ページ1に含まれる内容の要旨 
                    
                        AC Power
For Business-Critical Continuity™
® ™ 
Liebert GXT3 UPS 230V 700VA-3000VA
User Manual                                                                                                                                                                                                                                                                                                                                                                                                                      
                    
                    ページ2に含まれる内容の要旨 
                    
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    ページ3に含まれる内容の要旨 
                    
                        TABLE OF CONTENTS IMPORTANT SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.0 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
                    
                    ページ4に含まれる内容の要旨 
                    
                        4.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 4.1 Startup Checklist for the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 4.2 Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 4.3 Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
                    
                    ページ5に含まれる内容の要旨 
                    
                        FIGURES Figure 1 Liebert GXT3-700RT230 - GXT3-3000RT230 UPS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 2 Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA models. . . . . . . . . . . . 5 Figure 3 Rear panel components, Liebert GXT3 230V 2000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 4 Rear panel components, Liebert GXT3 230V 3000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 5
                    
                    ページ6に含まれる内容の要旨 
                    
                        iv                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  
                    
                    ページ7に含まれる内容の要旨 
                    
                        IMPORTANT SAFETY PRECAUTIONS WARNING ! Observe all cautions and warnings in this manual. Failure to do so may result in serious  injury or death. Refer all UPS and battery service to properly trained and qualified service personnel. Do not  attempt to service this product yourself. Opening or removing the cover may expose you to lethal voltages within this unit even when  it is apparently not operating and the input wiring is disconnected from the electrical source. Never work alone. SAVE THESE 
                    
                    ページ8に含まれる内容の要旨 
                    
                        Battery Safety CAUTION ! Do not dispose of the battery in a fire. The battery may explode. Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and  eyes. If electrolyte comes into contact with the skin, wash the affected area immediately with  plenty of clean water and get medical attention.  CAUTION ! A battery can present a risk of electrical shock and high short-circuit current. The following  precautions should be observed when working on batteries: • Remo
                    
                    ページ9に含まれる内容の要旨 
                    
                        GLOSSARY OF SYMBOLS Risk of electrical shock Indicates caution followed by important instructions ! AC input AC output Requests the user to consult the manual i - + Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 R Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON/Alarm Silence/Battery Test OFF/Bypass WEEE ® ™ 3Liebert GXT3                                                                                                                         
                    
                    ページ10に含まれる内容の要旨 
                    
                        Product Description 1.0 PRODUCT DESCRIPTION The Liebert GXT3 is a compact, online uninterruptible power system (UPS) that continuously  conditions and regulates its output voltage. The Liebert GXT3 is designed to supply microcomputers  and other sensitive electronic equipment with clean sine wave input power, 700VA to 3000VA at  230V. Upon generation, AC power is clean and stable. However, during transmission and distribution it is  subject to voltage sags, spikes and complete failure that may i
                    
                    ページ11に含まれる内容の要旨 
                    
                        Product Description 1.3 Appearance and Components 1.3.1 Appearance The Liebert GXT3 rack/tower models in various power ratings have the same general appearance,  controls and features (see Figure 1). The various rack/tower models differ largely in the type of  receptacles each has. Figure 1 Liebert GXT3-700RT230 - GXT3-3000RT230 UPS  Ventilation Slots Operation and Display Panel 1.3.2 Rear Panel Features The rear panel of the Liebert GXT3 has these features: •USB port • Cooling fan • C19 output 
                    
                    ページ12に含まれる内容の要旨 
                    
                        Product Description Figure 4 Rear panel components, Liebert GXT3 230V 3000VA models Output Circuit   Input Circuit  C20 Input Receptacle Liebert IntelliSlot Port USB Port Breakers Breaker External Battery  C13 Output  Terminal Block C19 Output  Cooling Fan Connector Receptacles Communication Receptacle 1.4 Major Components The operating principle of the UPS is shown in Figure 5. Figure 5 Operating principle diagram Input Output Dynamic Bypass  TVSS & EMI/ Rectifier/ L1 Inverter L1 RFI Filters PF
                    
