                        DIRECT-VENT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
Patent Pending
NATURAL GAS MODELS
(V)VC42N AND CGCDV42NR SERIES
PROPANE/LP GAS MODELS
(V)VC42P AND CGCDV42PR SERIES
WARNING: If the information in this manual is not fol-
lowed exactly, a fire or explosion may result causing 
property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable 
vapors and liquids in the vicinity of this or any other 
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not tr
                    
                    Resumo do conteúdo contido na página número 2 
                    
                        TALE b OF CONTENTS Safety Information ............................................... 2 Cleaning and Maintenance ................................ 31 Product Identification ........................................... 4 Troubleshooting ................................................. 33 Local Codes......................................................... 5 Replacement Parts ............................................ 37 Product Features ................................................. 5 Service
                    
                    Resumo do conteúdo contido na página número 3 
                    
                        SAFETy INFORMATION  WARNING: This appliance  Continued is only for use with the type of  This fireplace must be installed by a qualified (cer- gas indicated on the rating plate.  tified or licensed) service person. It has a sealed  This appliance is not convertible  gas combustion chamber that uses a coaxial pipe  (pipe within a pipe and having the same center) for use with other gases unless  venting system. It brings in fresh air for combus- a certified kit is used. tion through the outer pipe
                    
                    Resumo do conteúdo contido na página número 4 
                    
                        10. Do not operate fireplace if any log is broken.  SAFETy INFORMATION 11. Do not operate fireplace with glass door  Continued removed, cracked or broken. 1. For propane/LP fireplace, do not place pro- 12. Provide adequate clearances around air  pane/LP supply tank(s) inside any structure.  openings. Locate propane/LP supply tank(s) outdoors.  To prevent performance problems, do not  PRODUCT  use propane/LP fuel tank of less than 100 lbs.  IDENTIFICATION capacity. 2. If you smell gas Upper Louve
                    
                    Resumo do conteúdo contido na página número 5 
                    
                        PRODUCT FEATURES PRE-INSTALLATION  These are a few facts that can help you understand  PREPARATION and enjoy your direct-vent fireplace: LOCATION AND Sp ACE  • The venting system may be routed to the out- REqUIREMENTS side of your home in several ways. It may vent  through the roof (vertical) or it may vent to an Determine the safest and most efficient location  outside/exterior wall (horizontal). The vent for your DESA direct-vent fireplace. Make sure  pipe installation is very important to all
                    
                    Resumo do conteúdo contido na página número 6 
                    
                        CLEARANCES PRE-INSTALLATION  Minimum clearances to combustibles for the  PREPARATION fireplace are as follows: Continued *Back and sides 0"/mm • Your fireplace is designed to be used in zero  Perpendicular walls 6" (152 mm) clearance installations. Wall or framing material  Floor 0"/mm can be placed directly against any exterior sur- Ceiling to louver opening 42" (1067 mm) face on the back, sides or top of your fireplace,  Front 36" (914 mm) except where standoff spacers are integrally  Top of S
                    
                    Resumo do conteúdo contido na página número 7 
                    
                        PRE-INSTALLATION  1 PREPARATION 2 Continued 3 A Wall FRAMING AND FINISHING 4 Figure 4 shows typical framing of this fireplace.  B 5 Figure 5 shows framing for corner installation. All  C 6 minimum clearances must be met. D E 7 For available accessories for this fireplace, see  F Accessories on page 42. If you are using a sepa- G rate combustible mantel piece, refer to Figure 6  Top of Louver  for proper installation height. You can install  Opening noncombustible mantels at any height above the 
                    
                    Resumo do conteúdo contido na página número 8 
                    
                        G V G V A E D V B L LOCATION OF TERMINATION CAP N N H C I Fixed B V V Fixed Closed Openable Closed Openable F B V V J X G B B M A V K X V TERMINATION CAP AIR SUPPLY INLET G GAS METER RESTRICTED AREA X (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or I = clearance to service regulator vent outlet [*72" (182.9 cm)   balcony [*12" (30.5 cm) minimum]  minimum] B =  clearance to window or door that may be opened J = clearance to non-mechanical air supply inlet to building 
                    
                    Resumo do conteúdo contido na página número 9 
                    
                        VENTING INSTALLATION   WARNING: Read all instruc- INSTRUCTIONS tions completely and thoroughly  NOTICE: Read these instruc- before attempting installation.  tions completely before at- Failure to do so could result in  serious injury, property damage  tempting installation. or loss of life. These models are tested and approved for use  with DESA (direct-vent) pipe components and  NOTICE: Failure to follow these in- terminations. structions will void the warranty. The venting system must terminat
                    
                    Resumo do conteúdo contido na página número 10 
                    
                        5. Carefully determine the location where the vent  VENTING INSTALLATION  pipe assembly will penetrate the outside wall.  INSTRUCTIONS The center of the hole should line up with the  Continued center-line of the horizontal vent pipe. Mark the  3 3 wall for a 10 /4" x 10 /4" square hole. Cut and  INSTALLATION LANNING p frame the square hole in the exterior wall where  There are two basic types of direct-vent in- the vent will be terminated. If the wall being  stallation: penetrated is constructed
                    
                    Resumo do conteúdo contido na página número 11 
                    
                        VENTING INSTALLATION  INSTRUCTIONS Apply Mastic to  Continued All Four Sides Vent Cap  WARNING: Do not recess  vent termination into any wall.  This will cause a fire hazard. 6. Noncombustible Exterior Wall: Position the  1 2 horizontal vent cap in the center of the 8 / "	 round hole and attach to the exterior wall with  four wood screws provided. Before attaching  the vent cap to exterior wall, run a bead of Wood Screw non-hardening mastic (pliable sealant) around  Figure 10 - Installing Horizo
                    
