Résumé du contenu de la page N° 1 
                    
                        Instruction Manual
 resIdentIal Gas water heaters
power vented Gas Models w /hot surface IGnItIon
NOT FOR USE IN MANUFACTURED (MOBILE) HOMES
Model Gp6 50YIvIt serIes 100
Technical Support: 800-365-0024
Parts: 800-821-2017
www.statewaterheaters.com
Low Lead Content
• for Your safety •
AN ODORANT IS ADDED TO THE GAS USED 
BY THIS WATER HEATER.
all technIcal and warrantY questIons: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS 
PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRIT
                    
                    Résumé du contenu de la page N° 2 
                    
                        safe InstallatIon, use and servIce The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and  others of a potential injury hazard.  Read and obey all safety messages and instructions throughout this manual.  It is very important  that the meaning of each safety message is understood by you and others who
                    
                    Résumé du contenu de la page N° 3 
                    
                        General safetY InforMatIon 3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        
                    
                    Résumé du contenu de la page N° 4 
                    
                        General safetY InforMatIon at least 18" (45.7 cm) above the floor. This  will reduce, but not eliminate, the risk 4                                                                                                                                                                                                                                                                                                                                                                                                 
                    
                    Résumé du contenu de la page N° 5 
                    
                        taBle of contents SAFE INSTALLATION, USE AND SERVICE................................................2 Filling the Water Heater ................................................................17-18 APPROVALS ................................................................................................2 Vent Pipe Assembly ...........................................................................18 GENERAL SAFETY INFORMATION .........................................................3-4  Venting .
                    
                    Résumé du contenu de la page N° 6 
                    
                        InstallatIon requIreMents for the coMMonwealth of Massachusetts coMMonwealth of Massachusetts InspectIon The state or local gas inspector of the side wall horizontally  For all side wall terminated, horizontally vented power vent, direct  vented gas fueled equipment shall not approve the installation  vent, and power direct vent gas fueled water heaters installed in  unless, upon inspection, the inspector observes carbon monoxide  every dwelling, building or structure used in whole or in part fo
                    
                    Résumé du contenu de la page N° 7 
                    
                        tYpIcal InstallatIon Get to Know Your water heater - Gas Models  a v ent pipe h h Bushing  q rating plate   B anode II nipple  r  Insulation  c hot w ater outlet jj condensate t ee  s v ent t erminal  D Outlet (120 VAC) K K adapter  t drain v alve  f Gas supply ll plug  u Igniter and Main Burner  G Main Manual Gas shuttoff v alve MM vent pipe assembly #1  w  drain pan  h Ground joint union nn v ent pipe assembly #2  X  Gas control v alve  j dirt leg oo v ent pipe assembly #3  Y control harness* 
                    
                    Résumé du contenu de la page N° 8 
                    
                        tYpIcal InstallatIon condensate hose and draIn pan fIGure 1a. 8                                                                                                                                                                                                                                                                                                                                                                                                                                                     
                    
                    Résumé du contenu de la page N° 9 
                    
                        tYpIcal InstallatIon MIXInG valve / therMal eXpansIon tanK usaGe and space heatInG fIGure 2. h e a t e r 	 ( s e e 	 F i g u r e 	 3 ) 	 o r 	 a t 	 h o t 	 w a t e r 	 t a p s 	 t o 	 f u r t h e r 	 r e d u c e 	 s y s t e m	 MIXInG v alves water temperature. Mixing valves are available at plumbing supply stores. Consult a  Water temperature over 125°F (52°C) Q u a l i fi e d 	 I n s t a l l e r 	 o r 	 S e r v i c e 	 A g e n c y . 	 F o l l o w 	 m i x i n g 	 v a l v e 	 m a n u f a c t u r
                    
                    Résumé du contenu de la page N° 10 
                    
                        locatInG the new water heater f acts to consIder aBout the locatIon Carefully choose an indoor location for the new water heater, because  the placement is a very important consideration for the safety of the  occupants in the building and for the most economical use of the  appliance. t his water heater is not for use in manufactured  (mobile) homes or outdoor installation. Whether replacing an old water heater or putting the water heater in  a new location, the following critical points must b
                    
                    Résumé du contenu de la page N° 11 
                    
                        in	 an	 alcove	 or	 closet,	 the	 entire	 floor	 must	 be	 covered	 by	 the	 panel.	 If this water heater will be used in beauty shops, barber shops,  Failure	to	heed	this	warning	may	result	in	a	fire	hazard. cleaning establishments, or self-service laundries with dry cleaning  equipment, it is imperative that the water heater or water heaters  be installed so that combustion and ventilation air be taken from  outside these areas.   P r o p e l l a n t s 	 o f 	 a e r o s o l 	 s p r a y s 	 a n
                    
                    Résumé du contenu de la page N° 12 
                    
                        Such a condition often will result in a yellow, luminous burner free area and metal louvers and grilles will have 75% free area. Non  flame, causing sooting of the combustion chamber, burners and  motorized	louvers	and	grilles	should	be	fixed	in	the	open	position. flue tubes and creates a risk of asphyxiation. fresh aIr openInGs for confIned spaces D o 	 n o t 	 i n s t a l l 	 t h e 	 w a t e r 	 h e a t e r 	 i n 	 a 	 c o n fi n e d 	 s p a c e 	 u n l e s s 	 a n	 adequate supply of air for 
                    
