Inhaltszusammenfassung zur Seite Nr. 1 
                    
                         E6581741  
 
 
 
 
 
 
 
 
 
 
TOSVERT VF-MB1/S15 
 
®
EtherNet/IP™ - Modbus TCP option  
Function Manual
 
 
IPE002Z
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 NOTICE 
 
1. Read this manual before installing or operating. Keep this instruction manual on hand 
 
of the end user, and make use of this manual in maintenance and inspection.  
 
2. All information contained in this manual will be changed without notice. Please 
 
contact your Toshiba distributor to confirm the latest information. 
 
                    
                    Inhaltszusammenfassung zur Seite Nr. 2 
                    
                         E6581741  Introduction  ® Thank you for purchasing the “EtherNet/IP™ - Modbus TCP option (IPE002Z)” for  ® TOSVERT VF-MB1/S15 inverter. Before using EtherNet/IP™ - Modbus TCP module,  carefully read this function manual in order to completely and correctly utilize its excellent  performance.  This option needs the option adaptor to connect VF-S15 which type form is SBP009Z.  Please match here and buy it when SBP009Z is not at hand yet.  After reading this function manual, please keep it handy f
                    
                    Inhaltszusammenfassung zur Seite Nr. 3 
                    
                         E6581741  Table of Contents    1. OVERVIEW .................................................................................................................................................4  2. NAMES AND FUNCTIONS ........................................................................................................................4  2.1. Outline..................................................................................................................................................4  2
                    
                    Inhaltszusammenfassung zur Seite Nr. 4 
                    
                         E6581741  8.7. "23 (0x17) Read/Write Multiple Registers" function...........................................................................68  8.8. "43 (0x2B) Read Device identification" function ................................................................................69  8.9. Parameter data ..................................................................................................................................71  9. IO SCANNING SERVICE..........................................
                    
                    Inhaltszusammenfassung zur Seite Nr. 5 
                    
                         E6581741  1. Overview  ® The EtherNet/IP™ - Modbus TCP option (IPE002Z) allows the VF-MB1/S15 inverter to be connected  ® into the EtherNet/IP™ - Modbus TCP network.    2. Names and functions  The drawing below shows names and functions of main parts.    2.1. Outline    Connector to the inverter            LED indicator (See  2.4)      MS NS        LNK LNK             MAC address Label   (Back side)   Shielded female RJ45 Shielded female RJ45  EtherNet/IP Connector EtherNet/IP Connector    Rele
                    
                    Inhaltszusammenfassung zur Seite Nr. 6 
                    
                         E6581741  2.2. RJ45 connector pin layout  ® The EtherNet/IP™ - Modbus TCP option is equipped with two shielded RJ45  connectors.  When you use VF-MB1, the shielding is connected to the drive ground. When you use   VF-S15, the shielding is connected to the grounding terminal of option adapter.  Use an STP (shielded twisted pair) Ethernet cable.  The transmission speed is detected automatically by the unit (10 Mbps or 100 Mbps).  The card can operate in half duplex or full duplex mode, whether co
                    
                    Inhaltszusammenfassung zur Seite Nr. 7 
                    
                         E6581741  2.4. LED indicator  MS NS  The LED shows the present     status of the network and module.   LNK LNK           The behavior of LNK LED  Link Activity  Protocol Color and behavior Meaning  EtherNet/IP OFF No link  & Flashing Green/Red Power up testing  Modbus TCP  Green ON Link at 100Mbps  Yellow ON Link at 10Mbps  Green Blink Activity at 100Mbps  Yellow Blink Activity at 10Mbps     The behavior of MS LED  Module Status  Protocol Color and behavior Meaning  OFF No power is supplied to 
                    
                    Inhaltszusammenfassung zur Seite Nr. 8 
                    
                         E6581741  3. Parameters    3.1. Communication parameters   Set up the inverter parameters as follows. It is necessary to reset the inverter to update the parameter.  This option doesn't operate if these parameters are not correctly set.    Communi Factory  Title Function Description  cation No. setting 0: Terminal board  1: Panel keypad (including remote keypad)  cmod 0003 Command mode selection 2: RS485 communication 1  3: CANopen communication  4: Communcation option  0: Setting dial 1 (save 
                    
                    Inhaltszusammenfassung zur Seite Nr. 9 
                    
                         E6581741  Communi Factory  Title Function Description  cation No. setting 0:  -  1  1: fd01 (Status information 1)  2: fd00 (Output frequency, 0.01Hz)  3: fd03 (Output current, 0.01%)  4: fd05 (Output voltage, 0.01%)  5: fc91 (Alarm information)  6: fd22 (PID feedback value, 0.01Hz)  7: fd06 (Input terminal board status)  8: fd07 (Output terminal status)  9: fe36 (VIB input, 0.01%)  10: fe35 (VIA input, 0.01%)  11: fe37 (VIC input, 0.01%)  12: fd04 (Input voltage (DC detection), 0.01%)  13: fd1
                    
                    Inhaltszusammenfassung zur Seite Nr. 10 
                    
                         E6581741  Communi Factory  Title Function Description  cation No. setting This parameter is used to set the protocol of the option  card.  Protocol (*3)  c500  C500 0  0: Modbus TCP (default)  1: EtherNet/IP  This field is used to set the transmission speed and the  transmission mode of the card.  0: Autodetect(default)  c501  C501 Rate Setting (*3) 1: 10Mbps Full 0  2: 10Mbps Half  3: 100Mbps Full  4: 100Mbps Half  This field displays the baud rate and the transmission  mode currently used by 
                    
