Summary of the content on the page No. 1 
                    
                        This manual covers model numbers:
United States Canada
PG10* 34-100-2NV or 2PV PR 100-34 2NV or 2PV
PG10* 34-130-2NV or 2PV PR 130-34 2NV or 2PV
PG10* 50-130-2NV or 2PV PR 130-50 2NV or 2PV
PG10* 34-150-2NV or 2PV PR 150-34 2NV or 2PV
PG10* 50-175-3NV or 3PV PR 175-50 3NV or 3PV
PG10* 50-199-3NV or 3PV PR 199-50 3NV or 3PV
PG10* 100-199-3NV or 3PV PR 199-100-3NV or 3PV
* Indicates warranty period
Note:
The manufacturer of this water heater recommends that it 
be professionally installed by train
                    
                    Summary of the content on the page No. 2 
                    
                        Your safety and the safety of others are very important. We have provided many important safety messages in this manual and on your appliance. Always read and obey all  safety messages. This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.” These words mean: You can be killed or seriously injured if you don’t  immediately follow instructio
                    
                    Summary of the content on the page No. 3 
                    
                        INSTALLATION INSTRUCTIONS Consumer Information Unpacking the Water Heater OBSERVE ALL GOVERNING CODES AND ORDINANCES. This water heater is design-certified by CSA International  as a Category IV, direct vented water heater which takes  its combustion air from the outside of the structure and  Excessive Weight Hazard exhausts all products of combustion to the outside of the  Use two or more people to move and  structure. install water heater unless proper  This water heater must be installed acco
                    
                    Summary of the content on the page No. 4 
                    
                        • Consider the inlet and exhaust vent system piping   when selecting the water heater location.  The venting  system must be able to run from the water heater to  the termination with a minimal length and number of  elbows.  Input rates are reduced as vent system length  increases.  The venting system must comply with the  requirements  set forth in the venting section of this  manual. • Locate the water heater near the existing gas piping.  If installing a new gas line, locate the water heater 
                    
                    Summary of the content on the page No. 5 
                    
                        Clearances and Accessibility Figure 3A: 2” Condensation Trap Installation  100,000 - 150,000 BTU/Hr Models  Notice:  Minimum clearances from combustible materi- als are stated on the data plate located on the front of the  water heater. •    The water heater is certified for installation on a       combustible floor.  Important: If installing over carpeting, the carpeting must  be protected by a metal or wood panel beneath the water  heater. The protective panel must extend beyond the full  widt
                    
                    Summary of the content on the page No. 6 
                    
                        VENT PIPE SYSTEM Figure 4: Condensate Drain Carbon Monoxide Hazard Follow all instructions to locate and install  the vent pipe system. Instructions can be found in this manual, in  state or local codes (or the authority having  jurisdiction), or in the absence of such, the  National Fuel Gas Code, ANSI Z223.1, NFPA  54, Latest Edition.  Canadian installations  must be performed in accordance with  Condensate Drain Line CAN/CGA-B149. All parts of the condensate trap are glued except for the  Fai
                    
                    Summary of the content on the page No. 7 
                    
                        All pipe, fittings, pipe cement, primers and procedures  Vent Pipe Material must conform to American National Standard Institute and  The following plastic materials may be used for both the American Society for Testing and Materials (ANSI/ASTM)  combustion air inlet and exhaust outlet piping subject to  standards in the United States. This water heater has been  state and local codes: design certified by the Canadian Standards Association for  use with the specified (CSA) listed plastic vent pi
                    
                    Summary of the content on the page No. 8 
                    
                        1.   Use only 2 inch pipe or a 2 inch concentric vent on  Vent Termination Locations the vent termination for 100,000 - 150,000 BTU/Hr  The air inlet and exhaust outlet must be installed with the  models. For inputs of 175,000 BTU/Hr or more, use  following minimum clearances (see figure 6): only 3 inch pipe or a 3 inch concentric vent. Do not  expose any 3” X 2” reducers or bushings to out- • Twelve inches above grade or maximum anticipated  door ambient temperatures.  snow level. 2.   The air 
                    
                    Summary of the content on the page No. 9 
                    
                        INLET/OUTLET VENT TERMINATIONS (100,000 - 150,000 BTU/HR) Standard Horizontal Termination Alternative Horizontal Termination When 3 inch pipe is used between the water heater and the The combustion air and exhaust terminations may be raised  outside wall, reduce it to 2 inch pipe before penetrating the up to 24 inches above the wall penetrations if required for  wall. A maximum of 18 inches of 2 inch pipe may be used anticipated snow levels (see figure 8A).  The two elbows  between the 3 inch tr
                    
                    Summary of the content on the page No. 10 
                    
                        VERTICAL TERMINATIONS (100,000 - 150,000 BTU/HR) When 3 inch pipe is used between the water heater and the The air inlet and exhaust outlet terminations must be at  roof, reduce it to 2 inch pipe before penetrating the roof. A least 12 inches above the roof line or anticipated snow  maximum of 18 inches of 2 inch pipe may be used between levels.  See figure 9A below. the 3 inch transition and the inside of the roof. Note: See “Venting Additional Polaris® Units” below if  The vertical inlet air t
                    
