2 0 11
Room Air Conditioners
R-410A Models
Cool Only
  
115-Volt: XQ05M10 , XQ06M10 , XQ08M10 , XQ10M10
    
* * * *
Cool with Electric Heat
115-Volt: EQ08M11
*
X-Star-ServMan (1-11) Last character may vary.
*
Service Manual                                                                                                                                                                      
                    
                    ملخص المحتوى في الصفحة رقم 2 
                    
                        Table Of Contents Important Safety Information .......................................................................................................................................... 2-4  Unit Identifi cation ............................................................................................................................................................... 5  Performance Data .............................................................................................................
                    
                    ملخص المحتوى في الصفحة رقم 3 
                    
                                                  IMPORTANT SAFETY INFORMATION The information contained in this manual is intended for use by a qualifi ed service technician who is familiar  with the safety procedures required for installation and repair, and who is equipped with the proper tools and  test instruments required to service this product. Installation or repairs made by unqualifi ed persons can result in subjecting the unqualifi ed person making  such repairs as well as the persons being served by the equipm
                    
                    ملخص المحتوى في الصفحة رقم 4 
                    
                        • Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel,  and sleeve on the room side of the air conditioning unit while cleaning.  • Electrical component malfunction caused by water could result in electric shock or other electrically  unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry.  • Never operate the A/C unit with wet hands. • Use air conditioner on a single dedicated circuit within th
                    
                    ملخص المحتوى في الصفحة رقم 5 
                    
                        PROPERTY DAMAGE HAZARDS FIRE DAMAGE HAZARDS: • Read the Installation/Operation Manual for this air conditioning unit prior to operating. • Use air conditioner on a single dedicated circuit within the specifi ed amperage rating.  • Connect to a properly grounded outlet only. • Do not remove ground prong of plug. • Do not cut or modify the power supply cord. • Do not use extension cords with the unit. • Failure to follow these instructions can result in fi re and minor to serious property damage. WA
                    
                    ملخص المحتوى في الصفحة رقم 6 
                    
                        UNIT IDENTIFICATION Model Number Code   X Q 08 M  1  0  A - A 9th Digit – Engineering Suffi x Indicates Modifi cation (Subject to change) 1st Digit – Function  8th Digit – Marketing Suffi x   E = Electric Heat  Indicates Modifi cation  X = Straight Cool (Subject to change) 7th Digit – Options  0 = Straight Cool  1 = 1 KW Heat Strip, Nominal  2nd Digit   Q = Chassis Size 6th Digit – Voltage  1 = 115 Volts 5th Digit - Model Series / Year Introduced 3rd and 4th Digit - Approximate         M=2010 BTU/HR
                    
                    ملخص المحتوى في الصفحة رقم 7 
                    
                        PERFORMANCE DATA  * R-410A  EVAP. AIR TEMP. DEG. F OPERATING PRESSURES ELECTRICAL RATINGS BREAKER FUSE REF. COOLING CONDENSER  Discharge Temp Suction Temp Super Heat Sub-Cooling Voltage PERFORMANCE DATA** TEMPERATURE DEG. F Temp. Locked Rotor Charge in  Discharge Air Suction Discharge Amps Cool Amps Heat 60 Hertz Amps Drop F. Amps OZ. XQ05M10 57 23 117 133 60 5 19 157 410 4.5 24.0 27.0 115 15 * XQ06M10 54 26 120 152 63 12 18 150 410 4.9 25.0 21.0 115 15 * XQ08M10 51 29 119 160 63 13 25 138 420 6
                    
                    ملخص المحتوى في الصفحة رقم 8 
                    
                        ELECTRICAL DATA WARNING ELECTRIC SHOCK HAZARD  Turn off electric power before service or  installation. All electrical connections and wiring MUST be  installed by a qualifi ed electrician and conform to  the National Electrical Code and all local codes  which have jurisdiction. Failure to do so can result in personal injury or  death. NOTICE FIRE HAZARD Not following the above WARNING could result in fi re or  electically unsafe conditions which could cause moderate  or serious property damage. R
                    
                    ملخص المحتوى في الصفحة رقم 9 
                    
                        WARNING ELECTRICAL SHOCK HAZARD  Make sure your electrical receptacle has the same  configuration as your air conditioner’s plug. If  different, consult a Licensed Electrician. Do not use plug adapters. Do not use an extension cord. Do not remove ground prong. Always plug into a grounded 3 prong outlet. Failure to follow these instructions can result in  electrical shock, serious injury or death. 8                                                                                                   
                    
                    ملخص المحتوى في الصفحة رقم 10 
                    
                        How to operate the Friedrich room air conditioner (XQ models) To start unit Figure5 8 9 2 3 4 1 8 9 2 3 4 1 If your air conditioner is installed and plugged into a proper rec epta c le, it is Figure 3 ready to go. The first time the unit is started, the compressor will delay for three minutes. See Automatic Component Protection on the following page. PM Touch thePower button once. The unit will automatically be inCool X Star 1 PM mode with the temperature set at 75°F (24°C) and the fan speed at 
                    
                    ملخص المحتوى في الصفحة رقم 11 
                    
                        How to use the remote control (XQ models) To start unit To set the timer NOTE: You can set the START and STOP times a minimum of one hour POWER - Press thePower button once. The unit will automatically 1 apart, and a maximum of 23 hours apart. start in the mode and fan speed it was last left on. TIMERSTART - PressStart to view the current start time for cooling. 9 Continue pressing theStart button until you arrive at the start time To set mode of operation you desire. The start time for cooling 
                    