                    Inhaltszusammenfassung zur Seite Nr. 11 
                    
                         E6581741  EtherNet/IP parameters  Communi Factory  Title Function Description  cation No. setting Monitor of the EtherNet error. -  0: No error/clear error  c536 C536 EtherNet Error 1: Modbus TCP IO Scanning timeout  2: Network overload  3: Loss of Ethernet carrier  Enables web server. 1  c554 C554 Web service (*3) 0: Disable  1: Enable  Monitor the inverter status. -  3: Gate Block  c555 C555 Drive Status  4: Run  23: Fault    Modbus TCP parameters  Communi Factory  Title Function Description 
                    
                    Inhaltszusammenfassung zur Seite Nr. 12 
                    
                         E6581741  3.2. The details of the parameter setting    3.2.1. Device name (c081-c096)  This option module can set the "Device name" of 16 characters.  (Device name (c081-c096) is 1 character within one parameter.)  The device name is required if the option module uses DHCP to obtain its IP Address.    Please set the setting of the device name according to the following rules.  1. The parameter is displayed by the hexadecimal number.   2. One parameter shows an ASCII character.  3. The relation 
                    
                    Inhaltszusammenfassung zur Seite Nr. 13 
                    
                         E6581741  3.2.2. Assigning IP addresses (c504, c505-c516)  The drive needs 3 (4-Modbus TCP) IP addresses.  *The drive IP address.  *The subnet mask.  *The gateway IP address.  (*The IP Master address.- Modbus TCP protocol only)    These parameters are effective settings at c504 = 0 (IP mode: Manual).  If the address has been given by a BOOTP or a DHCP server, these parameters are  invalidity.  • After dynamic addressing by a BOOTP or DHCP server, the new address value is  displayed in the param
                    
                    Inhaltszusammenfassung zur Seite Nr. 14 
                    
                         E6581741  3.2.3. Network error detection (c100 - c103, c523)  ▼Display of trip information  err8 (Optional unit fault 1: 1BH): Network error stop    ▼Related parameter  Title Function Setting range Description  The waiting time from when a network error occurs  can be adjusted. If a network error continues past  the time set in c100, it is recognized as a  communication error and the operation of the  inverter follows the setting of c101.  When normal communication returns during the  setting t
                    
                    Inhaltszusammenfassung zur Seite Nr. 15 
                    
                         E6581741  3.2.4. Command data (c001-c006), Monitor data (c021-c026)  The outline is indicated about the setting item of parameter c001 – c006 and  c021 – c026 in Instance 102/152 and 105/155 of use. Please refer to a  communication functional description for details.    3.2.4.1. How to use Instance 102/152 and 105/155  Instance 102/152 and 105/155 choose a command or the monitor of the driving state by a menu of c001  - c006 and c021 - c026 and can perform the communication that is cyclic of Et
                    
                    Inhaltszusammenfassung zur Seite Nr. 16 
                    
                         E6581741  3.2.4.2. fa06 (Communication command1)    bit Function 0 1 Note  Preset speed  0 operation frequencies  1  Preset speed  0000: Preset speed operation OFF Preset speed operation is  1 operation frequencies  (*1) disabled or preset speed  2   operation frequencies (1-15) are  Preset speed  0001-1111: Setting of preset speed set by specifying bits for preset  2 operation frequencies  operation frequencies (1-15) speed operation frequencies 1-4. 3  Preset speed  3 operation frequencies  4
                    
                    Inhaltszusammenfassung zur Seite Nr. 17 
                    
                         E6581741  3.2.4.3. fa23 (Communication command 2)    bit Function 0 1 Note  0 (Reserved) - - -  Electric power quantity Electric power quantity (fe76,  1 OFF Reset  reset fe77) reset  2 (Reserved) - - -  3 (Reserved) - - -  4 (Reserved) - - -  5 (Reserved) - - -  6 (Reserved) - - -  Maximum deceleration  7 Normal Enabled -  forced stop  Select acceleration/deceleration  Acceleration/decele-  8  00: Acceleration/deceleration 1  1-3 by combination of two bits..  ration selection 1  01: Accelerati
                    
                    Inhaltszusammenfassung zur Seite Nr. 18 
                    
                         E6581741  3.2.4.4. fa07 (frequency reference from internal option)    Frequency reference is set up by 0.01Hz unit and the hexadecimal number.  For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,  80 / 0.01 = 8000 = 0x1F40 (Hex.)    3.2.4.5. fa50 (Terminal output data from communication)    The output data on the terminal board can be directly controlled with the computer.  To use this function, select functions from 92 to 95 in advance for the output te
                    
                    Inhaltszusammenfassung zur Seite Nr. 19 
                    
                         E6581741  3.2.4.7. fd01 (Inverter operating status 1)    bit Function 0 1 Note  Under in  0 Failure FL No output -  progress  Trip status includes rtry and  1 Failure Not tripped Tripped the trip retention status are also  regarded as tripped statuses.  2 Alarm No alarm Alarm issued -  3 Under voltage (moff) Normal Under voltage -  THR1: pt = setting value, vl,  Motor selection (1 or 2) vlv, vb, thr  4 Motor 1 (THR1) Motor 2 (THR2) (THR 2 selection) THR2: pt = 0, f170, f171,  f172, f173  PID co
                    
                    Inhaltszusammenfassung zur Seite Nr. 20 
                    
                         E6581741  3.2.4.9. fd03 (Output current)    The output current is read into 0.01% of units and by the hexadecimal number.   For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal  number) is read out.    Since the minimum unit is 0.01%,  0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)  Also about the following parameters, these are the same as this.  - fd05 (Output voltage (real time))............................................. Unit: 0.01% (V)  - f