                        INSTALLER’S & OWNER’S MANUAL
HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER
Dehumidification
The highly efficient Ultra-Aire 100V dehumidifier utilizes refrigeration 
to cool the incoming air stream below its dew point. This cooled and 
drier air is used to pre-cool the incoming air stream resulting in a 
significant increase in overall efficiency. After the pre-cooling stage, 
the processed air is reheated by passing through the condenser coil. 
The heat removed by the evaporator coil is ret
                    
                    ページ2に含まれる内容の要旨 
                    
                        TABLE OF CONTENTS Table of Contents Safety Precautions ....................................................................... 3 5.3C  On/Off Setting ........................................................ 13 1. Intended Application ................................................................ 4 5.3D  Setting Clock Time ................................................. 13 2. Specifications .......................................................................... 4 5.3E  Setting Relative Hum
                    
                    ページ3に含まれる内容の要旨 
                    
                        SAFETY PRECAUTIONS Safety Precautions Read the installation, operation and maintenance  instructions carefully before installing and operating this device.  Proper adherence to these instructions is essential to obtain  maximum benefit from your Ultra-Aire indoor air quality system. READ AND SAVE THESE INSTRUCTIONS •  The device is designed to be installed INDOORS IN A SPACE THAT  IS PROTECTED FROM RAIN AND FLOODING.  • I nstall the unit with space to access the front panel for  maintenance and 
                    
                    ページ4に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY the control wires leaving the Ultra-Aire may not be used with certain  1.  Intended Application for Ultra-Aire 100V  control panels and should be left safely disconnected with wire  For the ideal installation, draw air from the central part of the home  nuts taped onto the stripped ends. Be sure to consult the electrical  and return it to isolated areas of the home like the bedrooms, den,  schematic in this manual or on the front panel of the Ultra-Aire  utility room, or 
                    
                    ページ5に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY a separate supply duct from the Ultra-Aire to each isolated area is to 125 CFM of outside air. Large quantities of outside air will impact  recommended. DO NOT draw air directly from the kitchen, laundry, Ultra-Aire performance positively or negatively, depending upon the  or basement. All flexible ducting connected to the Ultra-Aire should difference between inside and outside air conditions. Consult the  be UL listed. factory by calling 1-800-533-7533 for recommendation
                    
                    ページ6に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY Connect a duct from outside to the 6" collar of the Ultra-Aire if you  3.4G Installation in a Structure with No Existing  wish to provide fresh make-up air. Forced Air HVAC Systems When installing the Ultra-Aire in a structure that does not have a  Crawlspace Installation: Locate a separate return for the Ultra- forced air HVAC system, a single return for the Ultra-Aire should  Aire in a central area of the structure. Duct the supply of the  be installed in central open a
                    
                    ページ7に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY dehumidification or when the ventilation timer calls for ventilation. 4.2 Ventilation Timer and Humidity Control Panel See Figure 2: The ventilation timer and humidity control panel  4.5 Ventilation Timer automatically controls both the ventilation and the humidity of  The ventilation timer controls the fan and the motorized fresh  the living space. The ventilation timer and humidity control panel  air damper. When the ventilation timer is activated, the central  contains
                    
                    ページ8に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY and the number “1” should remain in the lower right hand corner of  the display. The “1” and “OFF” signify the turn off time for the first  program. Set the turn off time using the 1…7, h, and m buttons in  the same way as described above and continue on to the second  through sixth programs. When setting the ventilation programs,  you can return to the current time display by sliding the switch in  the upper right corner of the timer to RUN. The slide switch in the  uppe
                    
                    ページ9に含まれる内容の要旨 
                    
                        ATTENTION INSTALLER WIRE THE UNIT AND CONTROL PACKAGE AS SHOWN IN THE DIAGRAM BELOW Humidity/Fan Control Panel Humidity Control D.BLU-5 YEL-2 Blower Switch GRN-6 GRN-6 PNK WHT-1 RED-3 YEL-2 Dehumidifier D.BLU-5 Control Part No. 4024155 Do not connect these leads  Ventilation Timer/ directly together or damage  Humidity Control Panel Optional to the transformer will result. Damper Humidity Control D.BLU-5 YEL-2 VIO-4 ORG GRN-6 L.BLU PNK REd-3 GRN-6 WHT-1 RED-3 GRY YEL-2 Control Part No. 4024125 D
                    
                    ページ10に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY 5.  DEH 3000 Digital Control   Installation Instructions Control Part No. 4026570 5.1 Specifications Part # (P/N) 4026570  Model: DEH 3000 Digital Control Electrical: 24 VAC Humidity Range: 10 – 95% RH Humidity Accuracy: +/- 5% Output: 3 Amps 24 VAC  Relay Capacity 5 Amps  Temp Range/Accuracy 2%  Size 4.95" wide x 4.19" high 5.2B Wiring FOR HVAC INSTALLER ONLY: WARNING: DO NOT ALLOW THE YELLOW LEAD  5.2 Installation FROM THE ULTRA-AIRE TO CONTACT THE RED OR WHITE LEADS  T
                    
