Summary of the content on the page No. 1 
                    
                         
OIL FIRED FURNACE 
INSTALLATION AND OPERATION MANUAL 
WITH USERS INFORMATION SECTION 
 
MODEL:  
OH6FA072D48B OH6FA072DV4B  OH8FA119D60B OH8FA119DV5B 
OH6FA072D48R OH6FA072DV4R  OH8FA119D60R OH8FA119DV5R 
OH6FA072D48N OH6FA072DV4N 
   OH6FX072DV4R 
 
 WARNING: IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A 
FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR 
LOSS OF LIFE. 
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE 
VI
                    
                    Summary of the content on the page No. 2 
                    
                          CONTENTS  SECTION                   PAGE  I.  SAFETY SECTION          1  A. CODES AND CLEARANCES       3  B. MAKE-UP AIR         4  II.  GENERAL INSTRUCTIONS         5  A. CHIMNEY          6  B. VENTING          10  C. DRAFT REGULATORS        11  D. DUCT WORK/AIR CONDITIONING       11  E. AIR FILTER(S)         15  F. LIMIT POSITION AND LOCATION       17  G. BURNER INSTALLATION        18  H. BURNER SPECIFICATIONS AND APPLICATIONS     19  I. OILTANK AND PIPING        22  J. OIL FILTER          2
                    
                    Summary of the content on the page No. 3 
                    
                        Model Number Digit 1 2 3 4 5 6 7 8 9 10 11 12     Oil Furnace Model Nomenclature   Example Model Numbers O H 6 F A 0 7 2 D 4 8 B  O H 6 F A 0 7 2 D V 4 R     O H 8 F A 1 1 9 D 6 0 B   O H 8 F A 1 1 9 D V 5 R                                            O = Oil O                        H = Highboy   D = Downflow   H                      6 = Heat Exchanger Size Identifier     6                    F = Front       F                  R = Rear       R                 A = Single Stage     A         X = 2
                    
                    Summary of the content on the page No. 4 
                    
                          I.  SAFETY SECTION  This page and the following contains various warnings and cautions found  throughout the Oil Furnace Manual. Please read and comply with the statements  below.    WARNING AND CAUTIONS:    WARNING: This furnace is not to be used as a construction heater. See Page 3    WARNING:  The predetermined limit locations on all of the Thermo Pride oil fired  furnaces have been tested and approved by Thermo Products, LLC. Any attempt to  relocate these safety controls or replace the
                    
                    Summary of the content on the page No. 5 
                    
                                 2                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          
                    
                    Summary of the content on the page No. 6 
                    
                          The entire text of these instructions must be read and understood, before  installing the appliance. It is the installer's responsibility to do the following:    1. Inform and demonstrate to the user, the correct operation and maintenance of the appliance, as  explained in the Homeowner/User Information and Routine Maintenance section of this manual.     2. Inform the user of the hazards of flammable liquids and vapors and to remove such liquids and  vapors from the vicinity of the appliance. 
                    
                    Summary of the content on the page No. 7 
                    
                              b. Non-combustible material:  “...material that is not capable of being ignited and burned; such as material  consisting entirely of, or a combination of, steel, iron, brick, concrete, slate,  asbestos, glass, and plaster.”    : Carefully read and thoroughly understand the following guidelines and warnings  before continuing with the installation of this appliance.  Failure to follow these guidelines can  cause improper and unsafe operation of this appliance. Unsafe operation can result in
                    
                    Summary of the content on the page No. 8 
                    
                            II.  GENERAL INSTRUCTIONS - READ BEFORE START OF INSTALLATION    1.  The heating output capacity of the furnace proposed for installation should be based on a heat loss   calculation made according to the manuals provided by the Air Conditioning Contractors of America  (ACCA) or the American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.  (ASHRAE).    2.  All local codes and/or regulations take precedence over the instructions in this manual and should be  followed ac
                    
                    Summary of the content on the page No. 9 
                    
                            A.  CHIMNEY:  The furnace must be connected to an adequate chimney or an approved vent in accordance with these  instructions. An adequate chimney is one that is sealed and lined with the capability of producing a (-).04"  WC flue draft and having the capacity to handle the amount of stack gases that are introduced into it. A  chimney with an internal construction of corrosion resistant tile, stainless steel, or some other material  that will withstand flue gas temperatures up to 900°F is re
                    
                    Summary of the content on the page No. 10 
                    
                          2. PROPER CHIMNEY HEIGHT:  The chimney shall terminate at least 3 feet above the highest point where it passes through the roof of a  building and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet.  (See Fig. 2a).                                Fig. 2: Proper chimney termination height for pitched roofs    If the chimney penetrates a roof more than 10 feet from a ridge, wall or parapet, a minimum of 3 feet  above roof or exit point must be maintained
                    
