ページ1に含まれる内容の要旨 
                    
                        Revision C:
• SPECIFICATION has been corrected.
Please void OB450 REVISED EDITION-B.
INDOOR UNIT
No. OB450
REVISED EDITION-C
SERVICE MANUAL
Wireless type
Models
MSZ-A09NA MSZ-A24NA
1 1
MSZ-A09NA - MSZ-A24NA - 
MSZ-A12NA MSY-A15NA
1 1
MSZ-A12NA - MSY-A15NA - 
MSZ-A15NA MSY-A17NA
1 1
MSZ-A15NA - MSY-A17NA - 
MSZ-A17NA MSY-A24NA
1 1
MSZ-A17NA - MSY-A24NA - 
Outdoor unit service manual
MUZ-A·NA Series (OB451)
MXZ-A·NA Series (OB444)
CONTENTS
1. TECHNICAL CHANGES ··································· 2
                    
                    ページ2に含まれる内容の要旨 
                    
                        Revision A :  • PARTS LIST has been revised. (10-1.8, 10-2.8) Revision B : •  MSZ-A•NA- 1 and MSY-A•NA- 1    Remote controller has been changed. Revision C : •  SPECIFICATION has been corrected.  Powerful has been added. (Airflow , Sound level) TECHNICAL CHANGES 1 MSZ09UN  MSZ-A09NA MSH24WN  MSZ-A24NA MSZ12UN  MSZ-A12NA MS15TN  MSY-A15NA MSH15TN  MSZ-A15NA MS17TN  MSY-A17NA MSH17TN  MSZ-A17NA MS24WN  MSY-A24NA  1. Control method between indoor and outdoor has been changed.   2. Indoor fan motor 
                    
                    ページ3に含まれる内容の要旨 
                    
                        2 PART NAMES AND FUNCTIONS MSZ-A09NA    MSY-A15NA MSZ-A24NA MSZ-A12NA    MSY-A17NA MSY-A24NA MSZ-A15NA    Front panel MSZ-A17NA Air inlet Heat exchanger Panel Air cleaning filter (Anti-Allergy Enzyme  Filter, Blue bellows   type) Catechin air filter Air outlet Vertical vane Remote controller Horizontal vane Line flow fan Operation section Display section MSZ-A09NA  MSZ-A12NA  (When the front panel is opened) MSZ-A15NA    MSZ-A17NA Operation Indicator lamp MSY-A15NA MSY-A17NA Emergency operation 
                    
                    ページ4に含まれる内容の要旨 
                    
                        3 SPECIFICATION Indoor unit model  MSZ-A09NA MSZ-A12NA  External fi nish White  Power supply V, phase, Hz 208/230, 1, 60  Max.-fuse size (time delay) / Disconnect switch A 15 Min. circuit ampacity A 1.0 Fan motor F.L.A 0.76 152-229-307-338 152-240-353-388 COOL Dry (Wet)  Airfl ow (134-205-275-303) (134-215-318-349) CFM Low–Med.–High–Powerful HEAT 159-222-307-321 159-240-353-353 Moisture removal pt./h 2.3 3.2 COOL 22-33-38-41 22-34-42-44 Sound level  dB(A) Low–Med.–High–Powerful HEAT 22-33-38-39 22
                    
                    ページ5に含まれる内容の要旨 
                    
                        3-1. OPERATING RANGE (1) POWER SUPPLY Rated voltage Guaranteed Voltage (V) 208/230 V  Min.187 208 230 Max.253 Indoor unit 1 phase  60 Hz  (2) OPERATION Intake air temperature (°F) Mode Condition Indoor Outdoor DB WB DB WB Standard temperature 80 67 95 — Maximum temperature 90 73 115 — Cooling Minimum temperature 67 57 14 — Maximum humidity 78% — Standard temperature 70 60 47 43 Heating Maximum temperature 80 67 75 65 Minimum temperature 70 60 14 13 3-2. OUTLET AIR SPEED AND COVERAGE RANGE Air sp
                    