                    ページ11に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY Dehumidification    Operation COM/NO COM/NC  UA Base Unit White  ON CLOSED OPEN  OFF OPEN CLOSED  Common uses (assuming standard thermostat wiring color  schemes as noted): Disengage A/C during dehumidification Redirect the yellow thermostat wire to the NC  DEH 3000 Wiring Diagram terminal. Wire the yellow wire from the A/C to the  COM (B) terminal. Engage A/C during dehumidification DMP COMP FAN Connect a wire from the “R” terminal on the the  thermostat to the “com” ter
                    
                    ページ12に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY DEHUMIDIFIER DEACTIVATES WHEN THE  motorized damper in series with these connections, or the  AIR-CONDITIONER IS RUNNING white wire must not be connected to the control. Mis-wiring  •  The common wire on the thermostat transformer may result in transformer damage. (black) needs to be wired with the yellow wire from the  After connections have been verified, this short test will  dehumidifier. confirm proper wiring. •  The Red wire on the thermostat needs to be wired with 
                    
                    ページ13に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER AND HOMEOWNER 8. V erify additional optional control operations such as fan interlock  or lockout. 9. Proceed to operation/setting section.  FOR INSTALLER & HOMEOWNER: 5.3 Operation 5.3A Display • W hen there is power to the control, the control display will  show the time, day, humidity, and temperature.  •  When the control is turned on, the setpoint, fan status,  auto/hold mode, and fresh air vent status is displayed.   • When a key is pressed the display will light. • T he
                    
                    ページ14に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY AND HOMEOWNER Operation continuously are filtration and air recirculation. The initial dead band setting (the range that the dehumidifier  “AUTO” – indicates the fan will run when the control calls for  cycles on and off) is 3%. With a setpoint of 50%, the dumidifier  dehumidification or ventilation. If the control has not called for  turns on when the reading reaches 53%. The dehumidifier  dehumidification for 3 hours, the control will automatically run  continues to rem
                    
                    ページ15に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER ONLY AND HOMEOWNER The ventilation indicator “O” will be displayed whenever the unit There are two programs available for ventilation Monday  through Friday. There are also two programs for Saturday and  is ventilating. The fan operation indicator “O” will also be lit. Sunday.  No other choice of days is available.  There are three damper operation modes, “OPEN –HOLD,”    “CLOSED – HOLD” and “PROGRAM” (denoted by “ON TIME” Each program has:  – “OFF TIME.”  Refer to section 3.8
                    
                    ページ16に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER AND HOMEOWNER 2.   Press the program enter key to toggle to the “open for” feature will not need to be used. If temperature cutout is desired,  setting.  Using the up/down “RH”  keys, change the program the setpoint by pressing the “PROGRAM ENTER”  duration that the damper will ventilate fresh air. button. Press RH until “TEMP CUTOUT”  is flashing. Use “RH”   up or “RH”  down to adjust setpoints. 3.   Press the program enter key to toggle to the “closed  for” setting.  Using t
                    
                    ページ17に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER AND HOMEOWNER 6. Maintenance 7. Service 6.1 Standard Air Filter CAUTION: Servicing the Ultra-Aire with its  The Ultra-Aire is equipped with a pleated cloth air filter. This filter  high pressure refrigerant system and high  should be checked monthly. Operating the unit with a dirty filter  voltage circuitry presents a health hazard  will reduce dehumidifier capacity and efficiency and may cause the  which could result in death, serious bodily  compressor to cycle off and on un
                    
                    ページ18に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER AND HOMEOWNER No dehumidification, compressor does not run but fan runs left in the system, it must be recovered before weighing in the new  with fan switch and ventilation timer OFF and humidity control charge. Refer to the unit nameplate for the correct charge weight  turned to ON. and refrigerant type. 1.Defective compressor run capacitor (Sec. 5.6). 7.5 Fan Replacement 2.Loose connection in compressor circuit (See Fig. 4). The centrifugal fan has a PSC motor and internal t
                    
                    ページ19に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER AND HOMEOWNER 6.  Compressor terminal C and overload terminal 1: was not rotating. Contaminants are therefore largely confined  No continuity indicates a defective overload lead. to the compressor housing. A single installation of liquid and  7.  Overload terminals 1 and 3: suction line filter/driers will probably clean up the system. If  If there is no continuity, the overload may be tripped. Wait sludge is evident in the discharge line, it will likely be found in  10 minutes
                    
                    ページ20に含まれる内容の要旨 
                    
                        FOR HVAC INSTALLER AND HOMEOWNER point. It opens when the RH drops 4 to 6% below the set point. If the  7.9 Electric Ventilation Damper Ultra-Aire does not run, try turning the humidity control clockwise  The electric ventilation damper is controlled by the ventilation timer.  until it reaches the stop and the knob pointer points at “ON”. The damper will open when the ventilation timer is activated to  allow fresh air into the structure through the 6" diameter fresh air  The Ultra-Aire is equipp