                        Service & Parts Manual
2007
Compact Programmable
Models
CP14N10
CP18N30
CP24N30
CP-14-18-24-Svc-Prts-07 (3-07)                                                                                                                                                                                                                                                                                                                                                                                                      
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        Table of Contents Performance Data ........................................................................................................................................................................ 3 Outer Component Identifi cation ................................................................................................................................................... 4 Installation Dimensions .........................................................................................
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        Specifi cations and Technical Parameters Model CP14N10CP18N30CP24N30 Function COOLING COOLING COOLING  Rated Voltage 115V ~ 230/208V~ 230/208V~  Rated Frequency 60Hz  60Hz 60Hz  Total Capacity (Btu/h) 14000 18000/17600 23500/23100 Power Input (W) 1430 1850/1810 2740/2710 Rated Input (W) 1540 2478 3538 Rated Current (A) 15 12.57 18.09 Air Flow Volume (CFM) (H) 458.8 458.8 617.6 Dehumidifying Volume (pints/h) 3.38 4.65 8.46 EER / C.O.P BTU/W.H) 9.8 9.7/9.7 8.6/8.5 Energy Class / / /  Fan Type-Piece
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        Outer Component Identifi cation Models: CP14N10, CP18N30, CP24N30 Cabinet Air inlet louver Front grille Front intake grille Air filter Power cord (behind front intake grille) Control panel cover 4                                                                                                                                                                                                                                                                                                                 
                    
                    Resumo do conteúdo contido na página número 5 
                    
                        Installation Dimensions Models: CP14N10, CP18N30, CP24N30 (Top View) Fence / obstruction Over 2' Over Over 1' 1' Wall Or window (Front View) (Side View) Ceiling Over 1' 25.98" Over 1' 16.85" Over 2' Less than 8.66" 5                                                                                                                                                                                                                                                                                            
                    
                    Resumo do conteúdo contido na página número 6 
                    
                        Wiring Diagrams CP24N30 CP18N30 / CP14N10 6                                                                                                                                                                                                                                                                                                                                                                                                                                                                         
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        Functional Component Defi nitions MECHANICAL COMPONENTS HERMETIC COMPONENTS Vent door  Allows introduction of fresh air into the room and/or Compressor  Motorized device used to compress refrigerant  exhausts stale room air outside (on select models.) through the sealed system. Plenum assembly  Diffuser with directional louvers used to direct Check valve  A pressure-operated device used to direct the fl ow  the conditioned airfl ow. of refrigerant to the proper capillary tube, during either the hea
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        Refrigeration System Sequence of Operation A good understanding of the basic operation of the refrigera- In the case of the capillary tube this is accomplished (by design)  tion system is essential for the service technician. Without this  through size (and length) of device, and the pressure difference  understanding, accurate troubleshooting of refrigeration system present across the device.  problems will be more diffi cult and time consuming, if not (in some  Since the evaporator coil is unde
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        Sealed Refrigeration System Repairs IMPORTANT ANY SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.   ALSO, ANY SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER. EQUIPMENT REQUIRED HERMETIC  COMPONENT REPLACEMENT cont’d  1. Voltmeter 6. Pressurize system to 30 PSIG with proper refrigerant and boost  refrigerant pressure to 150 PSIG with dry nitrogen.  2. Ammeter  7. Leak test complete system with electric halogen 
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        Refrigerant Charging NOTE: BECAUSE THE RAC SYSTEM IS A SEALED SYSTEM,  METHOD OF CHARGING SERVICE PROCESS TUBES WILL HAVE TO BE INSTALLED.  The acceptable method for charging the RAC system is the  FIRST INSTALL A LINE TAP AND REMOVE REFRIGERANT  Weighed in Charge Method.  The weighed in charge method is  FROM SYSTEM. MAKE NECESSARY SEALED SYSTEM  applicable to all units. It is the preferred method to use, as it is the  REPAIRS AND VACUUM SYSTEM.  CRIMP PROCESS TUBE  most accurate. LINE AND SOLD
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        Refrigerant Charging UNDERCHARGED REFRIGERANT SYSTEMS An undercharged system will result in poor performance (low low charge, however, frosting and thawing can also be caused by  pressures, etc.) in both the heating and cooling cycle. insuffi cient air over the evaporator. Whenever you service a unit with an under charge of refrigerant, Checks for an undercharged system can be made at the compressor  always suspect a leak. The leak must be repaired before charging . If the compressor seems quiete
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        Refrigerant Charging RESTRICTED REFRIGERANT SYSTEM  A quick check for either condition begins at the evaporator. With  Troubleshooting a restricted refrigerant system can be  a partial restriction, there may be gurgling sounds at the metering  diffi cult. The following proced ures are the more common  device entrance to the evaporator. The evaporator in a partial  problems and solutions to these problems. There are two  restriction could be partially frosted or have an ice ball close to the  type
                    
