Summary of the content on the page No. 1 
                    
                        Installationand 	 	
Operations	Manual
H-IM-CU	 August	2008	 PartN 	 o.25008101 	
Replaces None. Information formerly included in H-IM-64L.
Condensing	
Units
Table	ofC 	 ontents
General Safety Information...............................................................................2
Inspection ...............................................................................................................2
Warranty Statement .........................................................................
                    
                    Summary of the content on the page No. 2 
                    
                        General	Safety	Information 3. Make sure that all field wiring conforms to the requirements  1. Installation and maintenance to be performed only by qualified      of the equipment and all applicable national and local codes.  personnel who are familiar with this type of equipment. 4. Avoid contact with sharp edges and coil surfaces.  2. Some units are pressurized with dry air or inert gas.    They are a potential injury hazard.  All units must be evacuated before charging the system with refrige
                    
                    Summary of the content on the page No. 3 
                    
                        AIR FLOW AIR FLOW Space	and	Location	Requirements	for	 Air	CooledC 	 ondensingUnits 	 	andRemot 	 eC 	 ondensers The most important consideration which must be taken into account when Another consideration which must be taken is that the unit should be  deciding upon the location of air-cooled equipment is the provision for a mounted away from noise sensitive spaces and must have adequate support  supply of ambient air to the condenser, and removal of heated air from the to avoid vibration and n
                    
                    Summary of the content on the page No. 4 
                    
                        Requirements	for	Remote	and	 Water	Cooled	 	 Condensing	Units	 General	Installation 2. A double riser discharge line may be used as shown in     The indoor compressor units are designed to be used with a remote   Diagram 2.  Line “A” should be sized to carry the oil at minimum    condenser.  The water cooled units are similar, except that they have an   load conditions and the line “B” should be sized so that at the    integral water cooled condenser. Inlet and outlet water connections are to   
                    
                    Summary of the content on the page No. 5 
                    
                        CondensingUnit 	 	Riggingand 	 M 	 ounting Figure. 	 Spring 		 M 	 ount Rigging holes are provided on all units.  Caution should be exercised when  moving these units. To prevent damage to the unit housing during rigging,  cables or chains used must be held apart by spacer bars. The mounting  platform or base should be level and located so as to permit free access of  supply air.  Ground	Mounting Concrete slab raised six inches above ground level provides a suitable base.  Raising the base abov
                    
                    Summary of the content on the page No. 6 
                    
                        HeadP 	 ressureC 	 ontrol Several types of head pressure control systems are available on   C.		Ambient	Fan	Cycle	Control condensing units: This is an automatic winter control method which will maintain a condensing  A. Dual Valve System. (See section on operation and adjustment.) pressure within reasonable limits by cycling fan motors in response to  B. Single Valve system. No adjustments are necessary.     outside air temperature. The thermostat(s) should be field adjusted to shut   (See secti
                    
                    Summary of the content on the page No. 7 
                    
                        Refrigeration	Oils* Oil	 Types With the changes that have taken place in our industry due to the CFC Table 2 below summarizes which oils/lubricants are approved for use in  issue, we have reevaluated our lubricants to ensure compatibility with the Copeland compressors. new HFC refrigerants and HCFC interim blends offered by several chemical  Mineral	Oils producers. As a secondary criteria, it is also desirable that any new lubricant  be compatible with the traditional refrigerants such as HCFC-2
                    
                    Summary of the content on the page No. 8 
                    
                        d) Suitable P-type oil traps should be located at the base of each    PhaseL 	 ossM 	 onitor  suction riser to enhance oil return to the compressor. The combination phase sequence and loss monitor relay protects the system  e) For desired method of superheat measurement, a pressure tap    against phase loss (single phasing), phase reversal (improper sequence) and   should be installed in each evaporator suction line in     low voltage (brownout). When phase sequence is correct and full line volt
                    
                    Summary of the content on the page No. 9 
                    
                        Three	Pipe	System Liquid	Lines	 The three pipe system (sometimes called re-evap.) uses three pipes: one for  Liquid lines should be sized for a minimum pressure drop to prevent  liquid line, one for suction line, and one for hot gas line. In addition, a re- “flashing”. Flashing in the liquid lines would create additional pressure drop  evaporator accumulator is used at the suction outlet of the evaporator. The  and poor expansion valve operation. If a system requires long liquid lines  hot gas i
                    
                    Summary of the content on the page No. 10 
                    
                        Determine	linesiz 	 e1 	 (main 	 line 	 	from	condensingunit) 	 : Unit	Cooler	Piping 1. Main line from the condensing unit to be sized for the total capacity     (balance) of the whole system of 24,000 BTUH’s (Table 8). Pipe	size	example : 2. Refer to 24,000 @100 feet at -20°F SST R404A on the chart.     Given: -10°FF 	 reezer with one system having (2) evaporators  You will find the suction line to be 1-3/8" and 1/2" liquid line. •  One condensing unit rated at 24,000 BTUH’s @ -20°F SST R404A  
                    
