Inhaltszusammenfassung zur Seite Nr. 1 
                    
                        8
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
V8 SERIES
OIL - FIRED BOILER
As an                                                 
 ENERGY                                  
®
STAR Partner, 
Burnham Hydronics
has determined that the                  
V83S, V83WM, V84S, 
V84WM, V85S, V85WM,
V86S, V86WM and V87
® 
meet  the  ENERGY STAR
guidelines for Energy 
efficiency established by the 
United States Environmental 
Protection Agency (EPA).
For service or repairs to boiler, call your heat
                    
                    Inhaltszusammenfassung zur Seite Nr. 2 
                    
                        IMPORTANT  INFORMATION - READ CAREFULLY All boilers must be installed in accordance with National, State and Local Plumbing, Heating All boilers must be installed in accordance with National, State and Local Plumbing, Heating  a and Electrical Codes and the r nd Electrical Codes and the re egulations of the serving utilities.  gulations of the serving utilities.  T These Codes and Regulations hese Codes and Regulations  may differ may differ  fr fro om this instruction manual.  m this instructio
                    
                    Inhaltszusammenfassung zur Seite Nr. 3 
                    
                        DANGER DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance. WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death. Read and understand all instructions, including all those contained in component manufacturers manuals which are provided with the appliance before in
                    
                    Inhaltszusammenfassung zur Seite Nr. 4 
                    
                        WARNING This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings nor attempt to disconnect any components of this boiler without positively assuring the water is cool and has no pressure. Always wear protective clothing and equipment when installing, starting up or servicing this boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains components which become
                    
                    Inhaltszusammenfassung zur Seite Nr. 5 
                    
                        TABLE 1A:  DIMENSIONAL DATA  (SEE FIGURES 1A THRU 1D) Heat T Heat Transfer ransfer  Dimensions Dimensions  W Wa ater Content - Gallons ter Content - Gallons S Surface Area urface Area  A Approximate pproximate  S See Figures 1A ee Figures 1A - 1D - 1D B Boiler oiler - Sq. Ft. - Sq. Ft. S Shipping W hipping Weight eight  Model No. Model No. (LB.) (LB.) S Steam team W Wa ater ter  S Steam Boiler team Boiler " "A" A" "B" "B" "C" "C" Boiler Boiler Boiler Boiler V82 V82 1 12-1/8" 2-1/8" 6-5/8" 6-5/8"
                    
                    Inhaltszusammenfassung zur Seite Nr. 6 
                    
                        6 Figure 1A: V82 thru V89 Water Boiler without Tankless Heater                                                                                                                                                                                                                                                                                                                                                                                                                                                      
                    
                    Inhaltszusammenfassung zur Seite Nr. 7 
                    
                        7 Figure 1B: V83 thru V89 Water Boiler with Front Tankless Heater                                                                                                                                                                                                                                                                                                                                                                                                                                                   
                    
                    Inhaltszusammenfassung zur Seite Nr. 8 
                    
                        8 Figure 1C: V83 thru V89 Water Boiler with Rear Tankless Heater                                                                                                                                                                                                                                                                                                                                                                                                                                                    
                    
                    Inhaltszusammenfassung zur Seite Nr. 9 
                    
                        9 Figure 1D: V83 thru V89 Steam Boiler with or without Tankless Heater                                                                                                                                                                                                                                                                                                                                                                                                                                              
                    
                    Inhaltszusammenfassung zur Seite Nr. 10 
                    
                        SECTION  I:  PRE-INSTALLATION A. INSPECT  SHIPMENT  carefully for any signs of not level, or if water may be encountered on fl oor  damage. around boiler. 1. All equipment is carefully manufactured, inspected 4. PROVIDE  SERVICE  CLEARANCE of at least  and packed. Our responsibility ceases upon delivery 24” clearance from front jacket panel for servicing  of crated boiler to the carrier in good condition. and removal of front tankless heater (increase to  30" for #A54 heater).  If boiler is equip
                    
                    Inhaltszusammenfassung zur Seite Nr. 11 
                    
                        b. Outdoor air may be provided with the use of two  C. PROVIDE  COMBUSTION  AND  VENTILATION   permanent openings which communicate directly  AIR.   Local and National Codes may apply and should  or by duct with the outdoors or spaces (crawl or  be referenced. attic) freely communicating with the outdoors.  Locate one opening within 12 inches of top  WARNING of space. Locate remaining opening within 12  Adequate combustion and ventilation inches of bottom of space. Minimum dimension  air must be
                    
                    Inhaltszusammenfassung zur Seite Nr. 12 
                    
                        SECTION  II:  KNOCKDOWN  BOILER  ASSEMBLY G. INSTALL  AND  SECURE  CANOPY  with gasket  A. REMOVAL  OF  BARE  BOILER  FROM  SKID and hardware provided to ensure gas tight seal — see  1. Boiler is secured to skid with 4 bolts, 2 in front and  Figure 4. 2 in rear of shipping skid, see Figure 3.  Remove all  bolts. Figure 3:  Knockdown Boiler Removal from Skid 2. Tilt boiler to right and to rear. Using right rear leg  as pivot, rotate boiler 90° in a clockwise direction,  and lower left side of boi
                    