                    ページ6に含まれる内容の要旨 
                    
                        4 OUTLINES AND DIMENSIONS Unit : inch MSZ-A09NA   MSY-A15NA MSZ-A12NA   MSY-A17NA MSZ-A15NA MSZ-A17NA Conduit plate(MSZ-A•NA-      and MSY-A•NA-      are excluded.) 7/16x13/16 Oblong hole 7/16x1 Oblong hole Installation plate 2-3/16 8-7/8 8-7/8 2-3/16 hole 7/8 30-11/16 6-1/8 6-1/8 1-3/4 2-3/16 2-3/4 13-3/16 12-5/8 Indoor unit Air in Wall hole 2-9/16 3/16 8-1/4 Installation plate Liquid line   1/4 19-11/16 Gas line   3/8 16-15/16 { Insulation   1-3/8 O.D                    3/4 I.D Drain hose    5
                    
                    ページ7に含まれる内容の要旨 
                    
                        Unit : inch MSZ-A24NA MSY-A24NA Installation plate Indoor unit 3-7/8 6-13/16 42-1/16 3-7/8 16-5/16 16-5/16 6-13/16 Wall hole   3 10-1/4 3/16 43-5/16 Air in Installation plate Liquid line  1/4 19-11/16 Gas line  5/8 16-15/16 { Insulation  1-15/16 O.D   1-1/4 I.D 2-3/16 31-1/8 9-15/16 Drain hose 5/8 (Connected part O.D) Air out Insulation   1-1/8 2-5/16 3/4 Wireless remote controller 7 12-13/16 6-1/4 1-7/8 1/8 1-7/8 10-1/16 5/16 12-3/8                                                               
                    
                    ページ8に含まれる内容の要旨 
                    
                        5 WIRING DIAGRAM MSZ-A09NA   MSY-A15NA MSZ-A12NA   MSY-A17NA MSZ-A15NA MSZ-A17NA MSZ-A24NA MSY-A24NA 8                                                                                                                                                                                                                                                                                                                                                                                                              
                    
                    ページ9に含まれる内容の要旨 
                    
                        6 REFRIGERANT SYSTEM DIAGRAM Unit : inch MSZ-A09NA MSZ-A15NA   MSY-A15NA MSZ-A12NA MSZ-A17NA   MSY-A17NA Refrigerant pipe ø1/2 Refrigerant pipe ø3/8 (with heat insulator) (with heat insulator) Indoor coil Indoor coil Indoor Indoor thermistor thermistor heat heat RT12(main) RT12(main) exchanger exchanger Distributor Flared connection Flared connection Indoor coil Indoor coil  thermistor thermistor  RT13(sub) RT13(sub) Room temperature thermistor RT11 Room temperature thermistor RT11 Flared connec
                    
                    ページ10に含まれる内容の要旨 
                    
                        7 SERVICE FUNCTIONS MSZ-A09NA   MSZ-A12NA   MSZ-A15NA  MSZ-A17NA   MSZ-A24NA  MSY-A15NA   MSY-A17NA   MSY-A24NA 7-1. TIMER SHORT MODE  For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board.  The time will be shortened as follows. (Refer to 8-7.)  Set time : 1-minute  1-second  Set time : 3-minute  3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is    shortened by short circuit-of JPG and JPS.
                    
                    ページ11に含まれる内容の要旨 
                    
                        7-3. AUTO RESTART FUNCTION  When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed  are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment  power has restored after power failure. Then, the unit will restart automatically.  Operation  If the main power has been cut, the operation settings remain.  After the power is restored, the unit restarts automatically according to the 
                    
                    ページ12に含まれる内容の要旨 
                    
                          3. Troubleshooting procedure 1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality.   To make sure, check how many times the abnormality indication is flashing ON and OFF before starting service work.  2) Before servicing check that the connector and terminal are connected properly. 3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the  components for bursting a
                    
