                           BUCK STOVE MODEL ZCBB VENTLESS  
FIREBOX ENCLOSURE  
FOR GAS-FIRED DECORATIVE TYPE UNVENTED ROOM 
HEATERS FOR USE WITH OPTIONAL WOODEN FLUSH MOUNT 
MANTEL (FF) AND OPTIONAL WOODEN SURROUND (WS) 
(UNIVERSAL BOX) 
FOR USE ONLY WITH A LISTED GAS-
FIRED UNVENTED  DECORATIVE 
ROOM HEATER NOT TO EXCEED 
40,000 BTU/H. DO NOT BUILD A 
WOOD  FIRE 
                                 Carefully review the instructions supplied 
                             with the decorative type unvented room heater 
   
                    
                    ページ2に含まれる内容の要旨 
                    
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    ページ3に含まれる内容の要旨 
                    
                        TABLE OF CONTENTS  Safety Information and Warnings ....................................................................................... 3  Installation ........................................................................................................................... 5  Firebox and Framing Dimensions (ZC) (FF) ...................................................................... 6  Firebox Clearances (ZC) (FF) ..........................................................................
                    
                    ページ4に含まれる内容の要旨 
                    
                          2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 
                    
                    ページ5に含まれる内容の要旨 
                    
                        SAFETY INFORMATION  WARNINGS  IMPORTANT: READ THIS OWNER’S MANUAL CAREFULLY AND COMPLETELY  BEFORE TRYING TO ASSEMBLE, INSTALL, OPERATE, OR SERVICE THIS  APPLIANCE (FIREBOX  ENCLOSURE).    Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, and/or nausea.   If you have these signs, the heater may not be working properly.  Get fresh air at once!    Have heater  serviced.   Some people-pregnant women, persons with heart or lung disease,  anemia, those under the in
                    
                    ページ6に含まれる内容の要旨 
                    
                        WARNING    DO NOT USE A BLOWER INSERT, HEAT EXCHANGER  INSERT, OR OTHER ACCESSORY NOT APPROVED FOR  USE WITH THIS HEATER.    THIS HEATER SHALL NOT BE INSTALLED IN A  CONFINED SPACE UNLESS PROVISIONS ARE MADE FOR  ADEQUATE COMBUSTION AND VENTILATION AIR.       ”See Page 10, for “Producing Adequate Ventilation”.     NOTE:  THIS IS A VENTLESS FIREBOX ENCLOSURE (UNIVERSAL)  FOR GAS FIRED DECORATIVE TYPE UNVENTED ROOM HEATERS.   IT WILL ACCEPT ANY GAS LOGS UP TO 40,000 BTU’S AS LONG AS  THE LOGS WILL
                    
                    ページ7に含まれる内容の要旨 
                    
                        INSTALLATION    Your New Buck Ventless Firebox Enclosure may be installed in Residential or *After-Market  Manufactured Mobile Homes.  This appliance may be installed in an *After Market Manufactured  Mobile Home,  where not prohibited by state or local codes.    *  (After Market:  Completion of sale, not for the purpose of resale from the manufacturer).    NOTE:      See page 13, for  “Producing Adequate Ventilation”.  CHOOSING THE LOCATION FOR YOUR FIREBOX   Figure 1 shows some of the many way
                    
                    ページ8に含まれる内容の要旨 
                    
                        FIREBOX AND FRAMING DIMENSIONS  (ZC) & (FF)  NOTE: SEE PAGE 10 IF AN OPTIONAL WOODEN FLUSH MOUNT MANTEL FRONT  (FF) IS TO BE USED.  WARNING: NOTCHING       OF THE FRAMING  AROUND THE STAND- OFFS (SPACERS) OR AL-  38 1/8"  36-5/8" TERATION OF THE  35-5/8" STANDOFFS CAN CAUSE  35 1/2"  18-15/16" 20 1/2"  A FIRE OR MAY RESULT  33-1/8" 36 3/16"  IN PROPERTY DAMAGE,  PERSONAL INJURY, OR    LOSS OF LIFE.      40 7/8”  37-5/16" 39 3/8"    Figure 2 NOTE:  YOUR NEW BUCK  GAS LINE CORPORATION VENTLESS  FI
                    
                    ページ9に含まれる内容の要旨 
                    
                          FIREBOX CLEARANCES  The firebox may be placed directly on a combustible floor, firebox before installing.  COMBUSTIBLE MATERIALS MUST NOT BE INSTALLED  against a combustible wall   at marked clearances, or on a  OVER OR TOUCH ANY BLACK PAINTED SURFACE.  DO  raised wooden platform.  NOT BLOCK HEAT CIRCULATING AIR OUTLETS.  DOING  If the firebox is to be installed on a raised wooden  SO MAY RESULT IN POTENTIAL FIRE HAZARDS.  platform, the platform must be a continuous level surface.   1. Sidewal
                    
                    ページ10に含まれる内容の要旨 
                    
                        FINISHING YOUR FIREBOX  materials before using them on the face of the  There is a wide variety of finishing material  firebox.  Some of these products contain  available for your firebox from formal wall  combustible materials.  Combustible wall  treatments with marble and mantels, to rustic  coverings such as paneling or wallboard may  wood paneling, stone or brick.  not overlap the black face of the firebox.  The  IT IS IMPORTANT THAT THE BLACK FACE  OF THE FIREBOX NOT BE COVERED WITH  space 
                    
