                        DUAL MOTOR PACKAGED TERMINAL AIR CONDITIONERS INSTALLATION, OPERATION, AND MAINTENANCE MANUAL P/N# 240004146, Rev. 1.7 [02/07] Shipping Damage MUST be Reported to the Carrier IMMEDIATELY!!! Examine the exterior. Remove cover and examine compressor and piping for signs of damage.  SAFETY INSTRUCTIONS This manual is intended as an aid to qualified service  personnel for proper installation, operation, and mainte-  Read all instructions before using the RetroAire   nance of the RetroAire  Dual Motor
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        TABLE OF CONTENTS MODIFICATION AND TAMPERING Warnings and Precautions ..................................... 2-3 DANGER !  !   The Dual Motor PTAC Family ................................... 4 Controls and Components ........................................ 4 Tampering with the RetroAire Dual Motor PTAC is  Preparation for Installation  ....................................... 5 dangerous and may result in serious injury or death.   Electrical Wiring  ...............................................
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        The RetroAire Dual Motor PTAC is available in nominal  THE DUAL MOTOR PTAC FAMILY sizes of 9,000 Btuh, 12,000 Btuh, 15,000 Btuh, and 18,000  Btuh.*  With energy efficiency ratings as high as 10, the  The RetroAire Dual Motor PTAC is available as a cooling- replacement of worn out and inefficient units is a very at- only model or, for those who wish to up-grade to a heat  tractive option. pump, the RH10, 20, 35, 45, 80, and 90 heat pump chassis  will fit the existing wall sleeve.  The heat pump vers
                    
                    Resumo do conteúdo contido na página número 5 
                    
                        WARNING  WARNING !  !  !   !   Moving parts can cause personal injury. Exercise  The correct condenser air baffles must be properly  all due caution when test running the chassis. installed or performance will be impaired and/or the  warranty will be voided!! See individual unit installation instructions for more  PREPARATION FOR INSTALLATION information. IMPORTANT: RetroAire Dual Motor PTACs are to be used  with metal wallsleeves. The sleeves must employ front  panels secured by screws that prev
                    
                    Resumo do conteúdo contido na página número 6 
                    
                        INSTALLATION INSTRUCTIONS RC/RH10 REPLACEMENT PTAC 5. Apply one piece of 1/2” x 1/2” open cell polyfoam to top fl ange  Install  of evaporator block off (See illustration at left). 1/2” x 1/2”  Foam Tape 6. Apply 2” x 1 1/2” open cell foam strips around supply air  duct to ensure that all the conditioned air is delivered into  the room. Failure to do so results in recirculation of the  conditioned air around the wall sleeve and through the unit  causing the unit to short cycle and coils to freez,
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        INSTALLATION INSTRUCTIONS RC11 REPLACEMENT PTAC 6. Apply 2” x 1 1/2” open cell foam strips around supply air  duct to ensure that all the conditioned air is delivered  1/2 34 ” into the room. Failure to do so results in recirculation of  3/4 39 ” the conditioned air around the wall sleeve and through  the unit causing the unit to short cycle, thus raising  1/8 14 ” operating costs through improper heating and cooling  (Figure A2). Figure B2 7. 1” x 1” Open  Wall Sleeve cell foam strips  1/4 30 ”
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        INSTALLATION INSTRUCTIONS RC12 REPLACEMENT PTAC IMPORTANT: If adjoining room conditioning is required, the  RC12 is able to discharge to the right and left by utilizing  the four-inch knockouts (Figure B3) on either side of the  evaporator compartment using 4” flex duct. 3. Once confident that all seals are the correct size and in  the proper location and the correct baffles are attached  to the condenser coil and in the proper orientation, slide  unit into final position and tighten any tie down bo
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        INSTALLATION INSTRUCTIONS RC/RH20 REPLACEMENT PTAC ADJUSTABLE WEATHER SEAL ANGLE POSITIONS Two sets of baffles are provided in your kit to accommodate   (1) (2) mounting brackets in either position A or B. A 8 5/8” 7 7/8” 9 11/16” 8”  (1) (2) B 9 1/2” 10 1/4” 8 7/16” 10 1/8”  NOTE: Dimensions calculated without foam gaskets Figure A4 Figure B4 (1) Standard position-Factory installed (2) Position for Climate Master 702 and 703. REMOVEABLE  WEATHER SEAL  ANGLES 5 1/2” 4” 35 15/16” 3” 22” CONDENSER 
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        RC/RH20 INSTALLATION INSTRUCTIONS (Continued) 6. 1” x 1” Open cell foam strips  are provided to prevent  outside air from entering around the chassis to the room Hydronic Only: Remove the 2-position connector as- from the sides and top of the cabinet. Install between sembly from kit bag supplied with unit (this will have 2  yellow wires attached). Connect this 2-position connec- wall sleeve and cooling chassis. It is imperative to have  tor to the 2-position connection located on the bottom  a s
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        INSTALLATION INSTRUCTIONS RC21 REPLACEMENT PTAC DIMENSIONS 2. Slide unit out of wallsleeve. MODEL A B C 9-12 20 14” 9 7/8” 10 3/8” 3. Remove baffles from kit bag supplied with unit. 15-18 25 1/4” 10 1/8” 15 3/8” IMPORTANT: The correct condenser air baffles must be  A - OVERALL CHASSIS DEPTH B - CONDENSER SECTION DEPTH installed or performances may be impaired and/or the  C - EVAPORATOR SECTION DEPTH warranty will be voided.  NOTE: Dimensions “A” and “B” are with condenser  recirculation baffles and
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        RC21 INSTALLATION INSTRUCTIONS (Continued) Figure D5 Hydronic Only: Remove the 2-position connector as- Wall Sleeve sembly from kit bag supplied with unit (this will have 2  yellow wires attached). Connect this 2-position connector  to the 2-position connection located on the bottom of the  control box panel.  To Connect Aquastat:  Front View A. Remove the black jumper wire located on the bot- tom panel of the control box (this is also terminated  Cooling Chassis with a 2-position connector). 1 
                    
