Inhaltszusammenfassung zur Seite Nr. 1 
                    
                        Technical Guide Form UTG-0204
Continental Chillers LLC 
 
Phone: 317-337-9813   Fax: 317-337-9816 
 
www.continentalchillers.com 
 
 
™
UniPac  
Single Phase 
 
Air Cooled Chillers 
Water Cooled Chillers 
Split System Chillers 
 
3 through 60 HP 
 
 
 
Shown, model USAC-8  Typical Scroll 
Packaged Air Cooled Chiller with  Compressor 
Factory Mounted Chiller Pump 
 
                                                                                                                                    
                    
                    Inhaltszusammenfassung zur Seite Nr. 2 
                    
                         Continental Single Phase Chillers                              UniPac™    Introducing UniPac™ Chiller Systems    All over the world, Continental has successfully UniPac™ chillers have a full compliment of factory  developed and marketed various packaged and split installed and wired optional accessories. These  chillers to serve many needs. For several years accessories can save several hundreds of dollars in field  discerning Engineers, Contractors, and Owners have labor and material, resultin
                    
                    Inhaltszusammenfassung zur Seite Nr. 3 
                    
                         Continental Single Phase Chillers                              UniPac™    Standard Unit Specifications of UniPac™ Single Phase Chillers       General Description  • Sight glass/ moisture indicator  Continental’s Single Phase Air and Water Cooled Chillers  • Suction line fully insulated, designed for proper oil return at  are packaged systems complete with scroll compressor(s), air  minimum friction loss  cooled or water cooled condenser(s), individual  • Discharge line formed of clean ACR type 
                    
                    Inhaltszusammenfassung zur Seite Nr. 4 
                    
                         Continental Single Phase Chillers                             UniPac™ UniPac™ Options and Selection Procedures 1. Control Transformer - For applications where a separate 115-volt power 14. Copper Tube/Copper Fin Condenser Coil - Seamless copper tube with die  source is not available, a transformer can be installed and wired between the line formed copper fins, mechanically bonded to the tube. Provides maximum protection  voltage power terminal block and the 115-volt control circuit. Transformer
                    
                    Inhaltszusammenfassung zur Seite Nr. 5 
                    
                           Continental Single Phase Chillers                              UniPac™    Single Phase Air Cooled Ratings  Models USAC-3 through USAC-20  3 through 20 Tons  Ambient Air Temperature °F  LCWT Model  85 95 105 115 120  °F USAC  Cooler Cooler Cooler Cooler Cooler  TR kW TR kW TR kW TR kW TR kW  GPM GPM GPM GPM GPM  3 2.6 3.0 6.2 2.3 3.1 5.5 2.1 3.2 5.0 1.8 3.3 4.3 1.6 3.3 3.8  5 4.3 5.0 10.3 3.9 5.2 9.4 3.5 5.4 8.4 3.0 5.5 7.2 2.8 5.8 6.7  40 10 8.6 10.0 20.6 7.8 10.4 18.7 7.0 10.8 16.8 6.0 11.0 
                    
                    Inhaltszusammenfassung zur Seite Nr. 6 
                    
                           Continental Single Phase Chillers                              UniPac™    Single Phase Air Cooled Ratings  Models USAC-25 through USAC-60  25 through 60 Tons    Ambient Air Temperature °F  LCWT Model 85 95 105 115 120  °F USAC  Cooler Cooler Cooler Cooler Cooler  TR kW TR kW TR kW TR kW TR kW  GPM GPM GPM GPM GPM  25 21.5 25.0 51.6 19.5 26.0 46.8 17.5 27.0 42.0 15.0 27.5 36.0 14.0 29.0 33.6  30 25.8 30.0 61.9 23.4 31.2 56.2 21.0 32.4 50.4 18.0 33.0 43.2 17.0 35.0 40.8  40 40 34.4 40.0 82.6 31
                    