                    Inhaltszusammenfassung zur Seite Nr. 13 
                    
                        Figure 5: Boiler Tapping Locations and Usage (Knockdown Boilers Only) PURPOSE OF TAPPINGS Sr team Boiler Water Boile Tapping Size Location NPT Nr on-Heaterwr /HeateNr on-HeateFr ront Heate Rear Heate Pressure Limit (Probe LWCO) L8148A L8124C A" ¾ Flush Plug Plugged (Float LWCO) Operating Control Operating Control B" ¼ Pressure Gauge Temperature/Pressure Gauge Probe LWCO Std. N/A C" ¾ Plugged (Float LWCO) C" -C ¾Fg lush PlugFA lush Plu N/ Water Gauge Glass (Probe LWCO) D" ½ N/A Water Gauge Glass,
                    
                    Inhaltszusammenfassung zur Seite Nr. 14 
                    
                        Figure 6:  Knockdown Boiler Jacket Assembly H. INSTALL TRIM.  The following steam or water trim   2. Install jacket rear panel support bracket.  (See Figure  will be concealed or inaccessible after boiler jacket is  6, Item 2A).  Align bracket with two (2) 5/16" - 18  installed, see Figure 5 for boiler tapping locations and  tapped holes in rear section and secure with two (2)  usage. 5/16" - 18 x 1/2" long cap screws. 1. STEAM BOILER  — Top tappings: 3. Install jacket rear panel.  (See Figure 6
                    
                    Inhaltszusammenfassung zur Seite Nr. 15 
                    
                        Figure 7:  Oil Burner Installation (Beckett Burner Shown) 6. Install jacket top panel.  (See Figure 6, Item 2F).   2. Locate burner swing door and hinge assembly  Place jacket top panel on boiler and secure to front,  removed in Paragraph I, No. 1.  Check the burner  rear and left side panels with #8 x ½” long sheet  swing door insulation and rope gasket for damage  metal screws. and adhesion.  If damaged, replace insulation or  gasket.  If insulation or gasket is loose, reattach to  7. Install 
                    
                    Inhaltszusammenfassung zur Seite Nr. 16 
                    
                        e. Remove nozzle line electrode assembly. NOTICE f. Remove Beckett MD(V1) or MB(L1) Head. g. Remove plug from nozzle adapter and install  When securing burner swing door make the proper nozzle.  Refer to Table 6 for proper  sure door is drawn-in equally on both sides. nozzle.  The nozzle must be securely installed  Step 3.  Use a hand wrench to tighten door hardware  to assure leak free joints between the nozzle and  and always start with the right side fl ange  adapter.  When installing the nozz
                    
                    Inhaltszusammenfassung zur Seite Nr. 17 
                    
                            Disconnect the fl ared fi tting to the oil line  and remove the aluminum thumb-nut from  the nozzle line.  Remove the combustion  head assembly from the air tube.  Rotating  the assembly upside down will ease  removal.  Inspect the nozzle for size and  type, refer to Table 6 of this manual. ii.   To change a nozzle, loosen the clamp screw  on the retention ring assembly and slide the  retention ring off the adaptor.  Install and tighten the proper nozzle in  the adaptor.  See Table 6 of this m
                    
                    Inhaltszusammenfassung zur Seite Nr. 18 
                    
                        L. INSTALL  CARLIN ELITE EZ OIL  BURNER.   iv. Replace the retention ring assembly, slipping  (See Figure 7). one of the riveted arms through the 1/8-inch  gap between the electrode tips.  This arm  Follow instructions in Paragraph J, Steps 1 through 6. should be straight up.  Also, be sure that  7. Inspect oil nozzle, electrodes and head setting/ the retention ring clamp is tight against the  change fi ring rate. shoulder on the adaptor.  Then tighten the  clamping screw. DANGER v. Check the ele
                    
                    Inhaltszusammenfassung zur Seite Nr. 19 
                    
                        c. Initial Air Band Setting CAUTION i. The nozzle size in GPH INPUT is printed  directly on the air band.  Loosen the locking  Steam boilers must only be operated at the screw, move the air band until the pointer  lower input. Increasing the firing rate on the air shutter and housing lines up with  above this input will result in accelerated the appropriate GPH INPUT.  Tighten the  boiler corrosion and will void the warranty locking screws. provided with the boiler. ii. The Elite burners use cal
                    
                    Inhaltszusammenfassung zur Seite Nr. 20 
                    
                        Figure 7D:  Turbulator Setting iii. Retighten the retaining nut (1).  MODEL F3 NOTE:  Zero and three are scale  Figure 7C:  Nozzle Replacement indicators only.  From left to right the fi rst line is  i. Remove the nozzle adapter (2) from the  3 and the last line 0. drawer assembly by loosening the screw (1).  MODEL F5:  Same as above, except, scale  ii. Remove existing nozzle from nozzle  indicators are 0 and 4. adapter.  MODEL F10:  Same as above, except, scale  iii. Insert the proper nozzle int