ページ1に含まれる内容の要旨 
                    
                         
 
 
 
BroadBand Conversion Kit 
 
Additional Generator  
 
Status Monitoring
 
  
User’s Manual
 
 
 
                         990-1217  07/02                                                                                                                                                                                                                                                                                                                                                                    
                    
                    ページ2に含まれる内容の要旨 
                    
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    ページ3に含まれる内容の要旨 
                    
                            Chapter 1 General Information  The Conversion Kit is used to provide additional status monitoring capabilities for the Generac- Bowman generator.  Safety  This Safety Guide contains important instructions that should be followed during installation and  maintenance of the APC equipment and batteries.  It is intended for APC customers who setup,  install, relocate, or maintain APC equipment. Changes and modifications to this unit not expressly  approved by APC could void the warranty.  Instal
                    
                    ページ4に含まれる内容の要旨 
                    
                            Chapter 2 Installation and Maintenance  Only trained service personnel should install and maintain the Power Supply.  Unpacking  The packaging is recyclable; save it for reuse or dispose of it properly.  Check the package contents. The package contains the following:  Quantity Description  1 Relay, 12VDC  2 Butt Splice  1 Long Wire Harness   1 Short Wire Harness   2                                                                                                                                
                    
                    ページ5に含まれる内容の要旨 
                    
                            Power Shutdown Procedure  The generator power supply must be shutdown prior to installing the Conversion Kit.  1. Ensure that the CTEG4M Enclosure is NOT running on generator power.  2. Disconnect the cable from the negative (-) battery terminal in the generator enclosure.  3. Switch the battery circuit breaker to the OFF position.  4. Switch the utility circuit breaker to the OFF position.  Conversion Kit Installation  1. Open the generator enclosure.  2. Locate the gas solenoid valve and p
                    
                    ページ6に含まれる内容の要旨 
                    
                              4. Route the new long harness along the outer edges of the enclosures following the path of the  original wiring as closely as possible. Use tie-wraps when necessary.  5. Attach the new long harness to the transponder in the CTEG4M Enclosure. See figure below for  details.  Rear View CTEG4M Enclosure  Utility Meter  XP7 connector  for transponder  Existing Wiring  harness for  Generator Control  Transponder Ground Bar      New long harness  B:  Attach the wire A:  Cut the original      pre
                    
                    ページ7に含まれる内容の要旨 
                    
                            Chapter 3 Service, Contact and Warranty Information  Service  APC makes every effort to ensure parts and equipment arrive in working condition. Occasionally, it  may be necessary to return parts or equipment that are not in working condition.  If the unit requires service do not return it to the dealer. Instead, follow these steps:  1. Contact APC Customer Service through the APC web site, www.apc.com/support.   Note the product model number, the serial number, and the date purchased. If yo
                    
                    ページ8に含まれる内容の要旨 
                    
                            Limited Warranty  American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of  two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole  option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization  (RMA) number from customer support. Products must be returned with transportation charges prepaid and must