                        Instructions
Masonry Firebox
Models MM33, MM39, MM44, MM49 and MM63
IF FIRePlaCe Is T o Be InsT alled dIReCTl Y on anY CoMBUsTIBle Ma TeRIal, a MeTal Base 
Is ReQUIRed.
sa Ve THIs BooK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, 
it also contains information that will enable you to obtain replacement parts or accessory items 
when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning firepla
                    
                    ページ2に含まれる内容の要旨 
                    
                        table oF contents Safety ......................................................................2 Fireplace Installation..............................................22 Specifications ..........................................................4 Firebrick Installation...............................................29 Product Overview ....................................................6 Operation and Maintenance ..................................30 Pre-Installation Preperation ......................
                    
                    ページ3に含まれる内容の要旨 
                    
                        saFety Continued do noT Use oR sToRe GasolIne oR oTHeR  WaRnInG : THIs FIRePlaCe Has noT Been  FlaMMaBle lIQUIds oR Gases In oR neaR  TesTed FoR Use WITH an UnVenTed Gas  THe FIRePlaCe! loG seT. T o RedUCe THe RIsK oF FIRe oR  InJURY, do noT InsT all an UnVenTed Gas  aTTenTIon :  A fire or an explosion could occur  loG seT InT o FIRePlaCe. causing property damage, injury or loss of life if you  do not follow the information in this manual! WaRnInG : THIs FIRePlaCe Has Been  TesTed FoR Use WITH o
                    
                    ページ4に含まれる内容の要旨 
                    
                        speciFications 37" 23 ¼" 10" 21" 28 1 28" /8" 23" 33" Ø 12" 18 ½" SECTION A-A Ø4" OUTSIDE AIR ACCESS CAN BE INSTALLED 22" ON THE LEFT SIDE ALSO 4 ½" 54 ⅝" 30 ½" 24 ½" A A Figure 1: MM33 Fireplace Overall Dimensions 53 ¼" 22 ¼" 11" 28" 23 ⅛" 62 ⅞" 2X Ø 12" 66 ⅞" SECTION A-A 45 ⅝" 23 ½" 4 ½" 4 ⅛" OUTSIDE  COMBUSTION AIR  ACCESS HOLE  72 ⅞" 40 ¾" 32 ⅞" 7 ⅜" 21" A A Figure 2: MM63 Fireplace Overall Dimensions www.fmiproducts.com 4 125160-01A                                                           
                    
                    ページ5に含まれる内容の要旨 
                    
                        speciFications Continued E 4" 11" 21" 10" 28" 23" C 4 ¼" Ø F A/2 B A SECTION H-H D 4 ⅜" 63 ½" 40 ⅝" 32 ⅞" H H 7 ⅜" Fireplace Overall Dimensions Model a B C d e F MM39 43″ 39″ 29¼″ 27¾″ 38¾″ Ø12″ MM44 48″ 44″ 34¼″ 32¾″ 43¾″ Ø12″ MM49 53″ 49″ 39¼” 37¾″ 48¾″ Ø12″ Figure 3: MM39/44/49 Fireplace Overall Dimensions www.fmiproducts.com 125160-01A 5                                                                                                                                                             
                    
                    ページ6に含まれる内容の要旨 
                    
                        product overview InTRodUCTIon We extend a warm welcome from all of us at FMI Internal Wall PRODUCTS, LLC, proud manufacturers of the Grand  Corner  Installation Meridian Fireplaces. Thank you for choosing FMI. Installation You may have thought long and hard before you  chose the fireplace which would grace your home.  Rest assured that every component of the Fireplace  has been tested to ensure long-term durability. Flush Full  PRodUCT oVeRVIeW Installation Projection  The Grand Meridian Firepla
                    