                    Resumo do conteúdo contido na página número 13 
                    
                        INSTALLATION INSTRUCTIONS RC/RH35 REPLACEMENT PTAC 6. Once confident that all seals are the correct size and in  the proper location and the correct baffles are attached  to the condenser coil and in the proper orientation, slide  unit into final position and tighten any tie down bolts or  screws as necessary. Hydronic Only: Remove the 2-position connector as- sembly from kit bag supplied with unit (this will have 2  yellow wires attached). Connect this 2-position connector  to the 2-position conne
                    
                    Resumo do conteúdo contido na página número 14 
                    
                        INSTALLATION INSTRUCTIONS RC/RH45 REPLACEMENT PTAC  3. Slide unit out of wallsleeve and install baffles on the  condenser side. 18.63” 34.50” 4. Remove baffles from kit bag supplied with unit. 16.50” IMPORTANT: The correct condenser air baffles must be  installed or performances may be impaired and/or the  14.07” warranty will be voided.  5. Baffle Installation - Install left and right side baffles on  the condenser coil in existing holes:  5.50” • Choose the proper fitting baffles for your application
                    
                    Resumo do conteúdo contido na página número 15 
                    
                        RC/RH45 INSTALLATION INSTRUCTIONS (Continued) 7. 1” x 1” Open cell foam strips  are provided to prevent 8. Once confi dent that all seals are the correct size and in  outside air from entering around the chassis to the room the proper location and the correct baffl es are attached  from the sides and top of the cabinet (Figure D7). Install to the condenser coil in the proper orientation, slide  between wall sleeve and cooling chassis. It is impera- unit into fi nal position and tighten any tie down
                    
                    Resumo do conteúdo contido na página número 16 
                    
                        INSTALLATION INSTRUCTIONS RC/RH80 REPLACEMENT PTAC Figure A8 Baffl es-Directed Inward  Toward Coil � ���������� ��� � ������ � � �� �� �� �������� ���� �� � � � � 1/2” X 1/2” Supply Air  Air Filter  Duct Foam Tape 8”x30” Permanent  Aluminum Mesh 3. Take 1/2” x 1/2” open cell foam strips from kit bag and  apply to sheet metal fl anges around the perimeter of  the discharge outlet as shown in (Figure A8). Failure  to do so results in recirculation of the conditioned air  around the wall sleeve and t
                    
                    Resumo do conteúdo contido na página número 17 
                    
                        RC/RH80 INSTALLATION INSTRUCTIONS (Continued) 7. Connect line cord.  6. Once confident that all seals are the correct size and in  the proper location and the correct baffles are attached  8. See Final Inspection and Startup on page 20. to the condenser coil and in the proper orientation, slide  unit into final position and tighten any tie down bolts or  screws as necessary. RC/RH80 Performance Date* UNIT COOLING HEAT PUMP FRESH  EER COP Hydronic Only: Remove the 2-position connector as- SIZE BTUH 
                    
                    Resumo do conteúdo contido na página número 18 
                    
                        INSTALLATION INSTRUCTIONS RC/RH90 REPLACEMENT PTAC 3. Baffl e Installation - Remove baffl es from kit bag sup- Install Duct Collar here plied with unit. Install left and right side baffl es on the  condenser coil in existing holes:  • Baffl es must come in contact with the outdoor louver   • Make sure baffl es are directed inward toward the  center of coil  • Secure baffl es tightly to the condenser coil using the  NOTE: CONTROL BOX IS  screws provided (Figure A9) A SEPARATE PART THAT  IS ELECTRICALLY
                    
                    Resumo do conteúdo contido na página número 19 
                    
                        RC/RH90 INSTALLATION INSTRUCTIONS (Continued) 6. Once confident that all seals are the correct size and in  RC/RH90 FINAL INSPECTION  the proper location and the correct baffles are attached  AND START-UP to the condenser coil and in the proper orientation, slide  unit into final position and tighten any tie down bolts or ( All other units see “Final Inspecton and Startup” page 20) screws as necessary. 1. Mount control box in wall sleeve (in the same location  as the old control box) Hydronic Only:
                    
                    Resumo do conteúdo contido na página número 20 
                    
                        FINAL INSPECTION AND STARTUP  CAUTION !  !  discharge air or the return air to the units (i.e., curtains  or drapes that obstruct the air flow or plush carpeting  When the unit is first powered up, high humidity condi- that can obstruct the return air (see below)). Items like  tions can cause condensation to form on the discharge  these can cause serious damage to the chassis and  grill. Keep doors and windows closed to reduce humidity  can void the warranty. and condensation will evaporate. The p