                        Table of Contents Section 1: Warranty .......................................................................................................................................1      1.0 Warranty.......................................................................................................................................................... 1 Section 2:  Transmitter Overview ...................................................................................................................2  
                    
                    ページ3に含まれる内容の要旨 
                    
                        Table of Contents Section 8: Transmitter Calibration and Troubleshooting................................................................................28      8.0 Calibration ..................................................................................................................................................... 28      8.1 Troubleshooting ............................................................................................................................................ 28   
                    
                    ページ4に含まれる内容の要旨 
                    
                        Section Warranty 1 1.0  Warranty All Magtech products are warranted against defects  All Magtech gages and transmitters should  in materials and workmanship for a period of no  be unpacked and thoroughly inspected upon  less than one year from the date of shipment.  The  receipt.  Gages are shipped FOB factory and  level gage chamber and process connections are  are fully protected against damage or loss  guaranteed for the life of the tank or vessel to  during shipment.  Any claims for parts  w
                    
                    ページ5に含まれる内容の要旨 
                    
                        Section Transmitter Overview 2 2.0 General Description BBBB = The overall probe length of the instrument. The LTM-Series are 2-wire electronic field     Note:  THIS IS NOT THE MEASURING RANGE. instruments, suitable for installation in hazardous  and non-hazardous locations.  Testing and XXXX = The measuring range of the instrument.   certification has been obtained from different The 0 and 100% (4/20mA) output range. agencies for installation in such areas.  This  YYYY = The end user specified t
                    
                    ページ6に含まれる内容の要旨 
                    
                        2.3 Gage Mounted Transmitter 2.4 Standalone Transmitter The LTM-Series may be strapped to the outside of When a magnetic level gage is not present, the LTM the Magtech LG series magnetic level gage.  In such can be inserted into the tank/vessel with its own  an installation, it is used as an accessory transmitter float mounted around the sensor tube. for the visual level gage.  The same float used to  activate the magnetic gage is also used to activate The depictions below show the standalone ve
                    
                    ページ7に含まれる内容の要旨 
                    
                        A stilling well may be used along with the Optional Features that are available with the     transmitter inside the tank. Stilling-well is a pipe LTM-350 but NOT the LTM-250 are: external to the sensor probe and float encasing the  1. HART Protocol, which enables: entire assembly protecting it from surface agitation  or from physical damage due to the length of the  a. A second digital output proportional to  sensor probe.  A depiction of a transmitter with a  an interface level (requires a seco
                    
                    ページ8に含まれる内容の要旨 
                    
                        Section Transmitter Description 3 3.0 Detailed Description  In a brief description, the magnetostrictive principle  The LTM-Series is an assembly of two major consists of a wire extruded and heat treated under  components: carefully chosen conditions to retain desired  magnetic properties, which is pulsed by a circuit  The Sensor Tube Assembly:  This is a 5/8” diameter with a relatively high current pulse.  The high  stainless steel probe, sealed on one end, with the current pulse produces a cir
                    
                    ページ9に含まれる内容の要旨 
                    
                        A high-speed microcontroller is utilized in the  design to process and calculate the elapsed time  LTM-350, via HART protocol only. measurement.  Accurate crystals are used for the  time based to resolve sub-microsecond timing  increments.  The binary number, equivalent to the  2. Primary Level and Interface Level – A second  microseconds of the echo travel time is used to  float may be added below the first, and the  calculate the distance of the float and a  second output will be calibrated au
                    
                    ページ10に含まれる内容の要旨 
                    
                        Section Installation 4 4.0 Gage Mount Installation The LTM-Series can be mounted to the side of a transmitters, can be removed to allow the float to  Magtech LG series level gage using special mounting slide off the sensor tube. brackets and stainless steel hose clamps.  When  mounting the transmitter to an LG series gage the  4.2 General Installation Guidelines active sensor region of the probe should fall within  the centerline of the process connections on the  The basic steps to installing t
                    
                    ページ11に含まれる内容の要旨 
                    
                        2. Identify Proper Orientation of Transmitter:   There are a few possible orientations of the  LTM Series transmitters, they are: Do not over tighten the clamps because  they will bend and distort. Figure 10. Top view of mounting clamps and sensor probe Figure 9.  Possible transmitter configurations A:  Is the correct way to have clamps tightened.   Transmitter A is a standard top mount  The clamps do not have to meet. configuration.   Transmitter B is a top mount with elbow, usually  utilized w
                    