                    ページ7に含まれる内容の要旨 
                    
                        pre-installation preparation seleCTInG loCa TIon  WaRnInG: do not pack required air spaces  To determine the safest and most efficient location  with insulation or other materials. for the fireplace, you must take into consideration the  following guidelines: Minimum/Maximum Chimney Height for   1. The location must allow for proper clearances (see  Residential Installation Figures 6 and 7). Minimum height of chimney, measured from base of  2. Consider a location where fireplace will not be af- 
                    
                    ページ8に含まれる内容の要旨 
                    
                        pre-installation preparation  Continued  WaRnInG: Failure to position the parts in accordance with these diagrams or failure to use only  parts specifically approved with this appliance may result in property damage or personal injury. MAINTAIN THE 2" CLEARANCE  TO COMBUSTIBLES ABOVE  THE DOME. DO NOT ATTACH  COMBUSTIBLE MATERIALS  ON TOP OF THE DOME. 18" MIN* H** 8" MIN* NON-COMBUSTIBLE  FACING (NOT SUPPLIED). Condition dim. H** with 6" platform 10" with 8" platform 12" without platform 3" * MI
                    
                    ページ9に含まれる内容の要旨 
                    
                        pre-installation preparation Continued Model A MM33 70 ½" MM39 82 ½" MM44 84 ¼" MM49 86" MM63 91" 2” MIN 2” MIN a NON-COMBUSTIBLE FACING MATERIAL NON-COMBUSTIBLE HEARTH EXTENSION *   8”    8”  MIN MIN * Not provided as part of fireplace  1’-0” 1’-0” or sold by FMI PRODUCTS, LLC. MIN MIN * Not provided as part of fireplace Figure 8: Corner Installation for Combustible Floor Systems     2” MIN. FROM REAR AND  SIDES TO COMBUSTIBLES NON-COMBUSTIBLE FACING MATERIAL     HEARTH EXTENSION   8”  8” MIN M
                    
                    ページ10に含まれる内容の要旨 
                    
                        pre-installation preparation Continued aTTenTIon : You will note that there will be a gap  ManTel and ManTel sHelF CleaRanCes between the fireplace front and the extension of the  As with any radiant heat fireplace, the Grand Merid- non-combustible hearth material. Be certain that  ian fireplaces must comply with building code safety  you seal this with non-combustible material. clearances, per units that have openings of 6 sq. ft.  or greater. For Mantel clearances see Figure 5, page These Gran
                    
                    ページ11に含まれる内容の要旨 
                    
                        pre-installation preparation Continued 2” AIRSPACE  CLEARANCE TO  COMBUSTIBLES  ON REAR AND  SIDES OF UNIT. Figure 11: Non Combustible Floor Figure 12: Combustible Floor www.fmiproducts.com 11 125160-01A                                                                                                                                                                                                                                                                                                         
                    
                    ページ12に含まれる内容の要旨 
                    
                        venting installation Secure to Collars with Metal Tape, Screws  oPTIonal oUTsIde aIR KIT (Model MM4aK) or Straps (Min. of 1/4" x 20" in size) The Grand Meridian Fireplace needs enough re- Air Inlet  placement air to function properly and some local  Location  building codes may require outside combustion air  Must  to be provided. If no replacement air is provided,  Allow For  improper flue drafting may occur, creating negative  Bushes  pressure whereby smoke may enter the home, es- or Snow peci
                    
                    ページ13に含まれる内容の要旨 
                    
                        venting installation Continued been built at the correct heights;  system drafts  lIneal GaIn caused by faulty mechanical systems; adverse  PaRT no. desCRIPTIon GaIn weather conditions or any other environmental  MM33 Fireplace 54 ⅝" situations over which the manufacturer has no  control. MM39 Fireplace 63 ½” 5) Inspect all fireplace & chimney components for  MM44/49 evidence of damage prior to starting installation.  Consult your local distributor for replacement  MM63 Fireplace 73” parts if ne
                    
