Resumo do conteúdo contido na página número 1 
                    
                        27-0027-0111
June 2, 2008
Rev-01
Installation and Operation 
Manual
72A-196BAREM Series
72A-190BQREM Series
3-Phase Power Monitoring and 
Distribution Unit                                                                                                                                                                                                                                                                                                                                                         
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        27-0027-0111 Installation and Operation Manual Contents Introduction & Safety Information ..............................................3 Technical Specifications ..............................................................4 Declaration of Conformity ................................................................. 5 Connections and Installation  Operating Environment ............................................................... 6  Electrical Connections .....................................
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        27-0027-0111 Installation and Operation Manual Introduction & Safety Information The Spectrum Control PDU is an AC power distribution unit designed to  Introduction distribute power for up to eighteen (18) AC loads.  The PDU distributes 3  phase power to six individual, over current protected, output banks. The  unit has multiple alarm capabilities and includes an audible alarm circuit.   Voltage and current are monitored and displayed locally on a liquid crys- tal display and remotely through a
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        27-0027-0111 Installation and Operation Manual T echnical	Specifications               Global Domestic Input Power Entry IEC 309, 4pole, 5 wire, 32A, NEMA L21-30P Connector WYE connected 5 pin, Delta connected Nominal Input  3 ∅ 400/230VAC ±10% 3 ∅ 208/208VAC ±10% Voltage Input Frequency 50 – 60 Hz 50 – 60 Hz Input Current 72A maximum 41.6A maximum Output              Global Domestic Outlet Connectors (18) IEC C13 (18) IEC C13 Load Current per 16A maximum 13.9A maximum Bank Load Current per 10A 
                    
                    Resumo do conteúdo contido na página número 5 
                    
                        27-0027-0111 Installation and Operation Manual Declaration of Conformity Manufacturer’s Name: Spectrum Power Management Systems, a Spectrum  Control Business Manufacturer’s Address: 1900 West College Avenue State College, PA 16801 Declares that the product: Product Name: 3-Phase Power Monitoring and Distribution Unit Model Number: 72A-196BAREM-01 72A-190BQREM-01 Conforms	to	the	following	Product	Specifications: Safety: UL 60950-1 File E149758-A8 Volume X3, First Edition;  CSA C22.2 No. 60950-1-0
                    
                    Resumo do conteúdo contido na página número 6 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation • Locate PDU in dry area. Operating  Environment • Rack Mount in equipment rack using mounting brackets. • Restricted Access Location not required. • This PDU relies on protective devices in the building installation    for short circuit and over current protection.   • Elevated Operating Ambient- If installed in a closed or multi-unit    rack assembly, the operating ambient temperature of the rack   environment may be g
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation • Depress rocker handle of all circuit breakers to “off” position. Electrical  Connections Example: Breaker Off Example: Breaker On    • Connect input supply cord to a grounded power source rated for    the input voltage and current of the PDU. • Connect equipment to AC output connectors.  Continuous   current draw for all connected units must not exceed the current    rating per output. CAUTION:   • Power source for PDU
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation LAN Module and  Communications RJ45 LAN Connection The LAN Module provides an interface between a computer  LAN Module  network and the power distribution unit using the front RJ-45 jack.    Interface Communications between the PDU and a computer can take place via a  Telnet session or SNMP manager. If you are connecting the PDU directly  to a PC without a router, a crossover cable is required. The module oper- ates at 1
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation The LAN module consists of integrated hardware and a network agent  software	program.		 These	components	provide	the	ability	to	configure,	 control, and monitor aspects of multiple units using a standard web  browser.  The network interface can operate using Telnet and SNMP. The	LAN	module	is	configured	at	the	factory	to	an	IP 	 Address	of	 192.168.1.110 and subnet mask of 255.255.255.0.  A default gateway ad- dress of 1
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation The discovery tool “digi_dev_disc.exe” has the following: Device Discovery 1.	“Configure	Network	Settings”	is	to	configure	the	IP/Subnet/Gateway .	 2. “Restart Device” is to reboot the PDU after assigning the new network      					configuration	. 3. “Refresh View” is to search again.  4. “Open Web Interface” is to launch the web page.    This program is part of the PDU tools and should be placed in  C:\Program Files SCI 
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation Once the IP address is assigned, you should test the IP address  Testing the IP  configuration	to	be	sure	it	works	as	configured.	 Address  Configuration Prerequisite  This	procedure	assumes	that	you	have	configured	the	device	server	with	 an IP address.  Procedure  1. Access the command line of a PC or other networked device.  2. Issue the following command:  ping ip-address (where ip-address    is the address you assig
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation Menu option 8 restores all PDU and LAN module defaults back to the  Set PDU and LAN  factory settings.  This command will ensure that both the LAN module  Module to Factory  and internal PDU microprocessor are returned to identical  Defaults communication	settings.	PDU	with	LAN	modules	should	have	all	configu- ration	changes	made	using	the	LAN	module	configuration	menu	selec- tions. Items that get restored back to defaul
                    
