                        Installation Manual
GEN12AD-V
Generator Systems
Questions? Questio Questio
Help is just a moment away! p is jus p is jus
Call:  Generator Helpline
877-369-9400    
Monday through Friday 8:00 AM to 5:00 PM Central Time
NOT 
FOR 
REPRODUCTION                                                                                                                                                                                                                                                                    
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        Thank you for purchasing this quality-built Rheem / Ruud generator. We are pleased that you’ve placed your confidence in the  Rheem or Ruud brand. When operated and maintained according to the instructions in the operator’s manual, your generator  will provide many years of dependable service. This manual contains safety information to make you aware of the hazards and risks associated with generator systems and  how to avoid them. This generator system is designed and intended only for use as a
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        Table of Contents Important Safety Instructions........................ 4 Installation .................................... 7 Equipment Description.........................................7 Home Owner Responsibilities ...................................7 Installing Dealer/Contractor Responsibilities........................7 Cold Weather Kit .............................................7 Unpacking Precautions ........................................7 Delivery Inspection...........................
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        Save These Instructions Important Safety Instructions  WARNING Running engine gives off carbon monoxide,  an odorless, colorless, poison gas.  SAVE THESE INSTRUCTIONS - This manual contains  Breathing carbon monoxide could result  important instructions that should be followed during  in death, serious injury, headache, fatigue,  installation and maintenance of the generator and batteries. dizziness, vomiting, confusion, seizures, nausea  or fainting. Safety Symbols and Meanings  Operate this pr
                    
                    Resumo do conteúdo contido na página número 5 
                    
                         WARNING Propane and Natural Gas are extremely  WARNING Generator produces hazardous voltage.  flammable and explosive, which could cause  Failure to properly ground generator could result  burns, fire or explosion resulting in death, in electrocution.  serious injury and/or property damage. Failure to isolate generator from utility power could  result in death or serious injury to electric utility   Install the fuel supply system according to NFPA 37 and  workers due to backfeed of electrical e
                    
                    Resumo do conteúdo contido na página número 6 
                    
                         WARNING Exhaust heat/gases could ignite combustibles  CAUTION Installing the 15A fuse could cause the  or structures resulting in death, serious engine to start at any time without warning  injury and/or property damage. Contact with resulting in minor or moderate injury. muffler area could cause burns resulting in  serious injury.  Observe that the 15 Amp fuse has been removed from the   DO NOT touch hot parts and AVOID hot exhaust gases. control panel for shipping.  Allow equipment to cool be
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        Installing Dealer/Contractor Responsibilities Installation         Equipment Description           compatible with the generator. This product is only for use as an optional generator system           which provides an alternate source of electric power and  installation and start-up manual. to serve loads such as heating, refrigeration systems, and  communication systems that, when stopped during any         codes, industry standards, laws, and regulations. power outage, could cause discomfort 
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        Shipment Contents The generator is supplied with: Not Included:                                                                                                                        8 NOT  FOR  REPRODUCTION                                                                                                                                                                                                                                                                                                     
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        Installation Checklist This generator has been installed per the manufacturer’s  instructions: Operation Installing Contractor Signature:  ____________________________      Cold weather kit is installed in temperatures below  40°F (5°C). See Cold Weather Kit. Date: _________________________________________________      Correct battery type is installed and fully charged. See  Carbon Monoxide (CO) Detector/Smoke Detector Final Installation Considerations.       Carbon Monoxide (CO) detector(s) in
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        PAGE LEFT INTENTIONALLY BLANK 10 NOT  FOR  REPRODUCTION                                                                                                                                                                                                                                                                                                                                                                                                                                                             
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        Generator Placement Other General Location Guidelines Before installing generator, consult with home owner and            convey the following requirements, which must be satisfied is flat and has provisions for water drainage. before the installation is complete.           There are two equally important safety concerns in regards to  pump discharge, rain gutter downspouts, roof run-off,  carbon monoxide poisoning and fire. There are also several  landscape irrigation, or water sprinklers will 
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        Placement of Standby Generator to REDUCE THE RISK OF CARBON MONOXIDE POISONING The arrows in the figure below point to POTENTIAL points of entry for Carbon Monoxide Gas. E B C F G D All fossil fuel burning equipment, such as standby such as sta such as stan           generators, contains carbon monoxide (CO) gas in the onoxide (C onoxide (CO as in as in th     B B B - windows engine exhaust. CO gas is odorless, colorless and tasteless dorless, colo dorless, colo ss and tast s and tast    C - doo
                    