                    Resumo do conteúdo contido na página número 12 
                    
                        GROUND FLOOR INSTALLATION VENTING INSTALLATION  Recommended Applications: INSTRUCTIONS • Installation using cabinet surrounds Continued • Through the wall using round or square termina- Minimum Pipe  tion (up to 12" horizontal pipe) Siding Standoff  1 Overlap 1 /4" • NOT FOR CORNER INSTALLATION Direct-Vent  Adjustable  Horizontal  Pipe Screws Pipe 12" Max. 45° Elbow High Wind  Square  Wall  Termination Firestop Wall Firestop Maintain 1"  Minimum Air  High Wind  Space Around  Square Termination T
                    
                    Resumo do conteúdo contido na página número 13 
                    
                        VENTING INSTALLATION INSTRUCTIONS Continued CORNER INSTALLATION Not to Exceed  (H) Limits Recommended Applications: Square  Termination • Corner ground floor installation 90° Elbow • Ground floor installation where pipe vents hori- zontally through wall (over 12" horizontal pipe) • Basement installation where one foot clearance  from ground to termination is possible Wall  90° Elbow 12" Min. Not to Exceed (H) Limits Firestop Square  As Required  Termination  for (V), See  Chart for  45° Elbow Pi
                    
                    Resumo do conteúdo contido na página número 14 
                    
                        VENTING INSTALLATION INSTRUCTIONS Continued HORIZONTAL SYSTEM INSTALLATION  USING TWO 90° ELBOWS The following configurations show the minimum  vertical rise requirements for a horizontal system  using two 90° elbows. 45° Elbow Venting with Two 90° Elbows Horizontal (H ) +  1 Vertical (V) Horizontal (H ) Horizontal (H ) 1 2 5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' max. 20' max. 20' max. 8' max. 20' max. Figure 17 - Horizontal Termination Configuration 
                    
                    Resumo do conteúdo contido na página número 15 
                    
                        Flat Ceiling Installation VENTING INSTALLATION  3 1. Cut a 10 /4" square hole in the ceiling us- INSTRUCTIONS ing the locating hole as a center point. The  Continued 3 3 opening should be framed to 10 /4" x 10 /4"	 (273 mm x 273 mm) inside dimensions, as  INSTALLATION FOR vERTICAL  shown in Figure 9 on page 10 using framing  TERMINATION lumber the same size as the ceiling joists. If  Note: Vertical restrictor must be installed in all  the area above the ceiling is an insulated ceil- vertical ins
                    
                    Resumo do conteúdo contido na página número 16 
                    
                        VENTING INSTALLATION Venting with Two 90° Elbows Horizontal (H ) +  1 INSTRUCTIONS Vertical (V) Horizontal (H ) 2 Continued 5' min. 2' max. 5. Place the flashing over the pipe section(s) 6' min. 4' max. extending through the roof. Secure the base of 7' min. 6' max. the flashing to the roof and framing with roof- 8' min. 8' max. ing nails. Be sure roofing material overlaps the  20' max. 8' max. top edge of the flashing as shown in Figure 19,  page 15. There must be a 1" clearance from  45° Elbow 
                    
                    Resumo do conteúdo contido na página número 17 
                    
                        VENTING INSTALLATION INSTRUCTIONS Continued Vertical Venting V = 40' max. Note: Install  restrictor into  inner collar  of fireplace  as shown. Note: Install  restrictor into  inner collar  of fireplace  as shown. 45° Elbow 45° Elbow Venting with Two 90°  Elbows vertical (v ) Horizontal (H) 1 5' min. 6' max. 6' min. 12' max. 7' min. 18' max. Figure 24 - Vertical Venting Configuration  8' min. 20' max. With No Horizontal Run (Vertical Round  Note: Vertical (V ) + Vertical (V ) = 40' max. 1 2 High
                    
                    Resumo do conteúdo contido na página número 18 
                    
                        Number Description VENTING INSTALLATION  VKR-58 Roof Vent Kit, Galvanized   INSTRUCTIONS  (Includes: 45° Elbow, 7"-12"   Continued  Adjustable Pipe, Flue Restrictor,    Vertical High Wind Termination,  45° Starter  Elbow 2' Pipe, 4' Pipe, Wall Firestop,    Storm Collar, Roof Flashing   [0/12 - 6/12], 26 Screws) VKC-58 Corner Vent Kit, Galvanized   (Includes 45° Elbow, 7"-12"    Adjustable Pipe, Wall Firestop,   12" Extension  Horizontal Termination, 6" Pipe,    90° Elbow, 18 Screws) HHTK-58 High
                    
                    Resumo do conteúdo contido na página número 19 
                    
                        5.  Mount speed control box to switch bracket  FIREPLACE  by placing the plastic control shaft forward  INSTALLATION through the round opening in the switch  bracket (see Figure 27). CHECK GAS TYPE 6.  While supporting speed control, secure control  Use proper gas type for the fireplace unit you are  shaft with lock nut by pushing and turning  installing. If you have conflicting gas types, do not  lock nut with pliers clockwise until it is tight  install fireplace. See retailer where you purchas
                    
                    Resumo do conteúdo contido na página número 20 
                    
                        Variable Fan Switch  Off On 110/115 M Blo otw or er V.A.C. Black Black White White Green 3.  Place the blower against the lower rear wall  FIREPLACE  of the firebox outer wrapper with the exhaust  INSTALLATION port directed upward and the thermodisc  Continued positioned up near the fireplace bottom. The  thermodisc must be oriented near the fireplace  bottom as shown in Figure 29 in order to sense   CAUTION: Never touch the  temperature and properly operate. The blower  blower wheel while in op