                    ページ13に含まれる内容の要旨 
                    
                        Product Description Rectifier/Power Factor Correction (PFC) Circuit In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts mains  power to regulated DC power for use by the inverter while ensuring that the wave shape of the input  current used by the UPS is near ideal. Extracting this sine wave input current achieves two  objectives: • Efficient power use by the UPS • Reduced reflected harmonics This results in cleaner power being available to other devi
                    
                    ページ14に含まれる内容の要旨 
                    
                        Product Description 1.5.2 Manual Bypass Mode Manual Bypass Mode occurs when the Standby/Manual Bypass button is pressed and held for about  2 seconds while the Liebert GXT3 is in Mains (AC) Mode. Bypass operation is indicated by an audible  alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 -  Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to  the connected load. NOTICE Turning Off the UPS in Bypass Mode w
                    
                    ページ15に含まれる内容の要旨 
                    
                        Installation 2.0 INSTALLATION 2.1 Unpacking and Inspection Unpack the UPS and conduct the following checks:  • Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and  ® your local dealer or Emerson representative immediately. • Check the accessories against the delivery list. If there is any discrepancy, contact your local  dealer or your Emerson representative immediately. 2.2 What’s Included With GXT3 UPS • Terminal Block Communication terminals • Co
                    
                    ページ16に含まれる内容の要旨 
                    
                        Installation 2.4 Mechanical Installation The Liebert GXT3 may be installed as a tower or in a rack, depending on space and use  considerations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery  cabinets. NOTE When installing the UPS or making input and output connections, comply with all relevant  safety codes and standards. 2.4.1 Tower Installation To install the Liebert GXT3 as a tower: 1. Take out support bases from the accessories (see Figure 6). Figure 6 Suppo
                    
                    ページ17に含まれる内容の要旨 
                    
                        Installation Figure 8 Rotate the operation and display panel Operation and Display Panel  Rotated Clockwise 90 Degrees c. Pull the logo on the front plastic bezel cover, rotate it 90 degrees clockwise and snap it back  into position. The rotated front plastic bezel cover is shown in Figure 9. d. Replace the front plastic bezel cover on the Liebert GXT3. At this point, the UPS operation  and display panel and logo have been rotated 90 degrees clockwise, which provides upright  viewing for users. 
                    
                    ページ18に含まれる内容の要旨 
                    
                        Installation 2.4.2 Rack Installation NOTE • When the Liebert GXT3 is installed in a rack, the UPS must be supported by a shelf,  brackets, or slide rails on each side. The factory-supplied rack-mount ears cannot support  the weight of the UPS. They are used to move the UPS into and out of the rack and attach the  UPS to the rack. • Mounting hardware and slide rails are sold separately. Contact your local dealer or  ® Emerson representative for these options and any assistance. To install a Liebe
                    
                    ページ19に含まれる内容の要旨 
                    
                        Installation Figure 11 Installing rear member of each bracket assembly Vertical pole M5 screw (4 pcs) Rear member Front member 5. Extend bracket assembly by sliding the front member forward until it touches the rack’s front  vertical rails (adjustable length: 18 inches to 32 inches). 6. Use two M5 screws to attach each front member onto the front vertical rails through the  installation holes. Make sure that the bracket assemblies are at the same mounting height on all  four of the rack’s vertic
                    
                    ページ20に含まれる内容の要旨 
                    
                        Installation 8. Fasten inner members pulled from the bracket assemblies in Step 2 to the UPS on both sides with  eight M4 screws provided in this kit. Make sure that the retaining latch is near the rear of the  UPS, as shown in Figure 14. Figure 14 Installing inner members Liebert GXT3 UPS Inner Member Retaining Latch M4 screw, 8 pieces 9. Use M4 screws to install ears of accessories on both sides of the UPS, as shown in Figure 15. Figure 15 Installing rack-mount ears Liebert GXT3 UPS Ear, 2piec