ページ1に含まれる内容の要旨
Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU8000RT3UN50
SmartOnline Expandable Rack/Tower UPS System- Special version of SU8000RT3U with twist-lock 50A input
plug
Highlights
8000VA (8kVA) on-line 6U rack/tower UPS with expandable runtime (3U
power module + 3U battery pack) with twist-lock 208/240V 50A input plug
Zero transfer time, on-line, double-conversion and economy-mode operation
supported
Detachable PDU w
ページ2に含まれる内容の要旨
Two sets of 4 post rackmount rails (one for each of the 3U components) One set of tower stands for upright tower configuration PowerAlert software, complete data cabling, user manual with warranty information Features 8,000 VA (8kVA) on-line, double-conversion UPS system (High voltage input/High voltage output) Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected equipment Installs in only 6 rack spaces (3U power module/3U b
ページ3に含まれる内容の要旨
Recommended 208/240V AC 50A circuit with either a 50A Hubbell CS8264C female connector or CS8269 wall receptacle Electrical Service BATTERY Full load runtime 6 min. (8000VA/6400W) Half load runtime 15 min. (4000VA/3200W) Expandable battery Runtime is expandable with optional external battery packs runtime Connects to UPS via Included 3-wire DC cable DC system voltage 240VDC Typical battery 4-6 years lifespan Battery recharge rate Less than 8 hours to 90% (included battery set only) VOLTAGE REGUL
ページ4に含まれる内容の要旨
Relative Humidity 0 to 95%, non-condensing Storage Temperature +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius Operating +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius Temperature Line mode BTU/hr. 2160 btu/hr. (Max.) COMMUNICATIONS Network monitoring Includes 2 built-in DB9 monitoring ports (1-RS232 / 1-contact closure) port Software and cabling Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Cabling included included. S
ページ5に含まれる内容の要旨
BP240V1037C-1PH External battery pack for use with select Tripp Lite UPS Systems Qty: [optional] Rackmount/Wallmount Kits 2POSTRMKITWM Universal 2-Post Rackmount Kit (Supports 2U to 4U UPS systems and battery packs.) Qty: [optional] Shutdown Cable Kits AS400CABLE KIT Power Management Tools - UPS Communication Cable Kit for System i / AS400 / iSeries Qty: [optional] Servers SNMP Accessories ENVIROSENSE Monitors temperature, humidity and contact-closure inputs. (Requires SNMPWEBCARD or Qty: [o