GO SERIES BOILER
SUGGESTED SPECIFICATIONS
I. General Requirements
A. Furnish and install (qty) low pressure, natural draft, cast iron sectional boiler(s).
B. Install boiler unit(s) in compliance with manufacturer’s installation instructions.
All work must be done in a neat and workmanlike manner.
C. Weil-McLain (qty) P/B/A (circle one) W/WT/S (circle one) GO - (size)
boiler(s) capable of burning No. 2 fuel oil. “P” boilers not available for sizes 7-9.
D. Boiler assembly:
1.
ページ2に含まれる内容の要旨
2. Water boiler(s) maximum allowable working pressure will be 50 PSIG. Steam boiler(s) maximum allowable working pressure will be 15 PSIG. J. Regulatory requirements: 1. Boiler(s) and controls shall comply with applicable regulations. K. Submittals 1. Submit shop drawings and product data. 2. Submittal packet to include boiler descriptive literature, installation instructions, operating instructions, and maintenance instructions. II. Product A. Acceptable boiler manufacturer(s) incl
ページ3に含まれる内容の要旨
• Provided with a swing-away burner mounting door to allow greater ease of service. • Provided with the means to vent out the top or out the rear of the boiler. • Shipped with insulated heavy gauge steel jacket(s) with durable powdered paint enamel finish. Jacket designed to be installed after connecting supply and return piping. C. Boiler foundation(s) 1. Installer shall construct required level concrete foundation(s) and support(s) where boiler room floor is uneven or will not support t
ページ4に含まれる内容の要旨
F. Optional Components 1. WGO or WTGO Boiler(s) only: The boiler(s) shall be able to be provided with an optional relief valve set to relieve at 50 PSIG. 2. The boiler(s) shall be able to be installed with an optional tankless heater (Not available for Model WGO Boiler(s); standard on Model P-WTGO Boiler(s)). • Tankless heater must be specified when order is placed. • Tankless heater shall have ½” inlet and outlet openings for Model A- or B-WTGO Boiler(s) and ¾” inlet and outlet openings