                    ページ14に含まれる内容の要旨 
                    
                        venting installation Continued asseMBl Y and InsT alla TIon oF doUBle  Wall CHIMneY sYsTeM Each double wall chimney section consists of a gal- vanized outer pipe, a stainless steel inner flue pipe  Screws and a wire spacer. The pipe sections must be as- B sembled independently as the chimney is installed.  When connecting chimney directly to the fireplace,  the inner flue pipe section must be installed first  with the lanced side up. The outer pipe section can  then be installed over the flue pi
                    
                    ページ15に含まれる内容の要旨 
                    
                        venting installation Continued Return Return PeneTRa TInG RooF Elbow Elbow To maintain a 2" clearance to the pipe on a roof with  Return Elbow Elbow a pitch, a rectangular opening must be cut. Elbow 6' Max. 6' Max. 1. Determine center point through which pipe will  Ceiling Support  Return Return 6' Max. Pipe 12S-12DM Elbow penetrate roof. Elbow 2. Determine center point of roof. Pitch is distance  6' Max. Elbow Elbow the roof drops over a given span, usually 12". A 6/12  6' Max. 6' Max. pitch me
                    
                    ページ16に含まれる内容の要旨 
                    
                        venting installation Continued Flas HInG Ins Talla TIon ( V6F-10dM o R  TeRMIna TIons/sP aRK aRResT oR V12F-10dM) The fireplace system must be terminated with the  Determine the flashing to be used with the roof open- listed round top or chase terminations. In any case,  ing chart. Slide flashing over pipe until base is flat  refer to the installation instructions supplied with the  against roof. Replace as many shingles as needed termination. to cover exposed area and flashing base. Secure in  
                    
                    ページ17に含まれる内容の要旨 
                    
                        venting installation Continued FInIsHInG FIRePlaCe Combustible materials, such as wallboard, gypsum  board, sheet rock, drywall, plywood, etc. may not  make direct contact with sides and top around the fire- place face. See clearance requirements in Figures 8  18"  and 9 on page 9. It is important that combustible ma- Min. terials do not overlap the face itself. Brick, glass, tile or  Typ. other noncombustible materials may overlap the front  face provided they do not obstruct essential openings
                    
                    ページ18に含まれる内容の要旨 
                    
                        2x FlooR JoIsT 2x FlooR JoIsT supporting Foor sy l stem installation It is the ultimate responsibility of the installer to en- For floors supported by I-Joists, the method of an- sure that proper concrete slab supports are used. chorage is illustrated in Figures 27 and 28, page 19.  Figure 31, page 20 illustrates the general arrange-  Wa RnInG to the licensed design professional  ment of anchorage to floor framing. and/or building contractor: It is your responsibility  It is important to take in
                    
                    ページ19に含まれる内容の要旨 
                    
                        supporting Foor sy l stems installation Continued anchor  Brackets I-Joist  Anchoring  I-Joist Anchoring  Bottom  Top View View simpson  example only strong-Tie  a-35 or  equivalent Example Only Figure 27 - Floor Joist Installation Figure 28 - Floor Joist Installation WeIGHT deTeRMIna TIon The following are dead load weight estimates for the Grand Meridian Fireplace. Table I Fireplace Model MM33 MM39 MM44 MM49 MM63 Fireplace Weight 835 lbs. 1,194 lbs. 1,250 lbs. 1,359 lbs. 1,704 lbs. Mortar, Reb
                    
                    ページ20に含まれる内容の要旨 
                    
                        supporting Foor sy l stems installation Continued 4" F a Model a MM33 32 ¾" 10" MM39 38 ¾" MM44 43 ¾" MM49 48 ¾" MM63 62 ¾" Figure 29 - Anchorage Dimensions Figure 30 - Hardware   exaMPle onl Y 2” min  Fireplace  clearance outline 10” seCTIon VIeW RoTaTed 90CW Figure 31 - Typical Anchorage Layout combustible Foor l installation 8" MeTal Base (MMB63) eMBeR PRoTeCT oR sTRIPs: The Metal Base (MMB63) ensures the minimum Ember protector strips (included with Metal Base Kit)  8" clearance above combus