                    Summary of the content on the page No. 11 
                    
                        Table	.		Pressure	Loss	of	Liquid	Refrigerantsin 	 Liquid 	 	Line	Risers	(Expressedin 	 	PressureD 	 rop,PSIG, 	 and 	 	Subcooling	Loss,	˚F) Liquid	Line	Risein 	 	Feet Refrigerant 10' 			15' 20' 25' 	0' 0' 50' 75' 	 100' PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F PSIG ˚F R22 4.8 1.6 7.3 2.3 9.7 3.1 12.1 3.8 14.5 4.7 19.4 6.2 24.2 8.0 36.3 12.1 48.4 16.5 R507, R404A 4.1 1.1 6.1 1.6 8.2 2.1 10.2 2.7 12.2 3.3 16.3 4.1 20.4 5.6 30.6 8.3 40.8 11.8 Based on 110˚F liquid temperat
                    
                    Summary of the content on the page No. 12 
                    
                        Table	7.	Recommended	Line	Sizes	for	R-22	* Suc 	 tionLine 	 Siz 	 e Liquid	Line	Size Suction	 Temperature Receiver	to	 Expansion	 Valve	 Capacity	 +0˚F  	 	 +20˚F	 	+10˚F	 	 0˚F	 -10˚F	 -20˚F	 Equivalent	 BTUH Equivalent	Lengths Equivalent	Lengths Equivalent	Lengths Equivalent	Lengths Equivalent	Lengths Equivalent	Lengths Lengths 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 1,000 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
                    
                    Summary of the content on the page No. 13 
                    
                        Table	8.	Recommended	LineSiz 	 es	for	R-0  A	and	R507* Suc 	 tion	LineSiz 	 e Liquid	LineSiz 	 e Suction	 Temperature Receiver	to	 Expansion	 Valve	 Capacity	 +20˚F	 	 +10˚F	 -10˚F 	 	 	 -20˚F	 -0˚F 	 -0˚F  	 Equivalent	 BTUH Equivalent	 Lengths Equivalent	 Lengths Equivalent	 Lengths Equivalent	 Lengths Equivalent	 Lengths Equivalent	 Lengths Lengths 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 25' 50' 100' 150' 1,000 3/8 3/8 3/
                    
                    Summary of the content on the page No. 14 
                    
                        Evacuation	and	Leak	Detection Due to the smaller molecule size of HFC’s, they will tend to leak more readily  Repeat this operation a second time.   than CFC’s. Consequently, it is of the utmost importance that proper system  Open the compressor service valves and evacuate the entire system to 500  evacuation and leak detection procedures be employed. microns absolute pressure.  Raise the pressure to 2 psig with the refrigerant  Copeland recommends a minimum evacuation to 500 microns. In additio
                    
                    Summary of the content on the page No. 15 
                    
                        Check	Out	and	Start	Up After the installation has been completed, the following points should be  covered before the system is placed in operation:   a) Check all electrical and refrigerant connections.    Be sure they are all tight. b) Observe compressor oil level before start-up. The      oil level should be at or slightly above the 1/4 level      of the sight glass. Refer to Table 3 for proper compressor oil. c) Remove upper mounting nuts on the compressor feet.     Remove the shipping spacer
                    
                    Summary of the content on the page No. 16 
                    
                        Operational	Check	Out SystemB 	 alancing	-	CompressorSup 	 erheat After the system has been charged and has operated for at least two hours at  IMPORTANT:		 normal operating conditions without any indication of malfunction, it should  be allowed to operate overnight on automatic controls.  Then a thorough  In order to obtain the maximum capacity from a system, and to ensure  recheck of the entire system operation should be made as follows: trouble-free operation, it is necessary to balance each 
                    
                    Summary of the content on the page No. 17 
                    
                        GeneralS 	 equenceof 	 	Operation Electric	Defrost	 Troubleshooting The electric defrost units are relatively simple and trouble-free in operation: Refrigeration	Cycle Timer 1. Power is supplied to the timer at terminals “1” and “N”. If the system does not go through its proper sequence , check timer  2. The fan delay and the defrost termination thermostat is closed in the fan   operation through a defrost cycle. Check for loose wires or  terminals. Before   delay position and open in the defros
                    
                    Summary of the content on the page No. 18 
                    
                        Table	10.		System	 TroubleshootingC 	 hart PROBLEM POSSIBLE	 CAUSES POSSIBLE	 CORRECTIVE	 STEPS Compressor will not 1. Main switch open. 1. Close switch. run 2. Fuse blown. 2. Check electrical circuits and motor winding for shorts or grounds.  Investigate for possible overloading. Replace fuse after fault is corrected. 3. Thermal overloads tripped. 3. Overloads are automatically reset. Check unit closely when unit  comes back on line. 4. Repair or replace. 4. Defective contactor or coil. 5. Dete
                    
                    Summary of the content on the page No. 19 
                    
                        PreventiveM 	 aintenance • Check moisture indicator/sightglass for flash gas. If found check  UnitC 	 oolers entire system for refrigerant leaks and add refrigerant as needed after  At every six month interval, or sooner if local conditions cause clogging  repairing any leaks. or fouling of air passages through the finned surface, the following items  • Check compressor sightglass (if equipped) for proper oil level. should be checked. • Check condition of condenser. Look for accumulation of dirt
                    
                    Summary of the content on the page No. 20 
                    
                        Diagram	.		 Typical	 Wiring	Diagram	for	Single	Evaporator	with	andwithout 	 	Defrost	 Timer Diagram	.		 Typical	 Wiring	Diagram	for	Single	Evaporator	with	Defrost	 Timer	Only 20