                    ملخص المحتوى في الصفحة رقم 12 
                    
                        ELECTRONIC CONTROL SEQUENCE OF OPERATION MODE CONTROL FAN ONLY MODE The mode control pad(s) allow the selection of the operating When in the FAN ONLY mode, the compressor will not  modes of the unit. operate. The fan will run continuously at the user-selected  speed (see “Fan Speed Set” below). Smart Fan is not  There is a two second delay before the mode activates its  available in FAN ONLY Mode. appropriate relay. FAN SPEED SET OPERATING SEQUENCE / CHARACTERISTICS  XQ fan speed is changed by p
                    
                    ملخص المحتوى في الصفحة رقم 13 
                    
                        FUNCTIONAL COMPONENT DEFINITIONS MECHANICAL COMPONENTS Plenum assembly  Diffuser with directional louvers used  to direct the conditioned airfl ow. Blower wheel  Attaches to the indoor side of the fan motor  shaft and is used for distributing unconditioned, room side  air though the heat exchanger and delivering conditioned  air into the room. Slinger fan blade  Attaches to the outdoor side of the fan  motor shaft and is used to move outside air through the  condenser coil, while slinging condens
                    
                    ملخص المحتوى في الصفحة رقم 14 
                    
                        COMPONENTS TESTING TESTING THE ELECTRONIC CONTROL ERROR CODE LISTINGS   BOARDS FOR XQ MODELS E1 SHORT CYCLE SITUATION: Defi ned as (compressor     powered on before the three minute time delay ten times in   one hour. Investigate and correct short cycling problem.  X Star PM E2 KEYBOARD STUCK ERROR: If key button(s) are  pressed continuously for twenty seconds or more. If MODE  Power key is  stuck, unit will default to cool. Exit Error Code  Cool Mode to see  if error “E2” is no longer displayed 
                    
                    ملخص المحتوى في الصفحة رقم 15 
                    
                        COMPONENTS TESTING (Continued) EQ08 SYSTEM CONTROL SWITCH - TEST 4. Turn thermostat knob counterclockwise to its warmest  position. “EQ08” SYSTEM CONTROL SWITCH – TEST   5. Test for continuity - contacts should be open.  Turn knob to phase of switch to be tested.  There must be   NOTE:  The thermostat must be within the temperature  continuity as follows: range listed to open and close. 1. “Fan Only” Position – between terminals “MS” and “H” To maintain the comfort level desired, a cross ambient
                    
                    ملخص المحتوى في الصفحة رقم 16 
                    
                        COMPONENTS TESTING (Continued) FAN MOTOR A single phase permanent split capacitor motor is used to drive Many motor capacitors are internally fused. Shorting the  the evaporator blower and condenser fan. A self-resetting terminals will blow the fuse, ruining the capacitor. A 20,000  overload is located inside the motor to protect against high ohm 2 watt resistor can be used to discharge capacitors  temperature and high amperage conditions. (See Figure 23) safely. Remove wires from capacitor and 
                    
                    ملخص المحتوى في الصفحة رقم 17 
                    
                        COMPONENTS TESTING (Continued) HEATING ELEMENT (See Figure) DRAIN PAN VALVE  All electric heat models are equipped with  a heating element. During the cooling mode of operation, condensate which   The EQ08 has a 1.15 KW element. collects in the drain pan is picked up by the condenser fan   blade and sprayed onto the condenser coil. This assists  in cooling the refrigerant plus evaporating the water.  Figure Heating Element   During the heating mode of operation, it is necessary that  water be re
                    
                    ملخص المحتوى في الصفحة رقم 18 
                    
                        REFRIGERATION SEQUENCE OF OPERATION  A good understanding of the basic operation of the The refrigerant leaves the condenser Coil through the liquid  refrigeration system is essential for the service technician.  line as a warm high pressure liquid. It next will pass  through  Without this understanding, accurate troubleshooting of the refrigerant drier (if so equipped). It is the function of the  refrigeration system problems will be more diffi cult and time drier to trap any moisture present in
                    
                    ملخص المحتوى في الصفحة رقم 19 
                    
                        R-410A SEALED SYSTEM REPAIR CONSIDERATIONS WARNING Refrigeration system under high pressure Do not puncture, heat, expose to fl ame or incinerate. Only certifi ed refrigeration technicians should  service this equipment. R410A systems operate at higher pressures than  R22 equipment. Appropriate safe service and  handling practicces must be used. Only use gauge sets designed for use with R410A.  Do not use standard R22 gauge sets. The following is a list of important considerations when working wit
                    
                    ملخص المحتوى في الصفحة رقم 20 
                    
                        R-410A SEALED REFRIGERATION SYSTEM REPAIRS IMPORTANT SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.  EQUIPMENT REQUIRED: 9.      High Pressure Gauge - (0 to 750 lbs.)  1. Voltmeter 10. Low Pressure Gauge - (-30 to 200 lbs.)  2. Ammeter  11. Vacuum Gauge - (0 - 1000 microns)  3. Ohmmeter 12. Facilities for fl owing nitrogen through refrigeration tubing    4.   E.P.A. Approved Refrigerant Recovery System during all brazing processes.  5. Vacuum Pump (capa