                    Résumé du contenu de la page N° 13 
                    
                        Figure 7. The water heater should have clearances of at least 1 inch T h e	 c o n fi n e d	 s p a c e	 s h o u l d	 b e	 p r o v i d e d	 w i t h	 t w o	 p e r m a n e nt	 v e r t i c a l	 ( 2 5 	 m m ) 	 f r o m 	 t h e 	 s i d e s 	 a n d 	 b a c k 	 a n d 	 6 	 i n c h e s 	 ( 1 5 0 	 m m ) 	 f r o m 	 t h e 	 f r o n t	 d u c t s ,	 o n e	 c o m m e n c i n g	 w i t h i n	 1 2	 i n c h e s	 ( 3 0 0	 m m )	 o f	 t h e	 t o p	 a n d	 of the appliance. The opening should directly communicate wi
                    
                    Résumé du contenu de la page N° 14 
                    
                        InstallInG the new water heater This water heater should not be connected to any heating systems or  cheMIcal vapor corrosIon c o m p o n e n t (s) 	 u s e d 	 w i t h 	 a 	 n o n - p o t a b l e 	 w a t e r 	 h e a t i n g 	 a p p l i a n c e . CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY  All piping components connected to this unit for space heating  OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL  applications should be suitable for use with potable water. VAPORS. SUCH CORROSION MAY R
                    
                    Résumé du contenu de la page N° 15 
                    
                        duct tape, electrical tape, or equivalent.  IMPORTANT:  The insulation  therMal eXpansIon and tape must not block the discharge opening or hinder access to the  A s 	 w a t e r 	 i s 	 h e a t e d , 	 i t 	 e x p a n d s 	 ( t h e r m a l 	 e x p a n s i o n ) . 	 I n 	 a 	 c l o s e d 	 s y s t e m	 m a n u a l 	 r e l i e f 	 l e v e r 	 ( F i g u r e 	 1 1 ) . 	 	 E n s u r e 	 a 	 d i s c h a r g e 	 p i p e 	 i s 	 i n s t a l l e d 	 i n t o	 the volume of water will grow when it is heated
                    
                    Résumé du contenu de la page N° 16 
                    
                        discharge opening must not be blocked or reduced in size under any  hIGh altItude InstallatIon c i r c u m s t a n c e s . 	 E x c e s s i v e 	 l e n g t h , 	 o v e r 	 3 0 	 f e e t 	 ( 9 . 1 4 	 m ) , 	 o r 	 u s e 	 o f	 more than four elbows can cause restriction and reduce the discharge  capacity of the valve. No valve or other obstruction is to be placed between the  Temperature-Pressure Relief Valve and the tank. Do not connect  discharge	piping	directly	to	the	drain	unless	a	6”	(15.2	c
                    
                    Résumé du contenu de la page N° 17 
                    
                        A gas line of sufficient size must be run to the water heater.   sedIMent traps C o n s u l t 	 t h e 	 c u r r e nt 	 e d i t i o n 	 o f 	 N a t i o n a l 	 Fu e l 	 G a s 	 C o d e 	 ( A N S I	 Z 2 2 3 . 1/ N F PA 	 5 4) 	 a n d 	 y o u r 	 g a s 	 s u p p l i e r 	 c o n c e r n i n g 	 p i p e 	 s i ze . There must be: •	 A 	 readily	 accessible	 manual	 shuttof f	 valve	 in	 the	 gas	 supply	 line	 serving the water heater, and •	 A 	 drip	 leg	 (sediment	 trap)	 ahead	 of 	 gas	 control	 
                    
                    Résumé du contenu de la page N° 18 
                    
                        Never use this water heater unless it is completely full of water. To prevent see Figure 16. Disassemble the parts and cement back together  d a m a g e 	 t o 	 t h e 	 t a n k , 	 t h e 	 t a n k 	 m u s t 	 b e 	 fi l l e d 	 w i t h 	 w a t e r . 	 W a t e r 	 m u s t 	 fl o w 	 f r o m	 using the alignment marks. After the cement dries, attach the  the	hot	water 	faucet	before	turning	“ON”	gas	to	the	water	heater. assembly to the blower and the water heater exhaust using the  supplied rubber
                    
                    Résumé du contenu de la page N° 19 
                    
                        v v terMInatIon clearances sIdewall power vent POWER VENT (using room air for combustion) EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION D E L B VENT TERMINAL AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED V X fIGure 15.   Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion. us InstallatIons us InstallatIons Clearance above grade, veranda, porch,  Clearance to each side of center line 3	feet	(91	cm)	within	a	height	15	feet	(4.5
                    
                    Résumé du contenu de la page N° 20 
                    
                        of cracks or fractures, particularly at joints between elbows and other  plannInG the vent sYsteM fi t t i n g s 	 a n d 	 s t r a i g h t 	 r u n s 	 o f 	 v e n t 	 p i p e . 	 C h e c k 	 s y s t e m 	 f o r 	 s i g n s 	 o f 	 s a g g i n g	 or other stresses in joints as a result of misalignment of any components  Plan the route of the vent system from the discharge of the blower  in system. If any of these conditions are found, they must be corrected in  to the planned location of the vent