ページ1に含まれる内容の要旨 
                    
                        USER’s MANUAL & INSTALLATION INSTRUCTIONS
2 Stage R-410A Single Package Heat Pump
15 SEER
IMPORTANT
Please read this information thoroughly and become familiar with the capabilities 
and use of your appliance before attempting to operate or maintain this unit. 
Keep this literature where you have easy access to it in the future. If a problem 
occurs, check the instructions and follow recommendations given. If these 
suggestions don’t eliminate your problem, call your NORDYNE Servicing 
Contracto
                    
                    ページ2に含まれる内容の要旨 
                    
                        SAFETY INFORMATION ...............................3 Defrost Cycle Control ................................9  Ambient Sensor Mounting .......................11 USER INFORMATION ...................................3  Electric Heat Package .............................11  About the Heat pump  ................................3  Operating Instructions ...............................3 SYSTEM OPERATION .................................12  Cooling Operation ...................................3 Pre - Star
                    
                    ページ3に含まれる内容の要旨 
                    
                        SAFETY INFORMATION Operating Instructions IMPORTANT: Please read all instructions before Cooling Operation servicing this equipment. Pay attention to all 1. Set the thermostat’s system mode to COOL  safety warnings and any other special notes  or AUTO and change the fan mode to AUTO.  highlighted in the manual. Safety markings See Figure 1 are used frequently throughout this manual to  2. Set the temperature selector to the desired  designate a degree or level of seriousness and temperature leve
                    
                    ページ4に含まれる内容の要旨 
                    
                        At the beginning of the defrost cycle, both the  outdoor condenser fan and compressor will   CAUTION: turn off. After approximately 30 seconds, the  compressor will turn on and begin to heat the This unit uses refrigerant R-410A. DO NOT  outdoor coil causing the ice and snow to melt. under any circumstances use any other  NOTE: While the ice and snow is melting, some refrigerant in this unit. Use of another  steam may rise from the outdoor unit as the warm refrigerant will damage the unit. coil 
                    
                    ページ5に含まれる内容の要旨 
                    
                        HEAT PUMP INSTALLATION 6 ft. Locating the Heat pump 24" � Select a solid, level position, preferably on a  concrete slab, slightly above the grade level,  and parallel to the home. DO NOT PLACE  UNIT UNDER THE HOME. � The hot condenser air must be discharged up  and away from the home, and if possible, in a  direction with the prevailing wind. � Do not place the unit in a confi ned space. � If practical, place the heat pump and its ducts  12" in an area where they will be shaded from  the afterno
                    
                    ページ6に含まれる内容の要旨 
                    
                        14” Duct Dimples Transition Duct Screws INSTALLING RETURN AND LOCATING AND INSTALLING THE  SUPPLY AIR FITTINGS RETURN AIR ASSEMBLY To simplify installation, locate and install the  The supply and return fi ttings are included with  return air assembly fi rst. If desired, the return  the unit and located in the supply duct. They  opening can be located inside a closet with  attach to the unit openings (Figure 4) with a  louvered doors that has an open area equal to  fl ange and bead arrangement and 
                    
                    ページ7に含まれる内容の要旨 
                    
                        LOCATING AND INSTALLING THE  DUCTING SYSTEM SUPPLY DAMPER(S) Air ducts should be installed in accordance with  the standards of the National Fire Protection  When locating the supply damper(s), carefully  Association “Standard for Installation of Air  check fl oor joists and frame members that could  Conditioning and Ventilation Systems” (NFPA  interfere with the installation of the damper or  fl exible duct. Ideally, the damper (Figure 6) should 90A), “Standard for Installation of Residence  Type
                    
                    ページ8に含まれる内容の要旨 
                    
                        Note: For highly resistive duct systems it may be 2. Locate the orange, black and red wires  necessary to add an additional return air duct and terminated to the blower motor. The orange  or supply to achieve maximum performance and wire controls the low speed cooling and heating  prevent coil icing and refrigerant fl ood back. operations, the black wire controls high speed  cooling and heating operations and the red  Connecting the Return and Supply Air  wire controls the electric heating operat
                    
                    ページ9に含まれる内容の要旨 
                    
                        Low Pressure Switch The low pressure switch is factory installed and  located in the suction line internal to the unit. The  switch is designed to protect the compressor if a  loss of charge occurs. Under normal conditions,  the switch is closed.  If the suction pressure falls below 5 psig, then  the switch will open and de-energize the unit. The  switch will close again once the suction pressure  High Voltage increases above 20 psig. The low pressure  Low Voltage switch interrupts the thermosta
                    
                    ページ10に含まれる内容の要旨 
                    
                        Y2 Y DF DF2 out out out YR C Y2 L in Green (from Blower Relay) R W2 O Y1 Y2 G C 1 Brown 2 Orange E 3 4 5 L 6 7 8 9 INDOOR DEFROST Accessory Heat Plug THERMOSTAT BOARD SUB-BASE Figure 9. Typical Wiring (Field Supplied) for 2-Stage Cool, 2 Stage Electric Heat Air Flow Model Q5RF Wire Color/Speed Tap Motor Speed (@ 0.3 in WC) T1 Low 560 Orange/T2 Medium/Low* 600 Black/T3 Medium** 800 X24K Red/T4 Medium/High*** 1,040 T5 High 1,250 Orange/T1 Low* 600 T2 Medium/Low 750 X36K Black/T3 Medium** 1,200 Red
                    