                    Summary of the content on the page No. 11 
                    
                          4. PROPER CHIMNEY BOTTOM LEVEL:  In cases where the chimney extends to the basement floor, the draft can usually be improved by filling the  base of the chimney with sand to within 12 inches of the vent connector pipe after relocating the clean-out  door. (See Fig. 5).  Fig. 5: Suggested method to improve chimney draft.      5. TIGHT JOINTS:  All joints of the chimney must be tightly sealed. The inside of the chimney should be free of any  obstructions, such as loose brick, broken pieces of ti
                    
                    Summary of the content on the page No. 12 
                    
                              Fig. 7: Alternate constructions that allow reduced clearances to combustible materials.    REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION:  Type of protection applied to and covering all surfaces of combustible material within the distance  specified as the required clearance with no protection unless otherwise noted, all dimensions in inches,  refer to Fig. 7.    18 inches 9 inches 6 inches  Required clearance with no protection from the appliance or  Sides & Sides & Sides &  
                    
                    Summary of the content on the page No. 13 
                    
                          B.  VENTING:  NOTE: On the OH6 & OH8 it is possible to rotate the flue elbow (which is factory installed for vertical    discharge) 90° counter clockwise from the vertical position to adapt to various venting systems.  The OH8    flue elbow can also be rotated 90° clockwise.    Notice:  Blocked Vent Switch Installation  The blocked vent switch kit must be installed to comply with CAN STD B140.4 where applicable.  For  installation instructions see AOPS2687 kit.      CAUTION MUST BE TAKEN NOT 
                    
                    Summary of the content on the page No. 14 
                    
                          C. DRAFT REGULATORS:    Note: Do not use with Direct Vent application.    A draft regulator is supplied with the furnace and should be installed according to the regulator  manufacturers recommendations. With the burner operating, use a draft gauge to adjust the regulator to  the proper setting. (refer to the instructions enclosed with draft regulator to adjust to the proper setting).  When the burner air supply and draft are properly adjusted, the over fire draft should be a negative (-).01" 
                    
                    Summary of the content on the page No. 15 
                    
                          1. Supply and return air ducts have to be furnished by the installer and run between the appliance,  which must be installed outdoors, and the interior of the structure the appliance serves. These ducts  must be sealed to the casing of the appliance.     2. To reduce the transmission of vibration and noise to the duct system and to reduce flexure of the duct  system due to thermal expansion and contraction, it is recommended that flexible joints be installed at  the supply and return duct conn
                    
                    Summary of the content on the page No. 16 
                    
                          g. Using the selected air flow rates for each component of the duct system and manufacturer’s  literature, or published literature on duct system pressure drops, the pressure drop for each  component in the duct system can be estimated.     The ASHRAE Handbook – Fundamentals is an excellent source of duct system design principles  and pressure drop data.  Conversely, for a specified type of fitting, it is also possible to determine  the required size or diameter of the component for a specifie
                    
                    Summary of the content on the page No. 17 
                    
                                Table 3: Suggested Duct Sizes for Homes, Quiet Offices, Or Similar Installations  (Based on a 0.1 in. W.G. static pressure drop per 100 ft. of duct.)    7. The supply and return air ducts, or flexible joints, should be carefully secured and sealed to the  appliance housing to prevent air leakage from, or into, the duct system. For best performance,  insulate the outside surfaces of the ducts to reduce heat loss from, or heat gain to, the ducts.     8. As a final step in the installation,
                    
                    Summary of the content on the page No. 18 
                    
                            SIZING THE DUCT WORK FOR A COMBINATION HEATING AND COOLING SYSTEM:  Two formulas must be used in determining the CFM requirements of a combustion heating and cooling  system.    1. HEATING CFM:      HEAT OUTPUT OF FURNACE (BTUH)      1.1 X TR (TEMPERATURE RISE, °F) = HEATING(CFM)        EXAMPLES:      A. 110,000 BTUH OUTPUT           1.1 X 85°F TR = 1176 CFM FOR HEATING        B. 110,000 BTUH OUTPUT           1.1 X 70°F TR = 1429 CFM FOR HEATING    2. COOLING CFM: 400 CFM X COOLING TONNAGE (
                    
                    Summary of the content on the page No. 19 
                    
                          Connect the return air plenum to the filter rack and slide the filter into place.  Dimensions for adapting the  return air plenum to the filter rack are provided (See Fig. 10a & 10b).    Fig. 10a: A typical filter rack and dimensions for the OH6 furnace.                  Fig. 10b: A typical filter rack and dimensions for the OH8 furnace.      : Failure to comply with minimum filter installation requirements may affect the  performance and/or void the warranty on this unit.    If a method other
                    
                    Summary of the content on the page No. 20 
                    
                             Maximum   Filter Type Air Velocity Model Number  (ft/min)  OH6 OH8  *Thermo Products  600 384 in² 480 in²  Supplied Permanent  Standard  500 461 in² 576 in²  Permanent  Disposable 300 768 in² 960 in²    Table 4: Minimum Required Filter Area (in square inches)    * The Thermo Products supplied filter can be cut to size to fit other filter retention systems as  long as the maximum air velocity is not exceeded.    NOTICE: Any internal stiffeners used in the filter must not be removed, although