                    Resumo do conteúdo contido na página número 13 
                    
                                  parallel to the building or structure. DO NOT direct  STANDBY the generator exhaust towards a potentially occupied  GENERATOR building, structure, windows, doors, ventilation intakes,  soffit vents, crawl spaces, open garage doors or other  openings where exhaust gas could accumulate and  enter inside or be drawn into potentially occupied  building or structure. ENGINE EXHAUST           leaves or debris normally accumulates. Position  standby generator in an area where winds will carry
                    
                    Resumo do conteúdo contido na página número 14 
                    
                        Placement of Standby Generator to REDUCE THE Examples of standby generator locations to  RISK OF FIRE reduce the risk of fire: The National Fire Protection Association (NFPA) standard  Vertical Clearances NFPA 37 establishes criteria for minimizing the hazard  of fire during the installation and operation of stationary  combustion engines. NFPA 37 limits the spacing of an  enclosed generator from openings in walls, structures, and  combustible materials outside the enclosure. Structure The place
                    
                    Resumo do conteúdo contido na página número 15 
                    
                        Single Structure Installations Structure A A 5 ft. (1.5 m) min Exhaust Standby Direction 5 ft. (1.5 m) B Structure A 18 in. (45.7 cm) min 55f 5 ft. (1.5 m) min Standby dby db db 5 ft. (1.5 m) Legend for Generator Locations to reduce the risk of fire: Exhaust Direction   A - Standby weatherproof enclosure must be at least  5 ft. (1.5 m) from windows, doors, any wall opening,  shrubs, or vegetation over 12 inches (30.5 cm)   in height.   B - Exhaust oulet side of weatherproof enclosure  must have 
                    
                    Resumo do conteúdo contido na página número 16 
                    
                        Two Structure Installations Structure A 18 in. (45.7 cm) min 5 ft. (1.5 m) min Standby 5 ft. (1.5 m) Exhaust Direction A B A A S S Structure Struc 18 in. (45.7 cm) min 5f 5f 5f 5 ft. (1.5 m) min t m) min )i Standby Legend for Generator Locations to reduce the risk of  fire: A - Standby weatherproof enclosure must be at  least 5 ft. (1.5 m) from windows, doors, any wall  opening, shrubs, or vegetation over 12 inches  Exhaust 5 ft. (1.5 m) Direction (30.5 cm) in height. B - Exhaust oulet side of w
                    
                    Resumo do conteúdo contido na página número 17 
                    
                        Electrical and Fuel Inlet Locations Lifting the Generator The 3/4 inch N.P.T. fuel inlet connector (A) and electrical   WARNING Hazardous Voltage - Contact with power  inlet location (B) are shown below. lines could cause electric shock or burns,  The home generator is shipped already attached to its  resulting in death or serious injury.  mounting pad. Unless mandated by local code, a concrete Lifting Hazard / Heavy Object - Could result  in serious injury. slab is not required.  If lifting or 
                    
                    Resumo do conteúdo contido na página número 18 
                    
                        To remove side panels: Access Ports 1. Open the control panel access door. Each generator is shipped with a set of identical keys. These  keys fit the locks that secure the access ports. 2. Set generator’s circuit breaker to OFF position. 3. Set control panel system switch to OFF. To open access door: 4. Remove 15 Amp fuse from control panel. 1. Insert key into lock of access door and turn key one  5. Remove roof and divider. quarter turn counterclockwise. 6. Lift latches (B) up on both sides of
                    
                    Resumo do conteúdo contido na página número 19 
                    
                        4. Pull panel (A) up and out of base. A 5. Remove two screws (B) and pull muffler cover off. B 6. Replace muffler cover and exhaust panel in   reverse order. To install side panels: 1. Place panel in grooves and slide down in place. nd slide dow d slide do n plac n place. 2. Push latches down on both sides of panel to lock  both sides both side panel to lock panel to lock into place. 3. Replace divider and roof. 19 NOT  FOR  REPRODUCTION                                                           
                    
                    Resumo do conteúdo contido na página número 20 
                    
                                  The Gaseous Fuel System valve (E) shall be installed in the fuel supply line within  The information below is provided to assist gaseous fuel  6 ft. (180 cm) of the generator. system technicians in planning installations. In no way  should this information be interpreted to conflict with  D applicable fuel gas codes. Consult with your local fuel  C supplier or Fire Marshall if questions or problems arise.  WARNING Propane and Natural Gas are extremely  B flammable and explosive, which