Resumo do conteúdo contido na página número 1 
                    
                        KBXII-SER Rev F
Service Manual
Models:  400 - 801   
This manual must only be used 
 WARNING
by a qualified heating installer / 
service technician. Read all 
instructions, including this manual 
and the Knight XL Installation and 
Operation Manual, before installing.  
Perform steps in the order given.  
Failure to comply could result in 
severe personal injury, death, or 
substantial property damage.
Save this manual for future reference.                                                       
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        Contents 2.  MAINTENANCE CONTENTS ........................................................................ 2 Maintenance and Annual Startup ................................ 27-32 Hazard Definitions .............................................................. 2 3.  TROUBLESHOOTING PLEASE READ BEFORE PROCEEDING ........................ 3 Before Troubleshooting .................................................... 33 Handling Ceramic Fiber Materials ...................................... 3 Check C
                    
                    Resumo do conteúdo contido na página número 3 
                    
                                                                Service Manual    Please read before proceeding Installer – Read all instructions,  When calling or writing about the boiler   WARNING  NOTICE including this manual and the Knight  – Please have the boiler model and serial  XL Installation and Operation Manual,  number from the boiler rating plate. before installing.  Perform steps in the  Consider piping and installation when  order given. determining boiler location (see the Knight  User – This manual i
                    
                    Resumo do conteúdo contido na página número 4 
                    
                                                        Service Manual Please read before proceeding When servicing boiler – � To avoid electric shock, disconnect electrical supply   before performing maintenance. � To avoid severe burns, allow boiler to cool before   performing maintenance. Boiler operation – � Do not block flow of combustion or ventilation air to   the boiler. � Should overheating occur or gas supply fail to shut off,   do not turn off or disconnect electrical supply to   circulator.  Instead, shut o
                    
                    Resumo do conteúdo contido na página número 5 
                    
                                                        Service Manual What is in this manual? Service Maintenance � Service and maintenance schedules Near boiler piping � Address reported problems � Typical system components � Inspect boiler area and boiler interior � Clean condensate trap The Knight XL display � Check all piping for leaks � Display panel readout, buttons and their functions � Check air openings � Flue vent system and air piping Control module inputs � Check water system � Control module inputs and op
                    
                    Resumo do conteúdo contido na página número 6 
                    
                                                        Service Manual 1  Service Near boiler piping This piping reference is included to specify the Near Boiler Piping specific to the Knight XL.  This piping scheme is important  for proper operation of the SMART SYSTEM control.  See the Knight XL Installation and Operation Manual for more detailed  piping diagrams. DOMESTIC HOT WATER PUMP DIRT SEPARATOR   INDIRECT SYSTEM SENSOR  DOMESTIC HOT WATER SYSTEM PUMP      TANK Y-STRAINER (RECOMMENDED) BOILER PUMP TO FLOOR    
                    
                    Resumo do conteúdo contido na página número 7 
                    
                                                        Service Manual 1  Service (continued) The Knight XL display NAVIGATION DIAL The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the  NAVIGATION dial (in the center): MENU = Left SELECT Key SETPOINTS = NAVIGATION Dial - Pressing Down SHDN = Right SELECT Key     7                                                                                                                                                  
                    
                    Resumo do conteúdo contido na página número 8 
                    
                                                        Service Manual 1  1  Service Service  Control inputs SYSTEM PUMP SPEED CONTROL GAS PRESSURE SWITCH DHW THERMOSTAT ROOM THERMOSTAT / ZONE CONTROL LOW VOLTAGE  CONNECTION FLOW SWITCH BOARD SYSTEM SENSOR OUTDOOR SENSOR SEQUENCER / BUILDING MANAGMENT SYSTEM LOW WATER CUTOFF O-TEMP HEAT EXCHANGER SWITCH INLET TEMPERATURE SENSOR OUTLET TEMPERATURE / HI-LIMIT SENSOR FLUE GAS SENSOR AIR PRESSURE SWITCH LOUVER PROVING SWITCH FLAME SENSOR BLOCKED DRAIN SWITCH SMART CONTROL 
                    
                    Resumo do conteúdo contido na página número 9 
                    
                                                        Service Manual 1  1  Service Service (continued) Control outputs ALARM BELL LOW VOLTAGE  LOUVER RELAY CONNECTION BOARD RUN TIME CONTACTS BUILDING MANAGEMENT  SYSTEM BOILER PUMP SYSTEM PUMP DHW PUMP IGNITOR BLOWER SMART CONTROL MODULE GAS VALVE DISPLAY PANEL PC INTERFACE 9                                                                                                                                                                                                    
                    
                    Resumo do conteúdo contido na página número 10 
                    
                                                        Service Manual 1  1  Service Service  Access modes General Operation How the boiler operates User The user can adjust space heating and tank target temperatures  The Knight XL uses an advanced stainless steel heat  by pressing the NAVIGATION dial when “ SETPOINTS” is  exchanger and an electronic control module that allows  flashing at the bottom of the display. The date and time, and  fully condensing operation. The blower pulls in gas and air  the temperature un
                    
