ページ1に含まれる内容の要旨 
                    
                        DO NOT
DISCARD
Owner’s Manual
Installation and Operation
Models:
RHW-485, RHW-485H
Woodburning Fireplace
CAUTION
DO NOT DISCARD THIS MANUAL
• Read, understand • Leave this manual with 
• Important operating 
and follow these party responsible for 
and maintenance 
instructions for safe use and operation.
instructions included.
installation and 
operation.
WARNING
WARNING
HOT! DO NOT TOUCH. 
If the information in these instruc-
SEVERE BURNS MAY RESULT.
tions is not followed exactly, a 
CLOTHING 
                    
                    ページ2に含まれる内容の要旨 
                    
                        Read this manual before installing or operating this fi replace. Please retain this owner’s manual for future reference. Congratulations! Congratulations on selecting a Heat & Glo wood burning fi re- The information contained in this owner’s manual unless noted  place. The Heat & Glo fi replace you have selected is designed otherwise, applies to all models and gas control systems. to provide the utmost in safety, reliability and effi ciency. Your new Heat & Glo wood burning fi replace will give you  
                    
                    ページ3に含まれる内容の要旨 
                    
                        Table of Contents 1 Listing and Code Approvals  4 8 Finishing  25 A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . 4 A. Hearth Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 B. Finishing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 2 Getting Started  5 C. Mantel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 A. Design and Installation Considerations . . . . . . . . . . . . 5 D. Sidewalls/Surround
                    
                    ページ4に含まれる内容の要旨 
                    
                        Listing and Code Approvals  1 1   A. Appliance Certifi cation WARNING This fi replace system has been tested and listed in accor- dance with UL 127 and ULC-S610 standards by Underwrit- Improper installation, adjustment, alteration, service  ers Laboratories Inc. for installation and operation in the  or maintenance can cause injury or property damage.  United States and Canada. Refer to the owner’s information manual provided with  this fi replace. For assistance or additional information  This fi r
                    
                    ページ5に含まれる内容の要旨 
                    
                        Getting Started  2 2   A. Design and Installation Considerations CAUTION WARNING Check building codes prior to installation. Asphyxiation Risk • Installation MUST comply with local, regional,  Negative pressure can cause spillage of  state and national codes and regulations. combustion fumes and soot. Fire needs to draft  • Consult insurance carrier, local building inspector,  properly for safe operation. fi re offi cials or authorities having jurisdiction about  restrictions, installation inspect
                    
                    ページ6に含まれる内容の要旨 
                    
                        Location of the fi replace and chimney will affect performance.  As shown in Figure 2.1 the chimney should: • Be installed through the warm airspace enclosed by the  building envelope. This helps to produce more draft,  especially during lighting and die-down of the fi re. • Penetrate the highest part of the roof. This minimizes the  effects of wind turbulence. • Be located away from trees, adjacent structures, uneven  roof lines and other obstructions. Offsets can restrict draft so their use shou
                    
                    ページ7に含まれる内容の要旨 
                    
                        C. Typical Fireplace System The Heat & Glo fi replace system consists of the following: • Fireplace/integral grate/refractory/outside air system • Chimney termination cap • Chimney system • Hearth extension Optional components include: • Glass doors • Chimney air kit Additional lateral Termination cap support for chimney above roof (or enclosed in chase) if needed Non-combustible roof flashing maintains Storm Collar minimum clearance around chimney Chimney penetrates roof preferably without affec
                    
                    ページ8に含まれる内容の要旨 
                    
                        D. Tools and Supplies Needed E. Inspect Fireplace and Components Before beginning the installation be sure the following tools  WARNING and building supplies are available: Fire Risk Reciprocating saw Framing material Explosion Risk Pliers High temp caulking material Inspect fireplace and components for  damage. Damaged parts may impair safe  Hammer Gloves operation. Phillips screwdriver Framing square • Do NOT install damaged components. Flat blade screwdriver Electric drill and bits • Do NOT i
                    
                    ページ9に含まれる内容の要旨 
                    
                        Framing and Clearances  3 3  WARNING Note: • Illustrations and photos refl ect typical installations  Fire Risk and are FOR DESIGN PURPOSES ONLY. Provide adequate clearances. • Illustrations/diagrams are not drawn to scale. • Around air openings • Actual installation/appearance may vary due to  • To combustibles individual design preference. • For service access. • Hearth & Home Technologies reserves the right to  Locate fi replace away from traffi c areas. alter its products. Locating the fi replac
                    
                    ページ10に含まれる内容の要旨 
                    
                        3/4 in. (19 mm) to back of appliance B. Clearances WARNING Fire Risk • Comply with all minimum clearances to  combustibles as specifi ed. Failure to comply may cause  fi re. Storm Collar Roof Flashing 2 in. (51 mm) min.  2 in. min. Attic  (51 mm) Insulation Shield (attic) Ceiling Firestop (ceiling) 2 in. (51 mm) min.  2 in. (51 mm) min. 2 in. (51 mm) min.  Ceiling Firestop Offset/Return with  hanger straps (ceiling) 2 in. (51 mm) min.  2 in. (51 mm) min.  Must have 2 in. (51 mm) minimum clearance 
                    
