Installation and Operating Instructions
Passive Infra-Red Detector Switch
Issue 3 November 2006
Model No. DX4130
Height Width Depth
130mm 85mm 145mm
130mm
85mm
THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE
General
IMPORTANT SAFETY ADVICE
The Dimplex passive infra –red detector switch has been designed to
• The installation of this product should be carried out
enable Dimplex Quartz and
ページ2に含まれる内容の要旨
Installation continued 5. Insert top screw into the wall, allowing it to protrude by approximately 3mm. 6. Hook wall box on to screw using keyhole slot provided. 7. Mark position of remaining fixings, remove box and complete fixing. 8. Fix the wall box to the wall, ensuring the drain hole is at the bottom. 9. Cable entries are made to the base of the box, using the holes provided. 10. Connect circuit wiring to terminal block. (see Fig.2.) N = Neutral to load N = Supply Neutra
ページ3に含まれる内容の要旨
Testing 1. Set the light level to maximum (clockwise), and the time on to minimum (anti-clockwise). 2. Move in and out of detection pattern checking the PIR detector switches load on and then off. Once the detection area has been set satisfactorily, adjust the time (blue knob) to the desired level. For your convenience optimum settings have been indicated. 3. If the unit does not operate, refer to the check list and fault finding list. Check List 1. Check the supply to the de