                    Summary of the content on the page No. 11 
                    
                        CONCENTRIC VENT TERMINATIONS (100,000 - 150,000 BTU/HR) For new installations, install 2” Concentric vent kit model  Figure 13A: Through the Wall Termination KGAVT0501CVT, part number 6910542.  See Manufacturer’s  instructions for complete installation or call customer service at  1-800-456-9805 for assistance.   For planning purposes, see figures 10A-13A below for vent  terminal specifications. Note:  For replacement installations, previously installed  American Water Heater Company supplied co
                    
                    Summary of the content on the page No. 12 
                    
                        INLET/OUTLET VENT TERMINATIONS (175,000+ BTU/HR) Alternative Horizontal Termination Standard Horizontal Termination The combustion air and exhaust terminations may be  The standard horizontal air inlet termination is a 3 inch  raised up to 24 inches above the wall penetrations if  pipe which terminates at the exterior wall and utilizes a  required for anticipated snow levels (see figure 8B).  The  coupling to prevent the pipe from being pushed back into  two elbows shown in figure 8B are conside
                    
                    Summary of the content on the page No. 13 
                    
                        VERTICAL TERMINATIONS (175,000+ BTU/HR) For inputs of 175,000 BTU/Hr or greater, all termination pip- The air inlet and exhaust outlet terminations must be at  ing and fittings are 3”.  Do not reduce before penetrating least 12 inches above the roof line or anticipated snow  the wall. levels as shown in figure 9B below. ® The vertical inlet air termination requires a return bend or Note: See “Venting Additional Polaris Units” below if  ® two short or long sweep radius 90° elbows to keep the inle
                    
                    Summary of the content on the page No. 14 
                    
                        CONCENTRIC VENT TERMINATIONS (175,000 + BTU/HR) For new installations, install 3” Concentric vent kit  Figure 13B: Concentric Vent Piping Installation model KGAVT0601CVT, part number 6910543.  See  Manufacturer’s instructions for complete installation or call  customer service at 1-800-456-9805 for assistance.   For planning purposes, see figures 10B-13B below for vent  terminal specifications. Figure 10B: 3 Inch Concentric Vent Figure 11B: Through the Wall Termination *100 Gallon Model Shown. N
                    
                    Summary of the content on the page No. 15 
                    
                        Gas Input Rate Figure 14: Input Graph The gas input rate of this water heater is affected by  several environmental factors such as: • The heating value of the gas • The air and gas densities (which vary widely due to baro- metric pressure and temperature changes) • Venting installations (pipe diameter, length and fittings) • Altitude When measuring the input rate these factors should be  incorporated into the calculations. Also measure the gas  consumption over a sufficiently long time to obtai
                    
                    Summary of the content on the page No. 16 
                    
                        Figure 15: Typical One-Temperature System Piping Installation *100 Gallon Model Shown. Tempering Valve Installation Closed System/Thermal Expansion A tempering valve has been provided for use with the  When a backflow prevention device or check valve is  Polaris®  Gas water heater and must be installed, per the  installed, it can create a “Closed System.” Heating water  manufacturer’s instructions, in the domestic hot water line.   in a closed system causes normal thermal expansion and  See Figu
                    
                    Summary of the content on the page No. 17 
                    
                        Figure 17: Air Handler Piping Installation Massachusetts code does not  allow this type of installation. *100 Gallon Model Shown. • If the space heating system requires water temperatures Storage Tank Installation  in excess of 120°F, a tempering valve (provided) must  When installing the Polaris® with a storage tank, see figure  be installed per the manufacturer’s instructions in the  18 for piping suggestions. potable hot water supply to limit  the risk of scald injury. • Pumps, valves, piping
                    
                    Summary of the content on the page No. 18 
                    
                        Notes on Figure 18: Figure 18: Polaris with Auxillary Storage Tank - One or Two  If tank temperature is set above Temperature System (With or Without Building Recirculation) 120°F and water is supplied for  domestic use (hand washing, show- ering, etc.) a tempering valve must  be installed in the hot water line to  domestic fixtures. Installation must conform to local  code requirements. If a check valve  is installed in the cold water sup- ply line, an expansion tank must be  installed between 
                    
                    Summary of the content on the page No. 19 
                    
                        GAS SUPPLY AND PIPING Figure 19: Gas Piping Installation Explosion Hazard Use a new AGA or CSA approved gas  supply line. Install a shut-off valve. Do not connect a natural gas water  heater to a L.P. Gas Supply. Gas Pressure Do not connect an L.P. gas water heater  Important: The gas supply pressure must not exceed the  to a Natural Gas Supply. maximum supply pressure as stated on the water heater’s  Failure to follow these instructions can  data plate.  Minimum supply pressure should also be  
                    
                    Summary of the content on the page No. 20 
                    
                        Gas Pressure Testing Important: This water heater and its gas connection must  be leak tested before placing the appliance in operation.   • If the code requires the gas lines to be tested at      a pressure of 14” W.C. or greater, the water heater    and its manual shut-off valve must be disconnected   from the gas supply piping system and the line      capped. • If the gas lines are to be tested at a pressure less     Explosion Hazard than 14” W.C., the water heater must be isolated     Have