                    Inhaltszusammenfassung zur Seite Nr. 7 
                    
                           Continental Single Phase Chillers                              UniPac™    Single Phase Water Cooled Ratings  Models USWC-3 through USWC-60  3 through 60 tons  Condenser Leaving Water Temperature, °F  LCWT Model  85 95 100  °F USWC  Cooler Cond Cooler Cond Cooler Cond  TR kW TR kW TR kW  GPM GPM GPM GPM GPM GPM  3 3.0 3.0 7.2 9.0 2.8 3.0 6.7 8.4 2.6 3.0 6.2 7.8  5 5.0 5.0 12.0 15.0 4.7 5.0 11.3 14.1 4.3 5.0 10.3 12.9  10 10.0 10.0 24.0 30.0 9.3 10.0 22.3 27.9 8.6 10.0 20.6 25.8  15 15.0 15.0 3
                    
                    Inhaltszusammenfassung zur Seite Nr. 8 
                    
                           Continental Single Phase Chillers                              UniPac™    USAC Physical Data     USAC-3, 4, 5, 8                        USAC-10, 12, 15, 20                                                USAC-25, 30                USAC-40, 50, 60    Dimensions Water Connections Est R-22  Model USAC Weight, lbs.  Charge, lbs.  L” W” H” Inlet, MPT” Outlet, MPT”  -3, 4 48 43 53 500/600 ¾ ¾ 9/11  -5, 8 48 43 53 650/900 1 1 12/18  -10, 12, 15, 20 1,100/1,300/1,500  90 43 55 2 2 22/25/30/40 -25, 30 
                    
                    Inhaltszusammenfassung zur Seite Nr. 9 
                    
                           Continental Single Phase Chillers                              UniPac™    USWC Physical Data     USWC-3, 5, 10                                                                                     USWC-15, 20                  USWC-25, 30                       Water Connections,  Dimensions Est R-22  Model USWC Weight, lbs. Inlet”/Outlet”  Charge, lbs.  L” W” H” Condenser Cooler  -3, 5 20 34 48 400/500 ¾ ¾ 7/14  -10 20 34 48 700 1 1 24  -15, 20 48 34 48 900/1,000 1 ½  1 ½  40/55  -25, 30 84 34 4
                    
                    Inhaltszusammenfassung zur Seite Nr. 10 
                    
                           Continental Single Phase Chillers        UniPac™    Electrical Data  USAC Packaged Air Cooled Chillers   Total Unit Compressor Motor Data Condenser Fan Motor Data  Standard Unit Optional Low Ambient Unit  Single Phase/Single Single Phase/Speed  Model  Max Rec. HP RLA LRA MCC  Speed Motor Control  MCA Qty  HP FLA  Fuse Fuse Each Each Each Each  Qty  Each Each  HP RLA HP RLA  Qty Qty  Each Each Each Each  USAC-3 30 45 35 1 3 18.4 95 25.8 1 0.75 5.3 _ _ _ 1 0.75 5.3  USAC-4 33 55 40 1 4 22.1 137
                    
                    Inhaltszusammenfassung zur Seite Nr. 11 
                    
                           Continental Single Phase Chillers                                      UniPac™    Installation and Application Data 4. For multiple units, a minimum lateral clearance of 10 feet between  General  two units is recommended.  Continental UniPac™ Air Cooled Packaged Chillers models USAC    are designed for outdoor installations and normal exposure to summer  Field Piping  and winter conditions. The vertical condenser air discharge feature  1. If a circulating pump is field furnished, the pump mus
                    
                    Inhaltszusammenfassung zur Seite Nr. 12 
                    
                           Continental Single Phase Chillers                                    UniPac™    UniPac™Guide Spec      All power starting and safety/operating controls shall be mounted  Furnish and install where indicated on plans Qty______  in a fully enclosed control panel with access door  Continental UniPac™ model (USAC, USWC) _________  Power controls shall include:  packaged liquid chiller(s).  •   Single point electrical terminal block   The (each) unit shall have a cooling capacity of ______ Tons  wi