                    ページ13に含まれる内容の要旨 
                    
                        8-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (8-4.) disappears, the memorized failure details can  be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.   1. Flow chart of failure mode recall function for the indoor/outdoor unit Those figures show about MSZ-A09/12/15/17.  Ope
                    
                    ページ14に含まれる内容の要旨 
                    
                        2. Indoor unit failure mode table Left lamp of OPERATION Abnormal point  Condition Correspondence  INDICATOR lamp (Failure mode)  Not lighted Normal — — The room temperature thermistor short or  1-time fl ash every Room temperature Refer to the characteristics of the room temperature  open circuit is detected every 8 seconds dur- 0.5-second thermistor thermistor (8-7.).  ing operation.  Indoor coil  2-time fl ash The indoor coil thermistor short or open circuit Refer to the characteristics of the 
                    
                    ページ15に含まれる内容の要旨 
                    
                        8-3. INSTRUCTION OF TROUBLESHOOTING Start Indoor unit operates. Indoor unit  Indoor unit oper- OPERATION INDICATOR  Outdoor unit doesn't doesn't  receive   ates. lamp on the indoor unit is  operate normally. the signal from  Outdoor unit  fl ashing on and off. remote controller. doesn't operate. If blinking of OPERATION INDI- CATOR lamp cannot be checked,  it can be checked with failure  mode recall function. Outdoor unit Outdoor Indoor unit Indoor unit  Unit doesn't  operates only unit doesn't o
                    
                    ページ16に含まれる内容の要旨 
                    
                        8-4. TROUBLESHOOTING CHECK TABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the  power ON), the indoor fan motor turns OFF and  OPERATION INDICATOR lamp flashes. OPERATION INDICATOR Lighted Blinking    Not lighted Abnormal  No. Operation indicator lamp Symptom Condition Correspondence point Left lamp fl ashes. 0.5-second ON Mi
                    
                    ページ17に含まれる内容の要旨 
                    
                        OPERATION INDICATOR    Abnormal  No. Operation indicator lamp Symptom Condition Correspondence  point  Left lamp lights and lower lamp fl ashes. Lower lamp fl ashes. The operation mode of the each indoor unit  MXZ type Outdoor unit  is differently set to COOL (includes DRY) and • Unify the operation mode. Operation               operates but  1 HEAT at the same time, the operation mode Refer to outdoor unit service  mode indoor unit does  2.5-second OFF of the indoor unit that has operated at fi rs
                    
                    ページ18に含まれる内容の要旨 
                    
                        8-6. TROUBLESHOOTING FLOW  A  Check of indoor fan motor The indoor fan motor error has occurred, and the indoor fan doesn't operate. Turn OFF the power supply. Pay careful attention to the high voltage on the fan motor connector CN211. Turn ON the power supply, wait 5 seconds or more, and then press  EMERGENCY OPERATION switch. Measure the supply voltage as follows within 12 seconds after EMER- GENCY OPERATION switch is pressed. Is there any foreign matter that interferes  the rotation of the li
                    
                    ページ19に含まれる内容の要旨 
                    
                         B  Check of remote controller and indoor electronic control P.C. board  Check if the remote controller is exclusive for this air conditioner. Press OPERATE/STOP (ON/OFF)  button on the remote controller. Is LCD display on the remote controller  Replace the batteries. (Refer to 8-1.4.) visible? No (Not clear) Yes Remove the batteries, then set them back  and press RESET button. (Refer to 8-1.4.)  Check if the unit operates with the remote  controller. Turn ON a radio to AM and press OP- Does the
                    
                    ページ20に含まれる内容の要旨 
                    
                         C  Check of indoor electronic control P.C. board and indoor fan motor Turn OFF the power supply. Remove indoor fan motor connector CN211  and vane motor connector CN151 from the  indoor electronic control P.C. board and turn  ON the power supply.  Measure the resistance between  Short/open circuit: CN211  and  of the indoor fan motor  Replace the indoor fan motor. connector. Does the unit operate with the remote  controller? Does OPERATION INDICATOR  lamp light up by pressing EMERGENCY Yes OPER