                        Service & Parts Manual
2005
Room Air Conditioners
50 & 60 Hz Models
SH15L30-A
SH20L30-A
SH20L50-A
HG-SVC-PRTS-05 (4-05)                                                                                                                                                                                                                                                                                                                                                                                             
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        TABLE OF CONTENTS PAGE  Specifi cations ...................................................................................................................................3    Performance Data ............................................................................................................................ 3  Component Operation & Testing ...................................................................................................... 4  Compressors ................................
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        3 Performance Data: Cooling EVAPORATOR AIR EVAPORATOR OPERATING R-22 BREAKER  ELECTRICAL RATINGS TEMP. DEG. F TEMP. DEG. F PRESSURES REF. FUSE CONDENSER  Discharge Suction Liquid Super Sub- Evap Motor  TEMP. Locked  Temp Temp Temp Heat Cooling CFM RPM Discharge Temp. Amps Amps Charge 60 Hertz  DEG. F E(in) E(out) Suction Discharge Rotor  Air Drop F. Cool Heat in OZ. Amps Amps 60 Hz Models SH15L30-A 54 26 52 56 206 129 61 108 16 98 76 258 8.2 - - 28.5 363 1100 15 SH20L30-A 46 34 46 46 125 196 52 
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        COMPONENT OPERATION AND TESTING FIGURE 2  COMPRESSOR WINDING TEST WARNING DISCONNECT ELECTRICAL POWER TO THE  UNIT BEFORE SERVICING OR TESTING COMPRESSORS Compressors are single phase, 208/230 volt.  All  compressor motors are permanent split capacitor  type, using only a running capacitor across the start  and run terminal. All compressors are internally spring mounted and  Testing Procedures externally mounted on rubber isolators. 1. Terminal "C" and "S" - no continuity - open  Line Voltage Ov
                    
                    Resumo do conteúdo contido na página número 5 
                    
                        GROUND TEST FAN MOTOR (Figure 4) Use an ohmmeter set on its highest scale.  Touch one A 230 volt single phase permanent split capacitor motor  is used to drive the evaporator blower and condenser  lead to the compressor body (clean point of contact,  fan.  A running capacitor is wired across the start and  as a good connection is a must) and the other probe  run terminals of the motor. in turn to each compressor terminal.  (See Figure 3.)   If a reading is obtained, the compressor is grounded  T
                    
                    Resumo do conteúdo contido na página número 6 
                    
                        SYSTEM CONTROL SWITCH (Figure 6) CAPACITOR – TEST 1. Remove the capacitor from the unit. This switch is double pole, single throw. Check for  continuity between terminals 2 and 3, and 5 and 6. 2. Check for visual damage such as bulges, cracks,  or leaks. 3. For dual rated capacitors, apply an ohmmeter lead  to the common (C) terminal and the other probe to  FIGURE 6  SWITCH, ON-OFF the compressor (HERM) terminal.  A satisfactory  capacitor will cause a defl ection on the pointer,  then gradually 
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        TEST Remove the wires from the thermostat.  Turn the Note:  The temperature must be within the range listed  thermostat to its coldest position.  Check to see if to check the thermostat.  Refer to the troubleshooting  there is continuity between the two terminals.  Turn the section in this manual for additional information on  thermostat to its warmest position.  Check continuity  thermostat testing. to see if the thermostat contacts open. 7                                                       
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        LOW AMBIENT BYPASS VALVE (Figure 9) SEALED REFRIGERATION SYSTEM  REPAIRS The HazardGard unit is designed to operate at low  outside ambient temperatures.  This is accomplished by  EQUIPMENT REQUIRED: the use of a bypass valve installed in the refrigeration  circuit.  The valve is connected between the discharge  1. Voltmeter line at the compressor and the suction process tube.   The valve responds to suction pressure which, when 2. Ammeter reduced in the system, causes the valve to open and  3. 
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        HERMETIC COMPONENT REPLACEMENT  NOTE: This procedure can be sped up by the  The following procedure applies when replacing  use of heat lamps, or by breaking the vacuum  components in the sealed refrigeration circuit or  with refrigerant or dry nitrogen at 5,000 microns.   repairing refrigerant leaks.  (Compressor, condenser,  Pressure system to 5 PSIG and leave in the sys- evaporator, capillary tube, refrigerant leaks, etc.) tem a minimum of 10 minutes. Recover refriger- 1. Recover the refriger
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        ROTARY COMPRESSOR SPECIAL REFRIGERANT CHARGE TROUBLESHOOTING AND SERVICE 1. The refrigerant charge is extremely critical.  Measure  the charge carefully and as exactly as possible to  Basically, troubleshooting and servicing rotary com- the nameplate charge. pressors is the same as on the reciprocating compres- sor with only a few exceptions. 2. The correct method for charging the rotary is to  introduce liquid refrigerant into the high side of the  1. Because of the spinning motion of the rotar
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        TROUBLESHOOTING PROBLEM POSSIBLE CAUSE TO CORRECT Power disconnected. Check power source. System switch in “Off”  Set switch correctly. position. Replace fuse, reset breaker.  If repeats, check fuse  Branch circuit fuse blown or  or breaker size. Check for shorts in unit wiring and  circuit breaker tripped. UNIT DOES NOT RUN. components. Inoperative system switch. Test for continuity.  Loose or disconnected wiring Check wiring and connections.   at switch. Connect per wiring diagram. Inoperative
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        TROUBLESHOOTING  (Continued) PROBLEM POSSIBLE CAUSE TO CORRECT Compressor attempts to start  Allow a minimum of two (2) minutes to allow pressures to  before system pressures are  equalize before attempting to start. equalized. Check voltage with unit operating.  Check for other  Low or fl uctuating voltage. appliances on the circuit.  Unit should be on separate  COMPRESSOR  circuit for proper voltage, and be fused separately. ATTEMPTS TO  Incorrect wiring. Connect per wiring diagram. START, OR R
                    