                    Resumo do conteúdo contido na página número 11 
                    
                                                        Service Manual 1  1  Service Service (continued) Table 1-1 Sequence of Operation OPERATION DISPLAY 1. Upon a call for heat, the gas pressure switch(es) must be closed.  2. Once the gas pressure switch(es) are closed, the control turns  on the appropriate pumps (system and boiler pumps for space  heating, DHW pump for DHW).  The flow switch and/or LWCO  must close. 3. The control turns on power to the louver relay.  The louver  proving switch, air pressure switch, 
                    
                    Resumo do conteúdo contido na página número 12 
                    
                                                        Service Manual 1  1  Service Service  Table 1-1 (continued from previous page) Sequence of Operation OPERATION DISPLAY 8. If the space heating call for heat is active, and the tank thermostat  or sensor starts a DHW call for heat, the boiler will switch to the  DHW mode.  If programmed for normal DHW operation (not as  a zone), the DHW pump will turn on first, then the boiler pump  will turn off (boiler and DHW pump operation briefly overlap to  ensure flow is mai
                    
                    Resumo do conteúdo contido na página número 13 
                    
                                                        Service Manual 1  1  Service Service (continued) Display panel menu access Table 1-2 Use this procedure to access menus from the display panel SCREEN  BUTTON OPERATION DISPLAY STATUS [SHDN] Press the RIGHT SELECT soft key [SHDN]. [YES] Press the LEFT SELECT soft key [YES]. Press and hold the LEFT SELECT soft key [MENU]   [MENU] for five (5) seconds. Rotate the NAVIGATION dial clockwise until 5 is  displayed (first digit on the left). Press the NAVIGATION dial to s
                    
                    Resumo do conteúdo contido na página número 14 
                    
                                                        Service Manual 1  1  Service Service Display panel parameter access Table 1-3 This is a typical example of accessing a parameter, shown for parameter Temperature Settings, MIN  SH Setpt SCREEN  BUTTON OPERATION DISPLAY STATUS This example shows how to access parameter Temperature Settings.  The first display shown is at the beginning  of the menu listings, after entering the installer access code. Rotate the NAVIGATION dial counterclockwise until  the arrow (>) is
                    
                    Resumo do conteúdo contido na página número 15 
                    
                                                        Service Manual 1  1  Service Service (continued) Parameter table Table 1-4 This table lists SMART SYSTEM control module parameters and where to access them See User Access Installer Access Menu Description Page Display Modify Display Modify Time and Date 18 Yes Yes Yes Yes Software Version (read only) 18 No No Yes No Temperature Units (ºC/ºF) 18 Yes Yes Yes Yes SH Night Setback Offset 18 No No Yes Yes SH Night Setback On Times 18 No No Yes Yes SH Night Setback Off
                    
                    Resumo do conteúdo contido na página número 16 
                    
                                                        Service Manual 1  1  Service Service  Parameter table  Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where  to access them User Access Installer Access See  Menu Description Page Display Modify Display Modify Outdoor 1 Low 21 No No Yes Yes Outdoor 1 High 21 No No Yes Yes Set Point 1 at Low Outdoor Temp 1 21 No No Yes Yes Set Point 1 at High Outdoor Temp 1 21 No No Yes Yes Outdoor Air Shutdown SH1 21 No No Yes 
                    
                    Resumo do conteúdo contido na página número 17 
                    
                                                        Service Manual 1  Service (continued) Parameter table  Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where  to access them User Access Installer Access See  Menu Description Page Display Modify Display Modify Controlling Sensor 23 No No Yes Yes BMS Tstat Input 23 No No Yes Yes BMS 23 No No Yes Yes ModBus 23 No No Yes Yes ModBus T/O 23 No No Yes Yes Cascade Address 23 No No Yes Yes Cascade Type 23 No No Yes Yes
                    
                    Resumo do conteúdo contido na página número 18 
                    
                                                        Service Manual 1  Service Viewable and changeable control parameters Before changing parameters, note the Space Heating (SH) and Domestic Hot Water (DHW)   CAUTION settings so that the unit can be returned to  Night Setback On Times its original operating parameters. This is the time in which the SH Night Setback Offset becomes  active.  There are 7 start times and 7 stop times each for the  General space heating and DHW night setback features.  Both may be  Time 
                    
                    Resumo do conteúdo contido na página número 19 
                    
                                                        Service Manual 1  Service (continued) To save any changes and return to the Home Screen, press 3-Way Valve Time the RIGHT SELECT [HOME] key.  To return to the Status  The optional Lochinvar Multi-Temperature Loop Control  Screen without saving the changes, press the LEFT SELECT  Board (MTLCB) can be used to control the supply temperature   [EXIT] key. up to three (3) sub-loops, corresponding to each of the three  (3) SH set points, through the use of 3-way mixing 
                    
                    Resumo do conteúdo contido na página número 20 
                    
                                                        Service Manual 1  Service Freeze Protection Burner Differential Once this timer expires, it will switch back to the DHW demand.   The installer can adjust the length of time the boiler will service  Once the burner has started firing due to a low inlet  the space heating demand by accessing SH/DHW Switching  temperature, the inlet temperature must increase by this  Time parameter.  The minimum setting is 0 minutes and the  amount before the burner turns back off.