                    ページ12に含まれる内容の要旨 
                    
                        4. Remote Mount Electronics Option.  Due to  process temperature, vibration or accessibility  the housing/electronics of the LTM transmitter  There are a variety of ways to install a  can be remote mounted as far as 25 ft.  The  standalone transmitters (i.e. crane, lift, etc…),  housing/electronics are supplied with a pipe- the basic rule to remember when installing an  mount bracket that can be mounted most  LTM transmitter is DO NOT DAMAGE the  nearby posts or pipes with hose clamps.  The  sen
                    
                    ページ13に含まれる内容の要旨 
                    
                        4.3 Insulation (against extreme heat/cold) Magtech strongly recommends that an experienced  (When insulating gages): Magtech Technician do insulation of the magnetic  Magtech level transmitters have a maximum  level gages at the factory with externally mounted  operating temperature of 300 F.  When insulating a  transmitters. mag-gage and transmitter assembly in HOT service,  keep the transmitter OUTSIDE the insulating  material.  Special blankets for this type of insulation  If Cryogenic “Hard 
                    
                    ページ14に含まれる内容の要旨 
                    
                        Section Field Wiring 5 5.0 Recommended Loop Wiring The following is the recommended loop wiring. Figure 13.  Recommended Loop Wiring 11                                                                                                                                                                                                                                                                                                                                                                             
                    
                    ページ15に含まれる内容の要旨 
                    
                        The following is the Hart Topology. Figure 14.  HART Loop Topology Please visit www.hartcomm2.org to learn more about HART Protocol. 12                                                                                                                                                                                                                                                                                                                                                                             
                    
                    ページ16に含まれる内容の要旨 
                    
                        5.1 Area Classification Installation Safety If the instrument is used as an explosion proof (exp) device then exp conduit must be sealed within 18  inches of the termination point – at the instrument. Power must be supplied by an isolated supply. Caution-To reduce the risk of ignition of hazardous atmospheres, disconnect the device from the supply  circuit, or area must be known to be non-hazardous, before opening. 13                                                                               
                    
                    ページ17に含まれる内容の要旨 
                    
                        Section Transmitter Specifications 6 6.1 Hazardous Locations /              6.2 Electronic Specifications        General Ratings Supply Voltage: 13 – 36 Vdc (13V @ 20mA) CSA and CSAUS:  Explosion Proof: Repeatability: .005% of full scale or                                                                  Class I Div. 1 or 2, Grps. B, C, D                                                 .010”, whichever is greater Class II, Grps. E, F, G                                                            
                    
                    ページ18に含まれる内容の要旨 
                    
                        Section Menu Structure and Features 7 7.0  Pushbutton Operation The menu structure and pushbutton operation of the LTM series transmitters is simple and user-friendly.  The  electronics module has 3 pushbuttons (from left to right): ↑ :  This button is used to increment values and change “Yes” to “No” and “No” to “Yes”. ↓ : This button is used to decrement values and change “Yes” to “No” and “No” to “Yes”. ← : This is the enter button used to execute functions and enter/exit into or out of subme
                    
                    ページ19に含まれる内容の要旨 
                    
                        7.1  Menu Structure Main Screen (scrolling): The menu structure has been designed so the end user can make parameter changes relatively fast and easy.   Below is a detailed description of these menus. The LTM-250/350 LCD is a 2x8 character screen.  The main screen scrolls between the following parameters: 1. Level (in selected engineering units) 2. Interface (when option is provided – in selected engineering units)-LTM-350 only 3. Temperature (when option is provided – in selected engineering un
                    
                    ページ20に含まれる内容の要旨 
                    
                        The following is the LTM-250/350 LCD Menu Flowchart Magtech Magtech LTM-250     or LTM-350 SW Rev 1.00.00 HW Rev 1.00.00 Display? Scroll > Level > Intrface*   > Temp**   > mA Out  > % Range SelLngth 30.00 in Lvl Unit in > ft > mm > cm > m Temp Unit** C > F > R > K Sel PV* Level > Interface Sel Alrm FailHigh > FailLow > HoldOut ChgRnge?  >>> Sel LRV    >>>    Sel URV Yes > No    (yes) 0.00 in             24.00 in SelDamp 1 sec ROC Fltr 10.0in/s TrmSnsr?  >>> TrimZero  >>> TrimZero  >>> TrimSpan