                    Resumo do conteúdo contido na página número 13 
                    
                        TROUBLESHOOTING  (Continued) PROBLEM POSSIBLE CAUSE TO CORRECT Defective switch (On-Off). Check continuity across terminals 2 and 3. Check by substituting a known good capacitor of the  Fan capacitor open. same rating. Inoperative fan motor. Direct test fan motor. FAN MOTOR DOES  NOT RUN. Incorrect wiring of fan circuit. Connect per wiring diagram. Relay open. Replace Relay. Check for seized motor bearings. Rotate by hand, add oil, if noisy, replace. Bound fan blade or blower wheel. Adjust for p
                    
                    Resumo do conteúdo contido na página número 14 
                    
                        WIRING DIAGRAM MODELS SH15L30-A, SH20L30-A, SH20L50-A 14                                                                                                                                                                                                                                                                                                                                                                                                                                                            
                    
                    Resumo do conteúdo contido na página número 15 
                    
                        HAZARDGARD CABINET PARTS   15                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       
                    
                    Resumo do conteúdo contido na página número 16 
                    
                        HAZARDGARD CHASSIS PARTS    16                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      
                    
                    Resumo do conteúdo contido na página número 17 
                    
                        HAZARDGARD  PARTS LIST  REF DESCRIPTION PART NO# MODELS CODE ELECTRICAL PARTS 1 COMPRESSOR 61193549 1 600 1 COMPRESSOR 61193550 1 600 1 COMPRESSOR 61193565 1 600 2 MOTOR, FAN 618714261110 2 MOTOR, FAN 61871427 1110 2 MOTOR, FAN 61871450 1110 5 SWITCH, ON-OFF DPST 60935300 1 1 1 130 * INSULATOR, ELECTRICAL 61829700 1 1 1 399 * RELAY, SOLID STATE 61108800 2 2 2 399 6 THERMOSTAT 61825502 1 1 1 120 7 CAPACITOR 20/7.5  440 V. 61080546 1 1 1 150 7 CAPACITOR 25/7.5  440 V 61080547 1 1 1 150 * HARNESS, 
                    
                    Resumo do conteúdo contido na página número 18 
                    
                        HAZARDGARD  PARTS LIST  REF DESCRIPTION PART NO# MODELS CODE CHASSIS PARTS 26 SHROUD, CONDENSER 618036011720 26 SHROUD, CONDENSER 61804901 11 720 27 BRACE, COND.SHROUD 61802600 33 3 722 22 FAN BLADE, COND. 605420031710 22 FAN BLADE, COND. 60542004 11 710 23 BLOWER WHEEL, EVAP. 606106161700 23 BLOWER WHEEL, EVAP. 60610617 11 700 30 SCROLL 618149051743 30 SCROLL 61817505 11 743 29 BLOWER FRONT 618173001742 29 BLOWER FRONT 61817400 11 742 35 PLENUM ASSEMBLY 61831005 11 1 753 17 DECORATIVE PANEL 618
                    
                    Resumo do conteúdo contido na página número 19 
                    
                        19                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  
                    
                    Resumo do conteúdo contido na página número 20 
                    
                        Use Factory Certifi ed Parts. FRIEDRICH AIR CONDITIONING CO. Post Office Box 1540 · San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212 (210) 357-4400 · FAX (210) 357-4480 www.friedrich.com HG-SVC-PRTS-05 (4-05) Printed in the U.S.A.