                    Resumo do conteúdo contido na página número 13 
                    
                        27-0027-0111 Installation and Operation Manual Connections and Installation Select	9	to	exit	the	configuration	mode	without	saving	any	changes,	or	 Exit Configuration  select 10 to exit and save all changes.  All values are stored in  Mode nonvolatile RAM.  The LAN Module will automatically reset, but the state  of the PDU outputs will not be affected.  Run “digi_dev_disc.exe” utility to set up unit’s IP, if necessary. These are  LAN Module Reflash  part of the LAN tools. Instructions Locate	the
                    
                    Resumo do conteúdo contido na página número 14 
                    
                        27-0027-0111 Installation and Operation Manual Operational Control of PDU The	unit’ s	LCD	is	used	to	monitor	incoming	power	and	configure	the	 Front Panel Menu software.  The LCD has two modes of operation: Monitor or Menu.  The  system menu is organized in a top down tree structure.  The unit has  four buttons that are used to navigate through the menu system.  The  buttons are labeled with universal symbols for Menu, Select, Left, and  Right	as	shown	in	the	following	figure. MENU - Enters the 
                    
                    Resumo do conteúdo contido na página número 15 
                    
                        27-0027-0111 Installation and Operation Manual Operational Control of PDU Menu Tree Alarm Acknowledgment Incoming Power Peaks Incoming Power Limits System	Configuration None Minimum Current Channel A Minimum Current Channel A Monitor Display Mode Maximum Current Channel A Maximum Current Channel A Display Cycle time Minimum Current Channel B Minimum Current Channel B Voltage Calibration Step 1 Chan A Maximum Current Channel B Maximum Current Channel B Voltage Calibration Step 2 Chan A Minimum Cu
                    
                    Resumo do conteúdo contido na página número 16 
                    
                        27-0027-0111 Installation and Operation Manual Operational Control of PDU CONFIG - CYCLE TIME The CYCLE TIME parameter sets the amount of time to wait before  displaying the next bank measurement.  The parameter can be set to  FAST, MEDIUM, or SLOW. CONFIG - NUMBER OF CHANNELS The	unit	can	be	configured	to	work	for	1,	2,	or	3	power	bank	devices.		 Note that reducing the number of banks to 1 removes the total current  monitoring processes. CONFIG - CONTRAST The CONTRAST feature allows the user to
                    
                    Resumo do conteúdo contido na página número 17 
                    
                        27-0027-0111 Installation and Operation Manual Networking Functions The PDU LAN Port supports the Telnet and SNMP networking functions,  Introduction which allow remote monitoring through the network environment. Table  1 lists the available Telnet commands. Table 2 lists the content of SNMP  functions – Read/Set/Trap in detail. An SNMP Manager PC Tool is need- ed in order to implement the SNMP functions. To implement the Telnet  and	SNMP 	functions,	the	device	must	be	configured	properly ,	such
                    
                    Resumo do conteúdo contido na página número 18 
                    
                        27-0027-0111 Installation and Operation Manual Networking Functions telnet  10001 [space before and after address] Telnet Commands Table 1 List of Commands: Command Description Response @AACK Alarm Acknowledgement #AACK @SYSF Save settings to EEPROM #SYSF OK @BNKV A,? Voltage Bank A #BNKV 120.2 @BNKV B,? Voltage Bank B #BNKV 120.2 @BNKV C,? Voltage Bank C #BNKV 120.2 @BNKC A,? Current Bank A #BNKC 22.5 @BNKC B,? Current Bank B #BNKC 22.5 @BNKC C,? Current Bank C #BNKC 22.5 @BNKC T,? 
                    
                    Resumo do conteúdo contido na página número 19 
                    
                        27-0027-0111 Installation and Operation Manual Networking Functions @BULC B,? Read High Threshold Current Bank B #BULC 22.5 @BULC C,? Read High Threshold Current Bank C #BULC 22.5 @BULC T,? Read High Threshold Current Bank T #BULC 77.5 @BLLV A,? Read Low Threshold Voltage Bank A #BLLV 135.3 @BLLV B,? Read Low Threshold Voltage Bank B #BLLV 135.3 @BLLV C,? Read Low Threshold Voltage Bank C #BLLV 135.3 @BLLC A,? Read Low Threshold Current Bank A #BLLC 10.0 @BLLC B,? Read Low Threshold Current Bank
                    
                    Resumo do conteúdo contido na página número 20 
                    
                        27-0027-0111 Installation and Operation Manual Networking Functions An SNMP-managed network consists of three key components: Simple Network  Management     1. Managed devices Protocol (SNMP)     2. Agents    3. Network Management Systems (NMSs) A managed device is a network node that contains an SNMP agent and  that resides on a managed network. Managed devices collect and store  management information and make this information available to NMSs  using SNMP. Managed devices, sometimes called ne