                    ページ11に含まれる内容の要旨 
                    
                        C. Sidewalls/Surrounds Adjacent combustible side walls must be located a minimum of 12 in. (305 mm) from the fi replace opening. See Figure  3.3. If you are using a decorative surround constructed of combustible material, it must be located within the shaded area  defi ned in Figure 3.3. Short stub walls are also acceptable if they are contained within the shaded area. 4 in. (102 mm) 14-3/8 in. Flush Brick (365 mm) 9-3/4 in. Front Front (248 mm) A 50 deg. B 39 deg. 12 in. 12 in. (305 mm) (305 mm) 
                    
                    ページ12に含まれる内容の要旨 
                    
                        Gas line holes and other openings should be caulked with  E. Construct the Chase high temperature caulk or stuffed with unfaced fi berglass in- A chase is a vertical boxlike structure built to enclose the  sulation. If the fi replace is being installed on a cement slab,  fi replace and/or its vent system. Vertical chimneys that run  we recommend that in cold climates, a sheet of plywood or  on the outside of a building may be, but are not required to  other raised platform be placed underneath to p
                    
                    ページ13に含まれる内容の要旨 
                    
                        Installation of Fireplace  4 4   WARNING CAUTION Fire Risk Sharp Edges Asphyxiation Risk • Wear protective gloves and safety glasses  Do not draw outside combustion air from: during installation. • Wall, fl oor or ceiling cavity. • Enclosed space such as an attic or  garage. • Close proximity to exhaust vents or  A. Install the Outside Air Kit chimneys. Using an outside air kit is highly recommended to minimize  Fumes or odor may result. the effects of negative pressure within the structure. We  
                    
                    ページ14に含まれる内容の要旨 
                    
                        Handle left - open Handle right - closed Attic insulation shield may be used to keep 3 ft min. from top of insulation away from Figure 4.4 Locating the Outside Air Control uppermost chimney chimney.  section to air inlet. Ceilng firestop on floor of attic. Figure 4.2 Outside Air Inlet Locations NO NO Garage or NO Outlet blocked by combustible snow, leaves, etc. liquids storage Attic space NO Outlet placed higher than 3 ft below the termination cap YES Factory-built Clear area  fireplace outside 
                    
                    ページ15に含まれる内容の要旨 
                    
                        B. Secure the Fireplace • Position the Fireplace This fi replace may be placed on either a combustible or  noncombustible continuous fl at surface. Follow the in- structions for framing in Section 3.D. Slide the fi replace  into position. Be sure to provide the minimum air clear- ance at the sides and back of the fi replace assembly.  See Section 3.B. WARNING Fire Risk! • Prevent contact with sagging, loose  insulation. • Do NOT install against vapor barriers or 1 in. (25 mm) overlap exposed insulat
                    
                    ページ16に含まれる内容の要旨 
                    
                        Chimney Assembly  5 5   Termination Cap Chimney must extend beyond combustible roof structure Additional support for Maintain minimum tall chimneys height of chimney above roof Storm Collar Install roof flashing Maintain minimum according to minimum clearances to  requirements combustibles as specified Offsets/returns may not exceed Support straps for offsets/ 30° from vertical returns must be secured to adequate framing Lock chimney sections together firmly to resist movement Ceiling firestops 
                    
                    ページ17に含まれる内容の要旨 
                    
                        A. Chimney Requirements To determine the chimney components needed to complete  Vertical distances are measured from the base of the fi re- your particular installation, follow the steps below: place as shown in Figure 5.2. • Determine the total vertical height of the fireplace  • Minimum overall straight height 16.5 ft (5.03 m) installation. This dimension is measured from the base of  the fi replace assembly to the point where the smoke exits  • Minimum height with offset/return 16.5 ft (5.03 m)
                    
                    ページ18に含まれる内容の要旨 
                    
                        B. Using Offsets/Returns To bypass any overhead obstructions, the chimney may be  • Measure how far the chimney needs to be shifted to enable  offset using a 15-deg (SL315) or 30-deg (SL330) offset/re- it to avoid the overhead obstacle. See Figure 5.3. Use  turn.  dimension “A” to determine chimney section required to  achieve the needed shift. An offset and return may be attached together or a chimney  • After determining the offset dimension, refer to Table 5.2  section(s) may be used between 
                    
                    ページ19に含まれる内容の要旨 
                    
                        C. Assemble the Chimney Sections Note: The ceiling fi restop MUST be nailed to the bottom  Attach either a straight chimney section or an offset to the of the ceiling joists EXCEPT when the space above is  top of the fi replace (depending on your installation require- uninsulated and the attic insulation shield is not being used  ment). Chimney sections are locked together by pushing (see Figure 5.5). When the attic insulation shield is used  downward until the top section meets the stop bead on t
                    
                    ページ20に含まれる内容の要旨 
                    
                        E. Install the Attic Insulation Shield An insulation shield must be installed when there is a pos- Tabs sibility of insulation coming into contact with the factory built  chimney system. 14-1/2 in. (368 mm) Attic  • Bend the tabs at the top of the attic insulation shield inward.  24 in. Insulation (610 mm) This will help keep the chimney section centered in the  Insulation Shield shield. Ceiling Firestop • Position the shield over the vertical chimney section where  it penetrates a ceiling fi res