development. Close to the 
                    
                    Résumé du contenu de la page N° 11 
                    
                          Series 220/221 Instruction Manual Chapter 1 Introduction Flow Velocity Range  To ensure trouble-free operation, vortex flow meters must be correctly  sized so that the flow velocity range through the meter lies within the  measurable velocity range (with acceptable pressure drop) and the linear  range.    The measurable range is defined by the minimum and maximum velocity  using the following table.     Gas Liquid   25  ft/s    3 ρ Vmin 1 ft/s English ρ (lb/ft )  Vmax 300 ft/s 30 ft/s   37    
                    
                    Résumé du contenu de la page N° 12 
                    
                          Chapter 1 Introduction Series 220/221 Instruction Manual ™ As shown below, Innova-Flo Vortex Flow Meters exhibit a constant  Strouhal number across a large range of Reynolds numbers, indicating a  consistent linear output over a wide range of flows and fluid types. Be- low this linear range, the intelligent electronics in Innova-Flo automati- cally corrects for the variation in the Strouhal number.  Innova-Flo’s  smart electronics correct for this non-linearity by calculating the Rey- nolds nu
                    
                    Résumé du contenu de la page N° 13 
                    
                          Series 220/221 Instruction Manual Chapter 1 Introduction Flow Meter Configurations  Innova-Flo™ Vortex Flow Meters are available in two configurations:  • Series 220 in-line flow meter (replaces a section of the pipeline)  • Series 221 insertion flow meter (requires a “cold” tap or a “hot” tap  into an existing pipeline)    Both the in-line and insertion configurations are similar in that they both  use identical electronics and have similar sensor heads. Besides installa- tion differences, th
                    
                    Résumé du contenu de la page N° 14 
                    
                          Chapter 1 Introduction Series 220/221 Instruction Manual The meter includes a local 2 x 16 character LCD display housed within  the enclosure. Local operation and reconfiguration is accomplished using  six push buttons. For hazardous locations, the six push buttons can be  operated through the sealed enclosure using a hand-held magnet, thereby  not compromising the integrity of the hazardous location certification.    The electronics include nonvolatile memory that stores all configuration  in
                    
                    Résumé du contenu de la page N° 15 
                    
                          Series 220/221 Instruction Manual Chapter 2 Installation Chapter 2  Installation  Installation Overview  Innova-Flo™ meter installations are simple and straightforward. Both the Se- ries 220 In-Line and Series 221 Insertion type flow meter installations are  covered in this chapter. After reviewing the installation requirements given  below, see page 2-3 for Series 220 installation instructions. See page 2-6 for  Series 221 installation instructions. Wiring instructions begin on page 2-19.  Fl
                    
                    Résumé du contenu de la page N° 16 
                    
                          Chapter 2 Installation Series 220/221 Instruction Manual Unobstructed Flow Requirements  Select an installation site that will minimize possible distortion in the flow  profile. Valves, elbows, control valves and other piping components may  cause flow disturbances. Check your specific piping condition against the ex- amples shown below. In order to achieve accurate and repeatable perform- ance install the flow meter using the recommended number of straight run  pipe diameters upstream and dow
                    
                    Résumé du contenu de la page N° 17 
                    
                          Series 220/221 Instruction Manual Chapter 2 Installation Series 220 In-Line Flow Meter Installation  Install the Series 220 In-Line Flow Meter between two conventional pipe  flanges as shown in Figures 2-3 and 2-4. Table 2-1 provides the recom- mended minimum stud bolt lengths for wafer-style meter body size and dif- ferent flange ratings.    The meter inside diameter is equal to the same size nominal pipe ID in  schedule 80.  For example, a 2” meter has an ID of 1.939” (2” schedule 80).   Do 
                    
                    Résumé du contenu de la page N° 18 
                    
                          Chapter 2 Installation Series 220/221 Instruction Manual Wafer-Style Flow Meter Installation  Install the wafer-style meter between two conventional pipe flanges of the  same nominal size as the flow meter. If the process fluid is a liquid, make  sure the meter is located where the pipe is always full. This may require lo- cating the meter at a low point in the piping system. Note: Vortex flow me- ters are not suitable for two-phase flows (i.e., liquid and gas mixtures). For  horizontal pipeli
                    
                    Résumé du contenu de la page N° 19 
                    
                          Series 220/221 Instruction Manual Chapter 2 Installation Flange-Style Flow Meter Installation  Install the flange-style meter between two conventional pipe flanges of the  same nominal size as the flow meter. If the process fluid is a liquid, make  sure the meter is located where the pipe is always full. This may require lo- cating the meter at a low point in the piping system. Note: Vortex flow me- ters are not suitable for two-phase flows (i.e., liquid and gas mixtures). For  horizontal pipe
                    
                    Résumé du contenu de la page N° 20 
                    
                          Chapter 2 Installation Series 220/221 Instruction Manual  Series 221 Insertion Flow Meter Installation  Prepare the pipeline for installation using either a cold tap or hot tap method  described on the following pages. Refer to a standard code for all pipe tap- ping operations. The following tapping instructions are general in nature and  intended for guideline purposes only. Before installing the meter, review the  mounting position and isolation value requirements given below.  Mounting Posi