                    ページ11に含まれる内容の要旨 
                    
                        Control is uncalibrated when power is applied. 6.  Install one spacer next between the  Calibration occurs after a defrost cycle. The plastic clip and mounting bracket. control initiates defrost after 34 minutes of 7.  Bend the mounting bracket into position.  accumulated compressor run time in heating Install the mounting bracket to the unit  with coil temperature below 35° F. The defrost using the screw in the corner panel. cycle terminates when the coil sensor reaches  termination temperature
                    
                    ページ12に含まれる内容の要旨 
                    
                        SYSTEM OPERATION setting until the whole system de-energizes.  Immediately lower the thermostat temperature  Pre-Start Checklist to the original setting and verify that the indoor  The following check list should be observed prior  blower is energized. After approximately 3  to starting the unit. minutes the compressor and the outdoor fan   Is the unit level? Unit should be level or slightly  will energize. slanted toward the drain for proper condensate  drainage.  Emergency Heat  Is the unit 
                    
                    ページ13に含まれる内容の要旨 
                    
                        Anti Short Cycle Timer Test determined in step 4, then there is too much  charge in the system. Remove refrigerant and  The 3 minute time delay feature can be bypassed  repeat steps 1 through 3 until the system is  by shorting the “TEST” pins together. correctly charged. Heating Mode � If the pressure measured in step 1 is less  When the “TEST” pins are shorted together  than the required liquid refrigerant pressure  for more than 1 second, the control will switch determined in step 4, then ther
                    
                    ページ14に含まれる内容の要旨 
                    
                        Refrigerant Charging Charts for Cooling Mode of Operation Q5RF-X24K CHARGING CHART 600 575 550 525 500 Remove refrigerant when above curve 475 450 425 400 375 350 325 Add refrigerant when below curve 300 275 250 225 200 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 LIQUID TEMPERATURE (F) Figure 11. Charging Chart for 2 ton Units Q5RF-X36K CHARGING CHART 600 575 550 525 500 Remove refrigerant when above curve 475 450 425 400 375 350 325 Add refrigerant when below curve 300 275 250 225 200
                    
                    ページ15に含まれる内容の要旨 
                    
                        Refrigerant Charging Charts for Cooling Mode of Operation - Continued Q5RF-X48K CHARGING CHART 600 575 550 525 500 Remove refrigerant when above curve 475 450 425 400 375 350 325 Add refrigerant when below curve 300 275 250 225 200 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 LIQUID TEMPERATURE (F) Figure 13. Charging Chart for 4 ton Units Q5RF-X60K COOLING CHARGING CHART 600 575 550 525 500 Remove refrigerant when above curve 475 450 425 400 375 350 325 Add refrigerant when below curve
                    
                    ページ16に含まれる内容の要旨 
                    
                        16 Refrigerant Charging Tables for Heating Mode of Operation Refrigerant Charging Chart Legend for Heating Mode of Operation:  Shaded boxes indicate fl ooded conditions.  Rated design values. The suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures  vary. 1. All pressures are listed psig and all temperatures in °F 2. Discharge temperatures greater than charted values indicate an undercharged system. Q5RF-X24K OUTDOOR TEMPERATURE (D
                    
                    ページ17に含まれる内容の要旨 
                    
                        17 Refrigerant Charging Tables for Heating Mode of Operation - (continued) Refrigerant Charging Chart Legend for Heating Mode of Operation:  Shaded boxes indicate fl ooded conditions.  Rated design values. The suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures  vary. 1. All pressures are listed psig and all temperatures in °F 2. Discharge temperatures greater than charted values indicate an undercharged system. Q5RF-X48K OUTDOOR 
                    
                    ページ18に含まれる内容の要旨 
                    
                        Figure 15. Q5RF/PPH2RF Series Wiring Diagram - 2 & 3 Ton Units 18 3. Not sutiable on systems that exceed 150V to ground. 4. For replacement wires use conductors suitable for 105°C. WIRING DIAGRAM Q5RF/PPH2RF SERIES SMALL PACKAGE H/P 208/230 VOLT 60HZ/SINGLE PHASE 2 TON AND 3 TON 5. Couper le courant avant de faire letretine. BLOWER 6. Employez uniquement des conducteurs NOTES: SEE TABLE FOR FACTORY  MOTOR     en cuiver. SET BLOWER WIRING 1. Disconnect all power before servicing. 7. Ne convient p
                    
                    ページ19に含まれる内容の要旨 
                    
                        Figure 16. Q5RF/PPH2RF Series Wiring Diagram - 4 & 5 Ton Units 19 WIRING DIAGRAM Q5RF/PPH2RF SERIES SMALL PACKAGE H/P 208/230 VOLT 60HZ/SINGLE PHASE 7. Couper le courant avant de faire letretine. 4 TON AND 5 TON 8. Employez uniquement des conducteurs NOTES: BLOWER     en cuiver. SEE TABLE FOR FACTORY 1. Disconnect all power before servicing. MOTOR SET BLOWER WIRING 9. Ne convient pas aux installations de plus 2. For supply connections use copper conductors only. HIGH SPEED     de 150V a la terre
                    
                    ページ20に含まれる内容の要旨 
                    
                        INSTALLER PLEASE LEAVE THESE INSTALLATION  INSTRUCTIONS WITH THE HOMEOWNER. 709064B (Replaces 709064A) Specifi cations and illustrations ¢709064-¤  subject to change without notice or incurring obligations. O’Fallon, MO 709064B Printed in U.S.A. (09/09)