                        Installation and Operation Instructions Docyment 1246
Installation and Operation 
Instructions for
BRUTE MAGNUM
Modulating Boiler 
Model BRHHH
Modulating Water Heater
Model BRHHV
U.S. Patent No. 6,644,393
Canada Patent Pending
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, 
qualified in hot water boiler and heater installation and maintenance. Improper installation and/or 
operation could create carbon monoxide gas in flue gases which could cause
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        Page 2 BRADFORD WHITE CORP.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        Brute Magnum Page 3 Table of Contents 5.5.3 Offset .............................................................26 SECTION 1  5.5.4 Throttling Range ............................................26 General Information 5.5.5 Minimum Output Setting ................................ 27 1.1 Introduction ......................................................5 5.5.6 Integration Constant ......................................27 1.2 Model Identification ..........................................5 5.6 Mixing
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        Page 4 BRADFORD WHITE CORP. List of Tables Table 1 Clearances ........................................................6 Table 4 Required Combustion Air Piping Material..........9 Table 2 Vent / Air Pipe Sizes ..........................................7 Table 5 Required Venting Material .................................9 Table 3 Horizontal Vent and Air Terminals Table 6 Gas Piping Sizes .............................................13  for Indoor Installations .....................................
                    
                    Resumo do conteúdo contido na página número 5 
                    
                        Brute Magnum Page 5 improper installation. Section 1 The Brute Magnum appliance is protected  GENERAL INFORMATION against over pressurization. A pressure relief valve is  fitted to all appliances. It is installed inside the jacket,  USING THIS MANUAL – Because the Brute  at the water outlet of the unit. (See Sections 4A and 4B  Magnum Boilers and Brute Magnum Water  for instructions on how to install a relief valve outlet.) Heaters are identical appliances, with the exception  of materials of ma
                    
                    Resumo do conteúdo contido na página número 6 
                    
                        Page 6 BRADFORD WHITE CORP. (13) Revision appliance should be chosen with regard to the vent   2 = Second version pipe lengths and external plumbing. The unit shall be  (14) Heat Exchanger installed such that the gas ignition system components   E = Glass-lined steel with copper tubes are protected from water (dripping, spraying, rain, etc.)   F = Glass-lined steel with cupronickel tubes during operation and service (circulator replacement,  (15) Control Option Code control replacement, etc.). W
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        Brute Magnum Page 7 “V” “A” “W” “G” Gas Connects. Vent Outlet Air Inlet Water Control Packages Size Connection Connection Inlet/ Outlet “B” Std & A B & E B & E Connection Nat/ LP Nat LP inches inches NPT NPT NPT NPT inches 1200 6 6 2-1/2” 1’ 1-1/2’ 1-1/2” 34-1/4” 1600 6 8 2-1/2” 1-1/2’ 2” 2’ 34-1/4” 2000 7 8 3” 1-1/2’ 2” 2” 34-1/4” 2400 10 8 3” 1-1/2” 2” 2” 32” Figure 1. Dimensional Drawing. Size Intake Exhaust Intake Exhaust   Size Size Maximum Run Maximum Run  1200 6" (15 cm) dia. 6" (15 cm) d
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        Page 8 BRADFORD WHITE CORP. 2.1.2 Intake Combustion Air Section 2  The combustion air can be taken through the  VENTING AND COMBUSTION AIR wall, or through the roof.  When taken from the wall,  it must be taken from out-of-doors by means of the  2.1 Combustion Air horizontal wall terminal, shown in Table 3. See Table 2  Brute Magnum boilers and water heaters must  to select the appropriate diameter air pipe. When taken  have provisions for combustion and ventilation  from the roof, a field-suppl
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        Brute Magnum Page 9 A condensate drain is built into the Brute  Term Description Magnum. A pressure switch monitors the condensate  Pipe Single-wall galvanized steel pipe, 24 gauge  drain pan, and will trip if the condensate level gets too  minimum (sized per section 1.9) high. This will prevent the Brute Magnum from firing  Joint Permanent duct tape or aluminum tape if there is a blockage or overflow. Sealing  Connect a clear plastic tube, minimum 3/8"  Insulation Not required, but recommended 
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        Page 10 BRADFORD WHITE CORP.   U.S. Installations (see note 1) Canadian Installations (see note 2) A= Clearance above grade, veranda, porch,  12 inches (30 cm) 12 inches (30 cm)   deck, or balcony B= Clearance to window or door that may be  4 feet (1.2 m) below or to side of opening;  36 inches (91 cm)   opened 1 foot (30 cm) above opening C= Clearance to permanently closed window See note 4 See note 5 D= Vertical clearance to ventilated soffit located   above the terminal within a horizontal  Se
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        Brute Magnum Page 11 1. The figure in this addendum shows the wall horizontal vented gas fueled equipment. It  requirements for mechanical vent terminal shall be the responsibility of the property owner  clearances for the U.S. and Canada. to secure the services of qualified licensed  2. Vent terminals for condensing appliances or professionals for the installation of hard-wired  appliances with condensing vents are not carbon monoxide detectors. permitted to terminate above a public walkway,  a
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        Page 12 BRADFORD WHITE CORP. (c) MANUFACTURER REQUIREMENTS – side wall. Consider the following when installing the  terminal: GAS EQUIPMENT VENTING SYSTEM  1. Do not locate the air inlet terminal near a source  PROVIDED. When the manufacturer of  of corrosive chemical fumes (e.g., cleaning fluid,  Product Approved side wall horizontally  chlorine compounds, etc.) vented gas equipment provides a venting  2. Locate the terminal so that it will not be subject  system design or venting system compon
                    