                    ページ11に含まれる内容の要旨 
                    
                        MANTEL PROFILES FOR VENTLESS FIREBOX ENCLOSURE  (UNIVERSAL BOX) ZERO CLEARANCE CABINET MUST BE  FOLLOWED  A  COMBUSTIBLE  3 1/2”  MATERIALS  3/4”  3”  STANDOFF  B  ZCBB  CANOPY  4”  FIGURE  5                                             MANTEL CLEARANCES    MANTEL WIDTH                                            MANTEL HEIGHT       (“A” inches)                                        (“B” inches above firebox opening)                   6.0                                                           
                    
                    ページ12に含まれる内容の要旨 
                    
                               INSTALLATION INSTRUCTIONS FOR MODEL ZCBB OPTIONAL    WOODEN FLUSH MOUNT MANTEL FRONT (FF) (KIT#PAKDMZCBBFF)  “NOTE: Follow the framing instructions on page(s) 6 & 7. With the exception of the placement  of the ZCBB in the framed opening . The ZCBB must be placed with the front surface of the  appliance 1-9/16” out from the finished wall. This well allow the FF to set flush with the front of  the ZCBB”.     CLEARANCES:  1. Sidewall Clearances:  Clearances from the side of the firebox openi
                    
                    ページ13に含まれる内容の要旨 
                    
                              INSTALLATION INSTRUCTIONS FOR MODEL ZCBB OPTIONAL                       WOODEN SURROUND (WS) (KIT# PAKDMZCBB)  CLEARANCES:  1. Sidewall Clearances:  Clearances from the side of the firebox opening to any adjacent  combustible wall should not be less than 7".  See Figure 4  2. Ceiling Clearances:  The ceiling height should not be less than 42" from the top of the firebox  opening.  ASSEMBLY INSTRUCTIONS:    Tools Needed: Medium Phillips Screwdriver    Step 1: Lay out all components. (See di
                    
                    ページ14に含まれる内容の要旨 
                    
                                                                            REAR VIEW  After assembling the WS you must insert the ZCBB. It is best to insert the ZCBB from the rear of the  WS, this gives you more area to hold the ZCBB and reduces the risk of scratching the surface of the  front area of the base (hearth) area. Flush and center the ZCBB’s front in the WS.  You can attach the ZCBB to the WS with “L” brackets at the rear sides of the ZCBB (brackets not  provided).  ZCBB  12                                 
                    
                    ページ15に含まれる内容の要旨 
                    
                        PRODUCING ADEQUATE VENTILATION  NOTICE: Information on provisions for adequate combustion and ventilation air are located in  the unvented room heater ‘s installation instructions. The unvented room heater’s instructions  must be followed exactly.  This section is used for residential installation or mobile home installation.    UNCONFINED SPACE:     3 An unconfined space has a minimum air volume of 50 cubic feet for each 1,000 BTU/Hr (4.8m per  Kw) input rating of all appliances in the space (C
                    
                    ページ16に含まれる内容の要旨 
                    
                         3.  Add the BTU/Hr of all fuel burning appliances in the space.    Vent-Free Heater                       _________________________BTU/Hr.    Gas Water Heater*                    _________________________BTU/Hr.     Gas Furnace                               _________________________BTU/Hr.    Vented Gas Heater                     _________________________BTU/Hr.       Gas Fireplace Logs                     _________________________BTU/Hr.    Other Gas Appliance*              +__________________
                    
                    ページ17に含まれる内容の要旨 
                    
                        VENTILATION AIR    VENTILATION AIR FROM INSIDE BUILDING  This fresh air would come from an adjoining unconfined space.  When venting to an adjoining space,  you must provide two permanent openings:  one within 12" of the ceiling  and one within 12" of the  floor on the wall connecting the two spaces (see Options 1 and 2, Figure 6).  You can also remove door  into adjoining room (see Option 3, Figure 6).    WARNING    REWORK WORKSHEET, ADDING THE SPACE OF THE ADJOINING UNCONFINED  SPACE.  THE COM
                    
                    ページ18に含まれる内容の要旨 
                    
                        VENTILATION AIR FROM OUTDOORS    Provide extra fresh air by using ventilation grills or ducts.  You must provide two permanent  openings: one within 12" of the ceiling and one within 12" of the floor.  Connect these items directly  to the outdoors.  These spaces include attics and crawl spaces.  Follow the National Fuel Gas Code  NFPA 54/ANSI Z223.1, Section 4.3, “Air For Combustion and Ventilation” for required size of  ventilation grills or ducts.    IMPORTANT:  Do not provide openings for inl
                    
                    ページ19に含まれる内容の要旨 
                    
                        OPTIONAL BLOWER INSTALLATION  The  Model ZCBB has an optional MA ZCBB714  blower kit that can be purchased from your dealer.  You will need to follow these steps and the diagram below and the wiring diagram on page 18.  NOTE: The receptacle which is provided in the Model ZCBB must be wired into your home  (residence)  in order to have electricity to operate the blower motor. If the receptacle hasn’t been  wired in during installation of the ZCBB you may need to contact a licensed electrician. Th
                    
                    ページ20に含まれる内容の要旨 
                    
                        WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE  HAZARDS OF HIGH SURFACE TEMPERATURES AND SHOULD STAY AWAY TO  AVOID BURNS OR CLOTHING IGNITION.  YOUNG CHILDREN SHOULD BE  CAREFULLY SUPERVISED WHEN IN THE SAME ROOM AS GAS LOGS.      WARNING: CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT  BE PLACED ON OR NEAR THESE GAS LOGS.        WIRING DIAGRAM (MA  ZCBB714)    BLACK    WHITE  Figure 8  NOTE:  “If any of the original wire  must be replaced, it must be replaced with a wire of at  least a