                    Resumo do conteúdo contido na página número 13 
                    
                        Cooling Only Room Air Conditioners: Troubleshooting Tips Problem Possible Cause Action Check voltage at compressor. 115V & 230V units  Low voltage will operate at 10% voltage variance Set t-stat to coldest position. Test t-stat & replace if  T-stat not set cold enough or inoperative inoperative Hard start compressor. Direct test compressor. If  Compressor hums but cuts off on B10 overload compressor starts, add starting components Compressor  does not run Open or shorted compressor windings Chec
                    
                    Resumo do conteúdo contido na página número 14 
                    
                        Cooling Only Room Air Conditioners: Troubleshooting Tips Problem Possible Cause Action Replace fuse, reset breaker. If repeats, check fuse  Fuse blown or circuit tripped or breaker size. Check for shorts in unit wiring &  components Power cord not plugged in Plug it in Unit does not run System switch in  "OFF" position Set switch correctly Inoperative system switch Test for continuity in each switch position Loose or disconnected wiring at switch or other Check wiring & connections. Reconnect pe
                    
                    Resumo do conteúdo contido na página número 15 
                    
                        Cooling Only Room Air Conditioners: Troubleshooting Tips Problem Possible Cause Action Check operation of unit. Replace overload if system  Overload inoperative. Opens too soon operation is satisfactory Allow a minimum of 2 minutes to allow pressures  Compressor restarted before system pressures  to equalize before attempting to restart. Instruct  equalized customer of waiting period Check voltage with unit operating. Check for  other appliances on circuit. Air conditioner should  Low or fl uctua
                    
                    Resumo do conteúdo contido na página número 16 
                    
                        Cooling Only Room Air Conditioners: Troubleshooting Tips Problem Possible Cause Action Ensure that foam gaskets are installed in between  Sublimation:                                   When  window panes & in between the unit & the sleeve.  unconditioned saturated, outside air mixes with  Also, ensure that fresh air/exhaust vents (on  conditioned air, condensation forms on the cooler  applicable models) are in the closed position & are  surfaces in tact Water "spitting"  into room Follow install
                    
                    Resumo do conteúdo contido na página número 17 
                    
                        Heat / Cool Room Air Conditioners: Troubleshooting Tips Problem Possible Cause Action Disconnect power to unit. Remove resistor from t- Heat anticipator (resistor) shorted (on applicable  stat bulb block. Plus in unit & allow to operate. Feel  models) resistor for heat. If not heat, replace resistor Room temperature  uneven  Wide differential - partial loss of t-stat bulb charge Replace t-stat & check (Heating cycle) Refer to appropriate wiring diagram. Resistor is  Incorrect wiring energized du
                    
                    Resumo do conteúdo contido na página número 18 
                    
                        Heat / Cool Room Air Conditioners: Troubleshooting Tips Problem Possible Cause Action Incorrect wiring Refer to applicable wiring diagram Defective solenoid coil Check for continuity of coil Unit cools when heat  Block condenser coil & switch unit to cooling. Allow  is called for Reversing valve fails to shift pressure to build up in system, then switch to  heating. If valve fails to shift, replace valve. Inoperative system switch Check for continuity of system switch Problem Possible Cause Acti
                    
                    Resumo do conteúdo contido na página número 19 
                    
                        Components Model CP14N10 19                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         
                    
                    Resumo do conteúdo contido na página número 20 
                    
                        Model CP14N10 No Description Qty Friedrich Part# Code 1 Supporter Assy 1 67700200 2 Screw ST4.2X13 7 67700154 3 Window locking bracket 2 67700113 4 Screw 4X20 6 67700151 5 Seal strip 1 1 67700128 6 Seal strip 2 1 67700129 7 Curtain Assemby Left and Right 1 67700201 8 Right  Curtain  1 67700202 9 Left  Curtain  1 67700203 10 Cabinet Assy 1 67700204 11 Screw ST4.2X6.5 6 67700155 12 Screw M4X8 1 67700149 13 Connect cord 1 67700170 14 Screw M4X5 1 67700205 15 Washer 4 1 67700158 16 Screw ST4.2X22 4