                    Resumo do conteúdo contido na página número 13 
                    
                        Brute Magnum Page 13 At the time of removal of an existing boiler, the as determined using the appropriate tables  following steps shall be followed with each appliance and guidelines in the National Fuel Gas Code,  remaining connected to the common venting system ANSI Z223.1 NFPA 54 and/or CSA B149.1,  placed in operation, while the other appliances Installation Codes. remaining connected to the common venting system are  not in operation. 1. Seal any unused openings in the common venting  Sect
                    
                    Resumo do conteúdo contido na página número 14 
                    
                        Page 14 BRADFORD WHITE CORP. 7. All threaded joints should be coated with to a drain or in a manner to prevent injury in the event  piping compound resistant to action of liquefied of pressure relief. Install an air purger, an air vent,  petroleum gas. a diaphragm-type expansion tank, and a hydronic  8. The appliance and its individual shutoff valve flow check in the system supply loop. Minimum fill  must be disconnected from the gas supply piping pressure must be 12psig (82.7kPa). Install shuto
                    
                    Resumo do conteúdo contido na página número 15 
                    
                        Brute Magnum Page 15 medium is piped in parallel with the boiler with  Section 4B appropriate valves to prevent the chilled medium from  WATER CONNECTIONS —   entering the boiler. BRUTE MAGNUM WATER HEATER The boiler piping system of a hot water heating  boiler connected to heating coils located in air  handling appliances where they may be exposed to  4B.1 Water System Piping — refrigerated air circulation must be equipped with flow   Water Heater control valves or other automatic means to prev
                    
                    Resumo do conteúdo contido na página número 16 
                    
                        Page 16 BRADFORD WHITE CORP. Figure 4. Hydronic Piping - Multiple Boilers. tube erosion. For extremely soft or hard water, cupro- 4B.3 Water Flow Requirements — nickel tubes are available. Contact a Bradford White   Water Heater Representative if you have questions or concerns about  In a water heating application (an open system),  water quality. new water is constantly being introduced. With the  The Brute Magnum water heater has an internal  new water comes a fresh supply of minerals that can
                    
                    Resumo do conteúdo contido na página número 17 
                    
                        Brute Magnum Page 17 Figure 5. Hydronic Piping — Multiple Boilers (Alternate). If the water at the inlet of the copper heat directly to the outlet of the Brute Magnum, and there  exchanger is less than 140°F (60°C), water from the will be a 20-25°F (11-14°C) temperature rise between  outlet of the copper heat exchanger will be directed the inlet and outlet of the unit, when the unit is at high  back to the inlet of the copper heat exchanger, and will fire. mix to bring the inlet water up to 140°
                    
                    Resumo do conteúdo contido na página número 18 
                    
                        Page 18 BRADFORD WHITE CORP. Figure 6. Hydronic Piping — One Boiler, Multi-Temperature System. water used for space heating. 4B.4 Combined Water (potable) Heating  This water heater when used to supply potable  and Space Heating water shall not be connected to any heating system  NOTE: These systems are not allowed in the  or component(s) previously used with a non-potable  Commonwealth of Massachusetts. water heating appliance. Piping and components connected to this water  When the system requ
                    
                    Resumo do conteúdo contido na página número 19 
                    
                        Brute Magnum Page 19 4B.5 Freeze Protection – Water Heater Brute Magnum heaters are not designed to be  placed outdoors, due to the potential for condensate to  freeze in the unit. Power outage, interruption of gas supply, failure  of system components, activation of safety devices,  etc., may prevent a heater from firing. Any time a  heater is subjected to freezing conditions, and the  heater is not able to fire, and/or the water is not  able to circulate, there is a risk of freezing in the  he
                    
                    Resumo do conteúdo contido na página número 20 
                    
                        Page 20 BRADFORD WHITE CORP. Figure 8. Water Heater Piping — One Heater, One Tank.